Figure 3.2 General sensor function Communication Object
No. | Object Function | Communication Object Name | Data Type | Flags | DPT | ||
672 | Actual temperature | Internal sensor | 2Bytes | C,R,T | 9.001 temperature (℃) | ||
This communication object sends temperature values detected by the device's internal temperature sensor to the bus. -Range: -40 ~ 80℃ | |||||||
673 | Temp.correction (-10…10)℃ | Internal sensor | 2Bytes | C,W | 9.001 temperature (℃) | ||
This communication object corrects the temperature measurement values of the device's internal temperature sensor via the bus. | |||||||
674 | Temp.error report | Internal sensor | 1bit | C,R,T | 1.005 alarm | ||
This communication object is used to send error telegrams of the internal temperature sensor. Its value is defined by the parameters. | |||||||
675 | Temperature | External sensor | 2bytes | C,W,T,U | 9.001 temperature (℃) | ||
This communication object is used to receive temperature measurement values sent from temperature sensors on the bus. -Range: -40~ 80℃ | |||||||
676 | Temp.error report | External sensor | 1bit | C,R,T | 1.005alarm | ||
This communication object is used to send error telegrams of external temperature sensors. Its value is defined by the parameters. | |||||||
677 | Humidity | External sensor | 2bytes | C,W,T,U | 9.007 humidity (%) | ||
This communication object is used to receive humidity measurement values sent from humidity sensors on the bus. -Range: 0 ~100% | |||||||
684 | Actual humidity | Internal sensor | 2Bytes | C,R,T | 9.007 humidity (%) | ||
This communication object is used to send the humidity values detected by the device's internal humidity sensor to the bus. | |||||||
685 | Humidity.error report | External sensor | 1bit | C,R,T | 1.005alarm | ||
This communication object is used to send error telegrams of external humidity sensors. Its value is defined by the parameters. | |||||||
Table 3.2 General sensor function Communication Object Table