6.2 Communication Objects of Function Page

Prev Next

6.2.1 "HVAC"

Figure 6.2.1 "HVAC" Function Communication Objects

No.

Object Function

Name

Type

Flag

DPT

168

Input-External temperature

Function x HVAC

2byte

C, W, T, U

9.001 temperature(℃)

This communication object is used to receive temperature measurement values sent from the temperature sensor on the bus. Range: -50~99.8℃

169

Input-Setpoint adjustment

Function x HVAC

2byte

C, W

9.001 temperature  (℃)

When the HVAC operation mode is disabled, this object is used to modify the baseline value of the set temperature.

When the HVAC operation mode is enabled and the set temperature is set to be relative adjustment, this object is used to modify the baseline value of the set temperature. Specifically, it adjusts the temperature setting value of the Comfort mode, while the setting temperature of the Standby and the Economy modes change according to the relative change. In Protection mode, only the protection mode temperature is modified.

When the HVAC operation mode is enabled and the set temperature is adjusted absolutely, this object is used to modify the set temperature value of the current operation mode.

170

Input-Switch Heating Cooling mode

Function x HVAC

1bit

C, W, U

1.100 cooling/heating

This communication object is used to receive status feedback from heaters and coolers on the bus.

The display on the screen will be updated according to the received telegram value.

- Telegram values

1: Heating

0: Cooling

171

Input mode

Function x HVAC

1 byte

C,W

20.102 HVAC mode

172

Input-Comfort mode

Function x HVAC

1bit

C, W

1.003 enable

173

Input-Standby mode

Function x HVAC

1bit

C,W

1.003 enable

174

Input-Economy mode

Function x HVAC

1bit

C, W

1.003 enable

175

Input-Frost/heat protection mode

Function x HVAC

1-bit

C,W

1.003 enable

The operation mode can receive status feedback through either four 1-bit objects (Objects 172, 173, 174, 175) or one 1-byte object (HVAC mode).

  • When using 1bit objects

Object 172: Comfort mode

Object 173: Standby mode

Object 174: Economy mode

Object 175: Frost/heat protection mode

When any of these objects receive a telegram “1”, the corresponding mode will be activated. The mode display status on the screen will also update accordingly.

  • When using 1byte object

Input values and their corresponding operation modes are as follows:

0: Reserved

1: Comfort mode

2: Standby mode

3: Economy mode

4: Frost/heat protection mode

5-255: Reserved, not used

176

Input-Fan speed

Function x HVAC

1 byte

C, W, U

5.001% (0..100%)

203

Input-Fan speed

Function x HVAC

1 byte

C, W, U

5.100 fan stage(0..255)

177

Input-Fan speed low

Function x HVAC

1-bit

C, W, U

1.001 switch

178

Input-Fan speed medium

Function x HVAC

1bit

C, W, U

1.001 switch

179

Input-Fan speed high

Function x HVAC

1-bit

C, W, U

1.001 switch

180

Input-Fan speed off

Function x HVAC

1bit

C, W, U

1.001 switch

The fan speed can receive status feedback through either four 1-bit objects (Objects 177, 178, 179, 180) or one 1-byte object (Fan speed).

  • When using 1bit objects

Object 177: Low fan speed

Object 178: Medium fan speed

Object 179: High fan speed

Object 180: Fan speed off

When any of these objects receive a telegram “1”, the corresponding fan speed will be activated. The fan speed display status on the screen will also update accordingly. When the fan speed is off, the telegram value for all fan speeds must be 0.

  • When using 1byte object

Fan speed status values are defined by parameters. When the object receives the specified value, the fan speed display status on the screen will update to the corresponding fan speed.

181

Input-Fan Automatic operation

Function x HVAC

1bit

C, W, U

1.003 enable

This object is used to receive status feedback from auto control of fan speed.

- Telegram values

1: Auto mode

0: Exit auto mode

182

Output-Instantaneous setpoint

Function x HVAC

2 bytes

C, R, T

9.001 temperature(℃)

This object is used to send the set temperature value of the current operating mode to the bus.

183

Output-Heating/Cooling mode

Function x HVAC

1bit

C, R, T

1.100 cooling/heating

This object is used to send telegrams of switching between heating and cooling functions to the bus.

