--- title: "5.8 Parameter Setting Interface \"Logic\"" slug: "58l" updated: 2026-08-24T07:53:48Z published: 2026-08-24T07:53:48Z canonical: "knowledge.akuvox.com/58l" stale: true --- > ## Documentation Index > Fetch the complete documentation index at: https://knowledge.akuvox.com/llms.txt > Use this file to discover all available pages before exploring further. # 5.8 Parameter Setting Interface "Logic" ## The parameter interface “Logic” (Figure 5.8.1) is used to enable logic functions. A total of 8 logic channels are available. ![](https://cdn.document360.io/f09a6106-e976-455e-b2d0-3d88b5385960/Images/Documentation/5.8l-image-8uu5y2pp.jpg) Figure 5.8.1 "Logic disable/enable" Interface - **Function of channel** Defines the logic function for the selected channel. Options: - Disable - AND - OR - NAND - NOR - XOR - Threshold comparator - Format convert > [!NOTE] > **NOTE:** > > The parameters and communication objects for AND / OR / NAND / NOR / XOR are identical except for the logic operation. The following describes one example. ### ## 5.8.1 “AND/OR/NAND/NOR/XOR” Function ![](https://cdn.document360.io/f09a6106-e976-455e-b2d0-3d88b5385960/Images/Documentation/5.8l-image-mzwani2s.png) Figure 5.8.2 “Logic AND/OR/NAND/NOR/XOR" Interface - **Input a/b/c/d/e/f/g/h** Defines how each input participates in the logic operation. Options: - Disconnected: Input not used. - Normal: Input value used directly. - Inverted: Input value is inverted before processing. - **Default value** Sets the initial value of the input. Options: - 0 - 1 - **Result is inverted** Defines whether the logic result is inverted. Options: - No: Output directly. - Yes: Invert the result before output. - **Read input object value after bus voltage recovery** Defines whether a read request is sent to logic input objects after bus recovery or programming. Options: - No - Yes - **Output send when** Defines when the logic result is sent. Options: - Receiving a new telegram: Sent whenever an input telegram is received. - Every change of output object: Sent only when the result changes. > [!NOTE] > **NOTE:** > > First calculation always sends result even if unchanged. - **Send delay time** Defines the delay before sending the logic result. Delay = Base × Factor. Base options: - None: No delay is applied. - 0.1s - 1s - … - 25s Factor options: - 1...255 ## 5.8.2 “Threshold Comparator” Function ![](https://cdn.document360.io/f09a6106-e976-455e-b2d0-3d88b5385960/Images/Documentation/5.8l-image-64kobpw9.png) Figure 5.8.3 “Logic Threshold Comparator" Interface - **Threshold value data byte** Defines the data type of the threshold. Options: - 4bit - 1byte - 2byte - 4byte - **Threshold value …** Defines the threshold value. The threshold value range is based on the data type. Options: - 4bit: 0...15 - 1byte: 0...255 - 2byte: 0...65535 - 4byte: 0...4294967295 - **If Object value < Threshold value** - **If Object value = Threshold value** - **If Object value ≠ Threshold value** - **If Object value > Threshold value** - **If Object value ≤ Threshold value** - **If Object value ≥ Threshold value** Each condition defines the value to be sent when met. Options: - Do not send telegram: Ignore the parameter with this option and does not include it in the logical operation. - Send value "0" - Send value "1": > [!NOTE] > **NOTE:** > > When the condition is met, a telegram with value 0 or 1 is sent. > > If multiple parameter conditions conflict, the value defined by the last matched condition takes precedence. > > For example, if “If Object value = Threshold value” is set to Send value “0” and “If Object value ≤ Threshold value” is set to Send value “1”, then when the object value equals the threshold, the logic result sent will be “1”. - **Output send when** Defines when the logic result is sent. Options: - Receiving a new telegram: Sent whenever an input telegram is received. - Every change of output object: Sent only when the result changes. > [!NOTE] > **NOTE:** > > First calculation always sends result even if unchanged. - **Send delay time** Defines the delay before sending the logic result. Delay = Base × Factor. Base options: - None: No delay is applied. - 0.1s - 1s - … - 25s Factor options: - 1...255 ## 5.8.3 “Format convert” Function ![](https://cdn.document360.io/f09a6106-e976-455e-b2d0-3d88b5385960/Images/Documentation/5.8l-image-eidm1i5d.png) Figure 5.8.4 "Logic Format convert" Interface - **Function** Defines source and target data format conversion. Options: - 2x1bit --> 1x2bit - 8x1bit --> 1x1byte - 1x1byte --> 1x2byte - 2x1byte --> 1x2byte - 2x2byte --> 1x4byte - 1x1byte --> 8x1bit - 1x2byte --> 2x1byte - 1x4byte --> 2x2byte - 1x3byte --> 3x1byte - 3x1byte --> 1x3byte - **Output send when** Defines when the logic result is sent. Options: - Receiving a new telegram: Sent whenever an input telegram is received. - Every change of output object: Sent only when the result changes. > [!NOTE] > **NOTE:** > > First calculation always sends result even if unchanged.