--- title: "5.2 Parameter setting interface “General Setting”" slug: "52" updated: 2026-08-20T03:16:24Z published: 2026-08-24T07:27:06Z canonical: "knowledge.akuvox.com/52" stale: true --- > ## Documentation Index > Fetch the complete documentation index at: https://knowledge.akuvox.com/llms.txt > Use this file to discover all available pages before exploring further. # 5.2 Parameter setting interface “General Setting” ## ## 5.2.1 “General setting” ![](https://cdn.document360.io/f09a6106-e976-455e-b2d0-3d88b5385960/Images/Documentation/5.2-image-jnkti9df.png) Figure 5.2.1 “General setting” Interface - **Send delay after voltage recovery [0..15]s** Set the delay time before the device sends telegrams to the bus after power-on reset. Options: 0~15 > [!NOTE] > **NOTE:** > > This delay does not include the device initialization time. Telegrams received during this period are still recorded. - **Send cycle of “In operation ” telegram [1…240s, 0 = inactive]** Set the time interval when this device cycle send telegrams through the bus to indicate this module in normal operation. - When set to “0”, the object “In operation” will not send a telegram. - If the value is not “0”, the object “In operation” will send a telegram with a logic “1” to the bus at the preset time interval. Options: 0~240s, 0 = inactive To minimize the bus load as much as possible, the maximum time interval should be selected according to actual needs. - **Status LED brightness in normal mode** Set the button’s LED brightness level during the day. Options: - 0% - 5% - 10% - 20% - ... - 70% - **Status LED brightness in night mode** Set the button’s LED brightness level during nighttime. Options: - 0% - 5% - 10% - 20% - ... - 70% - **Status LED brightness in standby mode** Set the button’s LED brightness level when the device enters standby mode. Options: - 0% - 5% - 10% - 20% - ... - 70% - **Time for switch to night at: Hours [0...23]** Set the hour the hour when night mode begins. Options: 0~23 - **Time for switch to night at: Minutes** Set the minute when night mode begins. Options: 0~59 - **Time for switch to day at: Hours [0...23]** Set the hour when day mode begins. Options: 0~23 - **Time for switch to day at: Minutes** Sets the minute when day mode begins. Options: 0~59 - **Delay time after no operation for standby mode** Sets the time of inactivity before the panel enters standby mode. Options: 1~255 - **Delay time for turn off indicator screen after standby mode** Set how long the OLED screen remains on after entering standby mode. Options: 1~30 - **Delay time for turn off status LED after standby mode** Sets how long the LED indicators remain on after entering standby mode. When the value is “0”, the LEDs remain on permanently. Options: 0~255, 0=inactive ### ## 5.2.2 “Proximity setting” The Proximity Setting interface, as shown in Figure 5.2.2, configures the proximity sensing feature, including sensor source, detection distance, the telegrams sent when a person approaches or leaves the sensing area, along with the delay time for sending these telegrams. “Approaching” means the built-in sensor detects someone entering the area, and “Leaving” means no presence is detected. ![](https://cdn.document360.io/f09a6106-e976-455e-b2d0-3d88b5385960/Images/Documentation/5.2-image-55rx270b.png) Figure 5.2.2 “Proximity setting” Interface - **Proximity** Enable or disable the proximity sensing feature. Options: - Disable: Turn off proximity sensing, hiding the “Proximity sensor resource” setting. - Enable: Activates proximity sensing. The panel will automatically wake based on the selected sensor source. - **Proximity sensor resource** This setting appears when proximity sensing is enabled and allows you to select the sensor source. Options: - Internal Sensor: Use the panel’s built-in sensor. When selected, the “Proximity sensor resource” and “Object type of output value” settings are shown. - External sensor: Uses an external sensor. When selected, the “Proximity sensor resource” and “Object type of output value” settings are hidden. - **Proximity sensor distance** This setting appears only when the Internal Sensor is selected. It sets the detection range of the built-in sensor. Options: - Short distance: Detect presence within 30cm to wake the screen. - Medium distance: Detect presence within 60cm to wake the screen. - Long distance: Detect presence within 100cm to wake the screen. - **Object type of output value** This setting appears when “Internal Sensor” is selected as the proximity sensor source. This sets the data type of telegrams sent to the bus when a person approaches or leaves the sensing area. Options: - 1bit[On/Off] - 1byte[scene control] - 1byte[0..255] - 1byte[0.100%] - **Reaction for approaching/leaving** Set whether to send telegrams when a person approaches or leaves the sensing area. Options: - No action - Send a value: Enables the following settings for telegram values sent on approach or leave. Note that the available value ranges depend on the selected data type. - Output value[On/Off] - Output scene NO.[1..64] - Output [0..255] - Output value[0..100%] - **Delay time for sending[0..255]** Set the the delay before sending telegrams. Options: 0~255 > [!NOTE] > **NOTE:** > > When the K32 detects an approaching object, it delays sending the “leaving” telegram based on the time set in “General Setting-Delay time after no operation for standby mode”. If the radar is triggered again during this delay, the timer resets. ## 5.2.3 “Internal temperature setting” The Internal Temperature Setting interface, shown in Figure 5.2.3, allows configuration of parameters related to the internal temperature sensor. ![](https://cdn.document360.io/f09a6106-e976-455e-b2d0-3d88b5385960/Images/Documentation/5.2-image-pp14npi4.png) Figure 5.2.3 “Internal temperature setting” Interface This section covers the configuration of filter type, calibration (temperature offset), conditions for sending data, and the cyclic sending interval. - **Filter type** Specify the number of measured values used to calculate the average before sending it to the bus. Options: - Low: Average 4 measurements - Average: Average 16 measurements. - High: Average 64 measurements. - **Temperature offset** Set the calibration value of the internal temperature sensor to match the actual ambient temperature. This only affects the telegram values sent to the bus and does not change the temperature shown on the panel. Options: -5℃~5℃ - **Minimum change of value to send[K] (0 means no value sent on change)** Define the minimum temperature change required to trigger sending a telegram of the current temperature. Options: 0~5 (0 = Do not send on change) - **Send actual Humi. when change by[1..20]** Set the minimum humidity change needed to trigger a telegram of current humidity. Options: 1~20 - **Cyclic sending interval** Specify how often the current temperature value is sent to the bus. Options: 0~120min > [!NOTE] > **NOTE:** > > This cycle starts after device programming or reset and runs independently of value-change triggers.