- Telegram values

1: Heating

0: Cooling

184

Output-HVAC mode

Function x HVAC

1byte

C,R, T

20.102 DPT_HVAC Mode

185

Output-Comfort mode

Function x HVAC

1bit

C,T

1.003enable

186

Output-Standby mode

Function x HVAC

1bit

C,T

1.003enable

187

Output-Economy mode

Function x HVAC

1bit

C,T

1.003enable

188

Output-Frost/Heat protection mode

Function x HVAC

1bit

C,T

1.003enable

These communication objects are used to send telegrams of the operation mode to the bus.

  • When the object type is 1byte

0: Reserved

1: Comfort mode

2: Standby mode

3: Economy mode

4: Frost/heat protection mode

5~255: Reserved, not used

  • When the object type is 1bit

Upon switching to the specific mode, the mode will send a telegram "1" to the bus.

201

Output-Heating/cooling control value

Function x HVAC

1bit

C,T

1.001 switch

202

Output-Heating/Cooling Control Value

Function x HVAC

1 byte

C,T

5.001% (0..100%)

197

Output-Heating control value

Function x HVAC

1-bit

C,T

1.001 switch

198

Output-Heating control value

Function x HVAC

1 byte

C,T

5.001% (0..100%)

199

Output-Cooling control value

Function x HVAC

1-bit

C,T

1.001 switch

200

Output-Cooling control value

Function x HVAC

1 byte

C,T

5.001% (0..100%)

This object sends control values of heating or cooling functions to regulate the HVAC valve, thereby adjusting the indoor temperature.

- Telegram values

Switch on/off use - 2-point control: On/off

Switch PWM - use PI control: On/off

Continuous control - use PI control: 0 ... 100%

189

Output-Fan speed

Function x HVAC

1 byte

C, W, U

5.001 percentage(0..100%)

204

Output-Fan speed

Function x HVAC

1 byte

C, W, U

5.100 fan stage(0..255)

190

Output-Fan speed low

Function x HVAC

1bit

C, W, U

1.001 switch

196

Output-Fan speed medium

Function x HVAC

1bit

C, W, U

1.001 switch

192

Output-Fan speed high

Function x HVAC

1bit

C, W, U

1.001 switch

193

Output-Fan speed off

Function x HVAC

1bit

C, W, U

1.001 switch

These communication objects are used to send control telegrams for fan speed to the bus.

  • When using 1bit objects

Object 190: Low fan speed

Object 196: Medium fan speed

Object 192: High fan speed

Object 193: Fan speed off

Activating the corresponding fan speed on the screen triggers the respective object to send a telegram “1” to the bus, except for the fan speed off telegram, which is “0”.

  • When using 1byte objects

The telegram value of each fan speed level is defined by parameters.

Activating the corresponding fan speed on the screen triggers the Object 189 or 204 to send the specific fan speed value to the bus.

194

Output-Fan Automatic operation

Function x HVAC

1bit

C,T

1.003 enable

This communication object is used to send auto control telegrams for fan speed to the bus.

- Telegram values

1: Auto mode

0: Exit auto mode

191

Input-on/off

Function x HVAC

1bit

C, W, T, U

1.001 switch

195

Output-on/off

Function x HVAC

1bit

C, W, T, U

1.001 switch

This object is used to control the HVAC (Heating, Ventilation, and Air Conditioning) function of the device.

When turning off the HVAC, corresponding controls are deactivated.

206

Scene,in

Function x HVAC

1byte

C, W

18.001 scene control

This communication object is visible when the Scene function is enabled.

It is used to recall scenes via the bus.

205

Error code

Function x HVAC

2 bytes

C, W

8.001 pulses difference

207

Error text

Function x HVAC

14 bytes

C, W

16.001 character string (ISO 8859-1)

208

Failure status

Function x HVAC

1bit

C, W

1.005 alarm

When the Error code function is enabled, the three communication objects become visible.

They are used to display error codes of different data types.

Table 6.2.1 "HVAC" Function Communication Objects Table

6.2.2 "Air conditioner"

Figure 6.2.2 "Air conditioner" Communication Objects

No.

Object Function

Name

Type

Flag

DPT

168

External temperature sensor, In

Function x AC

2 bytes

C, W, T, U

9.001 temperature(℃)

This communication object is used to receive temperature measurement values from the indoor temperature sensor on the bus and display the indoor temperature on the screen.

