--- title: "5.4 Parameter Setting Interface “Logic“" slug: "54-l" updated: 2026-08-19T03:14:17Z published: 2026-08-24T07:36:52Z canonical: "knowledge.akuvox.com/54-l" stale: true --- > ## Documentation Index > Fetch the complete documentation index at: https://knowledge.akuvox.com/llms.txt > Use this file to discover all available pages before exploring further. # 5.4 Parameter Setting Interface “Logic“ ![](https://cdn.document360.io/f09a6106-e976-455e-b2d0-3d88b5385960/Images/Documentation/5.4-l-image-f83eviyv.png) ![](https://cdn.document360.io/f09a6106-e976-455e-b2d0-3d88b5385960/Images/Documentation/5.4-l-image-h3b4hqlv.png) Fig.5.4 "Logic function setting" Interface - **1st/2nd/3rd... Logic function** This parameter is for setting the setting interface of logic function, display corresponding logic function page when select. Up to enable 8 logic functions. - **Description for logic function** This parameter is for setting the name description for logic function, up to input 30 characters. - **Function of channel** This parameter is for setting function of the channel. Options: - AND - OR - XOR - Gate forwarding - Threshold comparator - Format convert - Gate function - Delay function - Staircase lighting AND/OR/XOR: The parameters and communication objects are identical; only the logical operation differs. The following uses one option as an example to explain the parameters. ### ## 5.4.1 Parameter Setting Interface “AND/OR/XOR” ![](https://cdn.document360.io/f09a6106-e976-455e-b2d0-3d88b5385960/Images/Documentation/5.4-l-image-zxlzcdhl.png) Fig.5.4.1 "AND/OR/XOR" Interface - **Input a/b/c/d/e/f/g//h** Defines whether logic input Input x participates in the operation normally or participates with its value inverted. Options: - Disconnected: Not connected; does not participate in the operation. - Normal: The input value participates in the operation directly. - Inverted: The input value is inverted before participating in the operation. > [!NOTE] > **NOTE:** > > The initial value is not inverted. - **Default value** Defines the initial value of logic input x. Options: - 0 - 1 - **Result is inverted** Determines whether to invert the logic calculation result. Options: - No: Output directly. - Yes: Output after inverting. - **Read input object value after voltage recovery** Sets whether the device sends a read request to the logic input objects after power recovery or programming. Options: - No - Yes - **Output send when** Defines the condition for sending the logic operation result. Options: - Receiving a new telegram: The logic result is sent whenever a new logic input telegram is received. - Every change of output object: The logic result is sent only when the output value changes. > [!NOTE] > **NOTE:** > > During the first logic calculation, the result is sent even if it does not change. - **Send delay time** Sets the delay before sending the logic result to the bus. Delay = Base×Factor. If Base is set to None, no delay is applied. Base: - None - 0.1s - 1s - ... - 10s - 25s Factor: 1..255 ### ## 5.4.2 Parameter Setting Interface “Gate forwarding“ ![](https://cdn.document360.io/f09a6106-e976-455e-b2d0-3d88b5385960/Images/Documentation/5.4-l-image-ycc8e1c5.png) Fig.5.4.2 "Gate forwarding" Interface - **Object type of Input/Output** This parameter is for setting the object type of input/output. Options: - 1bit - 4bit - 1byte - **Default scene NO. of Gate after startup [1~64,0=inactive]** Sets the default scene that allows logic gate forwarding after the device starts up. The selected scene must be configured in the parameters. Options: - 1..64, 0=inactive > [!WARNING] > **TIP:** > > It is recommended to select a gate scene before operation; otherwise, the initial scene is enabled by default. - **z->Gate trigger scene NO. is [1~64,0=inactive] (z=1~8)** Sets the scene number used to trigger logic gate forwarding. Each logic function supports up to 8 trigger scenes. Options: - 1..64, 0=inactive - **Input A/B/C/D send on** Defines the output(s) to which input X (X = A/B/C/D) is forwarded after gate processing. Options: - Disable - Output A - Output B - ... - Output B,C,D Depending on the selection, one input can be forwarded to one or multiple outputs. The output value is identical to the input value. ### ## 5.4.3 Parameter Setting Interface “Threshold comparator” ![](https://cdn.document360.io/f09a6106-e976-455e-b2d0-3d88b5385960/Images/Documentation/5.4-l-image-otph7ljo.png) Fig.5.4.3 "Threshold comparator" Interface - **Threshold value data type** Defines the data type of the threshold value. Options: - 4bit value (DPT3.007) - 4byte unsigned value [0..4294967295] - 1byte unsigned value (DPT5.010) - Ext. temperature value (DPT 9.001) - 2byte unsigned value (DPT7.001) - Ext. humidity value (DPT 9.007) - 2byte signed value (DPT8.x) - Illuminance value (DPT 9.004) - 2byte float value (DPT9.x) - **Threshold value** Sets the threshold value. The available range depends on the selected data type. Options: - 4bit value (DPT 3.007): 0..15 - 1byte unsigned value (DPT 5.010): 0..255 - 2byte unsigned value (DPT 7.001): 0..65535 - 2byte signed value (DPT 8.x): −32768..32767 - 2byte float value (DPT 9.x): −670760..670760 - 4byte unsigned value: 0..4294967295 - Ext. temperature value (DPT 9.001): −20..95 °C - Ext. humidity value (DPT 9.007): 0..100 % - Illuminance value (DPT 9.004): 0..65535 lux *The parameter is visible only when the data type is 2byte float value (DPT 9.x) or Illuminance value (DPT 9.004).