--- title: "5.8 Parameter Window ”Motion sensor setting”" slug: "58-m" updated: 2026-08-19T02:53:56Z published: 2026-08-24T07:58:29Z canonical: "knowledge.akuvox.com/58-m" stale: true --- > ## Documentation Index > Fetch the complete documentation index at: https://knowledge.akuvox.com/llms.txt > Use this file to discover all available pages before exploring further. # 5.8 Parameter Window ”Motion sensor setting” > [!NOTE] > **NOTE:** > > This function is only supported in database versions 2.0 or above and DCA versions 2.0.0.1 or above. ![](https://cdn.document360.io/f09a6106-e976-455e-b2d0-3d88b5385960/Images/Documentation/5.8-m-image-bmtsx6lm.png) Fig.5.8 “Motion sensor setting” Interface - **Parameter “Number of movement detectors”** This parameter sets the number of movement detectors, up to 8 movement detectors for per output channel. Additionally, each movement detector can link to a brightness sensor. Options: - None - 1 - 2 - ... - 8 ![](https://cdn.document360.io/f09a6106-e976-455e-b2d0-3d88b5385960/Images/Documentation/5.8-m-image-c3h1ocb4.png) ### ## 5.8.1 Parameter Window ”Motion sensor X”(X=1~8) ![](https://cdn.document360.io/f09a6106-e976-455e-b2d0-3d88b5385960/Images/Documentation/5.8-m-image-0de99hwf.png) Fig.5.8.1 “Motion sensor X” Interface - **Parameter “Description (max.30 char)”** This parameter is used to input the sensor name (up to 30 characters). **DALI configuration** - **Parameter “Hold time”** This parameter defines the hold time for presence detection. After this period, the presence status will switch to unoccupied - meaning that if no movement is detected within this time, the area is assumed to be empty. Options: - 1s - 1min - ... - 35min - 40min - **Parameter “Dead time between movement detections”** This parameter defines the dead time between movement detections. The detector will only respond to a new movement after this time has passed since the previous movement ended. Options: - None - 0.1s - 0.2s - 0.5s - 1s - 2s **KNX Configuration** - **Parameter “Type of output”** This parameter sets the type of output. Options: - 1bit - 1byte **- Parameter “Object datatype”** This parameter sets the 1byte object datatype of output. Options: - 1byte percentage value - 1byte unsigned value - Scene number **- Parameter “Behaviour on begin of movement”** **- Parameter “Behaviour on end of movement”** These two parameter set whether send a value when behaviour on begin or end of movement. Options: - No action - Send a value **- Parameter “Value”** This parameter sets the output value when behaviour on begin or end of movement. Options are displayed according to the object datatype. For 1bit, options including: - OFF - ON For 1byte percentage value, options including: - 0% - 1% - ... - 100% For 1byte unsigned value, options including: 0..255 For scene number, options including: - Scene NO.1 - Scene NO.2 - ... - Scene NO.64 **- Parameter “Send telegram when the result change”** This parameter sets whether send a telegram when the result of movement detection change. **- Parameter “Cyclically send telegram [0...255,0=inactive]”** This parameter sets the time for cyclically sending the result of movement detection to the bus. Options: 0..255 min **- Parameter “Disable movement function”** This parameter sets whether enable the disable movement function. Options: - Disable - Disable=1/Enable=0 - Disable=0/Enable=1 - **Parameter “Additional brightness sensor”** This parameter sets whether to enable additional brightness sensor. - **Parameter “Detector depending on brightness”** This parameter is visible when previous parameter is selected to enable. Used to set whether the presence control depending on brightness. When enabled, a following parameter is visible. - **Parameter “Brightness threshold for presence evaluation [1..2000]”** This parameter is visible when previous parameter is selected to enable. Used to set the brightness threshold for evaluating begin of presence. Options: 1..2000 lux The detector will trigger the presence state only if the ambient brightness is below this threshold and motion is detected. ### ## 5.8.2 Parameter Window ”Brightness sensor” This parameter window is visible when additional brightness sensor is is selected to enable. ![](https://cdn.document360.io/f09a6106-e976-455e-b2d0-3d88b5385960/Images/Documentation/5.8-m-image-vizhf1k8.png) Fig.5.8.2 “Brightness sensor” Interface **DALI Configuration** - **Parameter “Dead time between brightness events”** This parameter sets dead time between brightness events, that is, the sensor will respond after this setting time since the end of last brightness detection. Options: - None - 1s - 2s - ... - 10s **- Parameter “Hysteresis value”** This parameter sets hysteresis value of brightness sensor. Options: 0...25 % **- Parameter “Send brightness when the result change by”** This parameter sets when brightness turns to a certain value send the current brightness value to the bus. Options: - 1 lux - 2 lux - .... - 225 lux - 250 lux **KNX Configuration** - **Parameter “Brightness calibration”** This parameter sets the brightness calibration value. Options: -500...500 lux **- Parameter “Threshold value for brightness alarm”** This parameter sets the threshold value for brightness alarm. Options: 5...2000 lux **- Parameter “Hysteresis value for brightness alarm”** This parameter sets the hysteresis value for brightness alarm. Options: - 1 lux - 2 lux - .... - 225 lux - 250 lux **- Parameter “If value < threshold, send”** This parameter sets the out value when brightness value is lower than the value (Threshold value for brightness alarm- Hysteresis value for brightness alarm). Options: - OFF - ON **- Parameter “Cyclically send brightness [0...255,0=inactive]”** This parameter sets the time for cyclically sending the the brightness detection value to the bus to the bus. Options: 0..255 min