169

Power on/off,Out

Function x AC

1 bit

C,T

1.001 switch

Power on/off: Send air conditioner power switch telegrams.

170

Status of Power,In

Function x AC

1 bit

C, W, T, U

1.001 switch

This object is visible in Gateway mode and is used to receive feedback of power switch status.

171

Control mode,Out

Function x AC

1 byte

C,T

20.105 HAVC control mode

In Gateway mode, it is used to send control telegrams for various modes.

172

Status of control mode, In:

Function x AC

1 byte

C, W, T, U

20.105 HAVC control mode

This object is visible in Gateway mode when the mode type is 1byte. It is used to receive feedback telegrams for various modes.

173

Fan speed,Out

Function x AC

1 byte

C,T

5.001 percentage(0..100%)

175

Fan Speed Status,

Function x AC

1 byte

C, W, T, U

5.001% (0..100%)

174

Fan speed,Out

Function x AC

1 byte

C,T

5.100 fan stage(0..255)

176

Status of Fan speed,In

Function x AC

1 byte

C, W, T, U

5.100 fan stage(0..255)

  • Fan speed Out

This communication object is available in Air Conditioner Gateway mode. The displayed data type depends on the selected configuration. It is used to send control telegrams for different fan speed levels.

  • Status of Fan speed, In

This communication object is available in Air Conditioner Gateway mode. The displayed data type depends on the selected configuration. It is used to receive status feedback telegrams for different fan speed levels.

177

Vanes swing (1-swing,0-stop)

Function x AC

1 bit

C, W, T, U

1.010 start/stop

Visible when the swing function is enabled. This communication object is used to send telegrams controlling the vanes swing (oscillation) to the bus.

178

Vanes swing (1-swing, 0-stop), status

Function x AC

1 bit

C, W, T, U

1.010 start/stop

Visible when the swing function is enabled. This communication object is used to receive the swing status of the vanes from the bus.

- Telegram values:

1: Swinging

0: Fixed

179

Vanes position 1..5

Function x AC

1 byte

C, W, T, U

5.010 counter pulses(0..255)

Visible when the vanes position function is enabled. This communication object is used to send control telegrams for vanes fixed positions 1 to 5 to the bus.

180

Vanes position 1..5, status

Function x AC

1 byte

C, W, T, U

5.010 counter pulses (0..255)

Visible when the vanes position function is enabled. This communication object is used to receive status feedback for vanes fixed positions 1 to 5 from the bus.

181

Current setpoint adjustment

Function x AC

1 byte

2 byte

C,T

5.010 counter pulses(0..255)

9.001 temperature(℃)

This communication object is used to adjust the setpoint temperature value and send telegram values to the bus.

NOTE:

The object type is defined by parameter settings. 2byte is KNX standard, while 1byte is non-standard, typically used for some custom control types. The telegram value represents the actual temperature, for example, a value of 17 (decimal) represents 17℃.

182

Current setpoint adjustment,in

Function x AC

1 byte

2 byte

C, W, T, U

5.010 counter pulses(0..255)

9.001 temperature(℃)

This communication object is used to receive the current setpoint temperature value from the bus and display it on the panel.

NOTE:

The object type is defined by parameter settings. 2byte is KNX standard, while 1byte is non-standard, typically used for some custom control types. The telegram value represents the actual temperature, for example, a value of 17 (decimal) represents 17℃.

206

Scene,in

Function x HVAC

1 byte

C, W

18.001 scene control

Visible when the scene function is enabled. This communication object is used to call a scene via the bus.

183

Error code

Function x HVAC

2 bytes

C, W

8.001 pulses difference

207

Error text

Function x HVAC

14 bytes

C, W

16.001 character string (ISO 8859-1)

208

Failure status

Function x HVAC

1 bit

C, W

1.005 alarm

When the error code function is enabled, three communication objects will become visible. These are used to display error codes of different data types.

Table 6.2.2 "Air conditioner" Communication Object Table

6.2.3 "Floor heating"

Figure 6.2.3 "Floor heating" Function Communication Objects

No.