* - **Hysteresis threshold value** Set the hysteresis threshold. Options: 0..500 - **If Object valueThreshold value"** - **Parameter "If Object value<=Threshold value"** - **Parameter "If Object value>=Threshold value"** Define the logical result to be sent when the object input value meets the corresponding condition. When the data type is 2byte float value (DPT 9.x) or Illuminance value (DPT 9.004), only the < Threshold value and > Threshold value options are available. Options: - Do not send telegram: The selected condition is ignored. - Send value "0": - Send value "1" Send value "0"/"1": Sends a telegram with value 0 or 1 when the condition is met. > [!NOTE] > **NOTE:** > > If multiple parameter settings conflict, the value defined by the last matching condition takes priority. > > *Example:* > > If Object value = Threshold value: Send value “0” > > If Object value ≤ Threshold value: Send value “1” > > When the object value equals the threshold, the logical result sent is “1”. - **Output send when** Defines when the logical operation result is sent. Options: - Receiving a new telegram: The logic result is sent each time a new logical input telegram is received. - Every change of output object: The logic result is sent only when the output value changes. > [!NOTE] > **NOTE:** > > During the first logic operation, the result is sent even if the output value does not change. - **Send delay time** Sets the delay before sending the logic result to the bus. Delay = Base×Factor. If Base is set to None, no delay is applied. Base: - None - 0.1s - 1s - ... - 10s - 25s Factor: 1..255 ### ## 5.4.4 Parameter Setting Interface “Format convert“ ![](https://cdn.document360.io/f09a6106-e976-455e-b2d0-3d88b5385960/Images/Documentation/5.4-l-image-l6dyz50i.png) Fig.5.4.4 "Format convert" Interface - **Function** Defines the data format conversion type. Options: - 2x1bit-->1x2bit - 8x1bit-->1x1byte - 1x1byte-->1x2byte - 2x1byte-->1x2byte - 2x2byte-->1x4byte - 1x1byte-->8x1bit - 1x2byte-->2x1byte - 1x4byte-->2x2byte - 1x3byte-->3x1byte - 3x1byte-->1x3byte - **Output send when** Defines when the logical operation result is sent. Options: - Receiving a new telegram: The logic result is sent each time a new logical input telegram is received. - Every change of output object: The logic result is sent only when the output value changes. > [!NOTE] > **NOTE:** > > During the first logic operation, the result is sent even if the output value does not change. ### ## 5.4.5 Parameter Setting Interface “Gate function” ![](https://cdn.document360.io/f09a6106-e976-455e-b2d0-3d88b5385960/Images/Documentation/5.4-l-image-wwza66a1.png) Fig.5.4.5 "Gate function" Interface - **Object type of Input/Output** Defines the data type of the input and output objects. Options: - 1bit[On/Off] - 1byte[0..100%] - 1byte[0..255] - 2byte[Float] - 2byte[0..65535] *The following parameter is visible when "1bit[On/Off]" is selected.* - **Filter function** Defines whether ON or OFF telegrams are filtered. Options: - Deactivate: Not filtering. - On filter out: OFF passes through; ON is blocked. - Off filter out: ON passes through; OFF is blocked. - **Value output** Defines whether the output value is inverted. Options: - Normal - Inverted - **Gate object value** Defines whether the gate object value is inverted before output. Options: - Normal - Inverted - **Gate status after voltage recovery** Defines the gate state after device startup. Options: - Disable - Enable - **Save input signal when gate close** Defines whether input signals are stored while the gate is closed. Options: - No: Input values received while the gate is closed are ignored. - Yes: Input values received while the gate is closed are stored and output when the gate opens (regardless of value change). ### ## 5.4.6 Parameter Setting Interface “Delay function“ ![](https://cdn.document360.io/f09a6106-e976-455e-b2d0-3d88b5385960/Images/Documentation/5.4-l-image-getk3f2g.png) Fig.5.4.6 "Delay function" Interface - **Object type of Input/Output** Defines the data type of the input and output objects. Options: - 1bit[On/Off] - 1byte[0..100%] - 1byte[0..255] - 2byte[Float] - 2byte[0..65535] - **Delay time [0..6500]** Defines the delay time before the input value is forwarded to the output. Options: 0..6500 s > [!NOTE] > **NOTE:** > > If a new input telegram is received during the delay period, the timer is restarted. ### ## 5.4.7 Parameter Setting Interface “Staircase lighting” ![](https://cdn.document360.io/f09a6106-e976-455e-b2d0-3d88b5385960/Images/Documentation/5.4-l-image-00uiww1b.png) Fig.5.4.7 “Staircase lighting" Interface - **Trigger value** Defines the trigger telegram value. Options: - 0 - 1 - 0 or 1 - **Object type of output** Defines the output object type. Options: - 1bit - 1byte - **Duration time of staircase lighting[10..6500]** Defines how long the staircase lighting remains ON after being triggered. Options: 10..6500 s - **Send value 1 when trigger** - **Send value 2 after duration time** Define the output values sent when triggered and after the duration expires. Available options depend on the output object type. 1 bit - OFF - ON 1 byte - 0..255 - **Retriggering** Defines whether the timer restarts when a trigger value is received during the delay period. Options: - Disable - Enable