Object Function

Name

Type

Flag

DPT

168

Floor heating-External temperature sensor, In

Function x

FloorHeating

2 bytes

C, W, T, U

9.001 temperature(℃)

This object is visible when the temperature reference is set to an external sensor.

It is used to receive temperature measurement values sent from a temperature sensor on the bus.

-Range: -50 ... 99.8°C

169

Floor heating-Power on/off, In/Out

Function x FloorHeating

1 bit

C, W, T, U

1.001 switch

This object is used to send switch control telegrams for underfloor heating and receive control status feedback.

-Telegram values

1: Underfloor heating control interface on, interface operable.

0: Underfloor heating control interface off, interface not operable.

NOTE:

In the off state, all interface icons except for the timer and switch icons are non-operational.

170

Floor heating- Heating on/off, In/Out

Function x FloorHeating

1 bit

C, W, T, U

1.001 switch

171

Floor heating-Heating control value, Out

Function x FloorHeating

1 byte

C, W, T, U

5.001% (0..100%)

This object is used to send control values for floor heating, controlling the opening and closing of the underfloor heating valve.

- Telegram values

Heating on/off - 2-point control: On/off

Heating PWM - use PI control: On/off

Heating continuous control - use PI control: 0 ... 100%

172

Floor heating-Setpoint,In/Out

Function x Floor heating

2 bytes

C, W, T, U

9.001 temperature(℃)

This object is used to send temperature setting values to the bus and to receive feedback of the temperature setting values.

- Range: 5 ... 40°C

174

Floor heating-Scene,in

Function x Floor heating

1 byte

C, W

18.001 scene control

Visible when scene function enabled, and used for bus sending scene.

175

Error code

Function x Floor heating

2 bytes

C, W

8.001 pulses difference

207

Error text

Function x Floor heating

14 bytes

C, W

16.001 character string (ISO 8859-1)

208

Failure status

Function x Floor heating

1 bit

C, W

1.005 alarm

When the error code function is enabled, these three communication objects become visible and are used to display error codes for different data types.

Table 6.2.3 "Floor heating" Function Communication Object Table

6.2.4 "Ventilation System"

Figure 6.2.4 "Ventilation System" Function Communication Objects

NO.

Object Function

Name

Type

Flag

DPT

168

Ventilation-Power on/off,In/Out

Function x Ventilation

1bit

C, W, T, U

1.001 switch

This object is used to send power on/off telegrams for ventilation control and receive control status feedback.

- Telegram values

1: Ventilation control interface on, interface operable

0: Ventilation control interface off, interface not operable

169

Ventilation-En./Dis. Heat Recovery,In

Function x Ventilation

1bit

C,W

1.003 enable

This object is used to disable/enable the heat recovery function of the ventilation system. The specific values are defined by parameters. When disabled, the heat exchange is turned off and cannot be controlled.

170

Ventilation-Heat Recovery, In/Out

Function x Ventilation

1bit

C, W, T, U

1.001 sw

This object is used to send control commands to turn on/off the heat recovery, and it can also receive status feedback values.

-Telegram values

1: On

0: Off

171

Ventilation-Filter time reset, In

Function x Ventilation

1bit

C, W

1.015 reset

This object is used to reset the filter time. After resetting, the duration of filter usage restarts counting.

- Telegram values

1: Reset

172

Ventilation-Filter time counter, In/Out

Function x Ventilation

2byte

C, W, T, U

7.001 plus

This object is used to count the filter usage time in hours.

Changes in the count value are transmitted to the bus, and this time can also be adjusted via the bus.

173

Ventilation-Filter alarm, Out

Function x Ventilation

1bit

C,T

1.005 alarm

When the filter usage time exceeds the set value, this object triggers an alarm to remind the user to replace the filter.

- Telegram values

1: Alarm

174

Fan speed, Out

Function x Ventilation

1 byte

C,T

5.010% (0..100%)

175

Fan speed, Out

Function x Ventilation

1 byte

C,T

5.100 fan stage (0..255)

When the wind speed type is set to "1 byte," this object becomes visible. It sends control telegrams for the wind speed to the bus. The specific telegram values for each wind speed level are defined by parameters.

176

Status of Fan speed, In

Function x Ventilation

1 byte

C, W, T, U

5.010 percentage(0..100%)

177

Fan SpeedStatus,In

Function x Ventilation

1 byte

C, W, T, U

5.100 fan stage (0..255)

When the wind speed type is “1byte”, this object is visible. It receives feedback of the wind speed. The specific telegram values for each wind speed level are defined by parameters.

178

Ventilation-Fan Speed No.1 1Bit, In/Out

Function x Ventilation

1bit

C, W, T, U

1.001 switch

179

Ventilation-Fan Speed No.2 1Bit, In/Out

Function x Ventilation

1bit

C, W, T, U

1.001 switch

180

Ventilation-Fan Speed No.3 1Bit, In/Out

Function x Ventilation

1bit

C, W, T, U

1.001 switch

When the wind speed type is 1”bit”, these three communication objects are visible.

The wind speed is controlled by three objects simultaneously, with each wind speed level corresponding to specific telegram values defined by parameters. They can receive feedback, with feedback values needing to correspond to the parameter-defined values to update the display on the screen.

181

Ventilation-Automatic function, In/Out

Function x Ventilation

1bit

C, W, T, U

1.003 enable

This object is used to enable the automatic operation function.

By default, automatic operation is disabled after power recovery or programming. It can be disabled by turning off the device, manually adjusting the fan speed, or activating a scene. Specific values for enabling or disabling automatic operation are defined by parameters.

183

182

CO2, In

Function x Ventilation

2byte

C, W, T, U

9.008 parts/million(ppm)

7.001 pulse

This object is used to receive the input of CO2 values from the bus and update the display accordingly. The unit is ppm.

- Range: 0 ... 4000

If the automatic operation control value is set to CO2, the ventilation system in automatic mode adjusts fan speed based on CO2 concentration. The object's data type is determined by parameters.

185

184

PM2.5, In

Function x Ventilation

2byte

C, W, T, U

9.030 concentration(ug/m3)

7.001 pulses

This object is used to receive the input of PM2.5 values from the bus, updating the display accordingly. The unit is ug/m3.

- Range: 0 ... 999

If the control value for automatic operation is set to PM2.5, the ventilation system in automatic mode adjusts fan speed based on PM2.5 concentration. The object's data type is determined by parameters.

183

182

PM10, In

Function x Ventilation

2byte

C, W, T, U

9.030 concentration(ug/m3)

7.001 pulses

This object is used to receive the input of PM10 values from the bus, updating the display accordingly. The unit is ug/m3.

- Range: 0 ... 999

If the control value for automatic operation is set to PM2.5, the ventilation system in automatic mode adjusts fan speed based on PM2.5 concentration. The object's data type is determined by parameters.

182

AQI, In

Function x Ventilation

2byte

C, W, T, U

7.001 pulses

This object is used to receive the input of AQI values from the bus, updating the display accordingly. The unit is ug/m3.

- Range: 0 ... 999

If the control value for automatic operation is set to AQI, the ventilation system in automatic mode adjusts fan speed based on AQI concentration. The object's data type is determined by parameters.

183

182

VOC, In

Function x Ventilation

2byte

C, W, T, U

9.008 parts per million (ppm)

7.001 pulses

This object is used to receive the input of VOC values from the bus, updating the display accordingly. The unit is ppm.

- Range: 0 ... 4000

If the control value for automatic operation is set to VOC, the ventilation system in automatic mode adjusts fan speed based on VOC concentration. The object's data type is determined by parameters.

182

Others, In

Function x Ventilation

2byte

C, W, T, U

7.001 pulses

This object is used to receive the input of Other sensor from the bus, updating the display accordingly.

- Range: 0 ...65535

If the control value for automatic operation is set to Other, the ventilation system in automatic mode adjusts fan speed based on Other concentration. The object's data type is determined by parameters.

186

Scene,in

Function x Ventilation

1byte

C,W

18.001 scene control

Visible when scene function enabled, and used for bus sending scene.

187

Error code

Function x Ventilation

2 bytes

C, W

8.001 pulses difference

207

Error text

Function x Ventilation

14 bytes

C,W

16.001 character string (ISO 8859-1)

208

Failure status

Function x Ventilation

1bit

C,W

1.005 alarm

When the error code function is enabled, three communication objects will become visible. These are used to display error codes of different data types.

Table 6.2.4 "Ventilation System" Function Communication Objects Table