6.2.1 "HVAC"









Figure 6.2.1 "HVAC" Function Communication Objects
No. | Object Function | Name | Type | Flag | DPT | |
168 | Input-External temperature | Function x HVAC | 2byte | C, W, T, U | 9.001 temperature(℃) | |
This communication object is used to receive temperature measurement values sent from the temperature sensor on the bus. Range: -50~99.8℃ | ||||||
169 | Input-Setpoint adjustment | Function x HVAC | 2byte | C, W | 9.001 temperature (℃) | |
When the HVAC operation mode is disabled, this object is used to modify the baseline value of the set temperature. When the HVAC operation mode is enabled and the set temperature is set to be relative adjustment, this object is used to modify the baseline value of the set temperature. Specifically, it adjusts the temperature setting value of the Comfort mode, while the setting temperature of the Standby and the Economy modes change according to the relative change. In Protection mode, only the protection mode temperature is modified. When the HVAC operation mode is enabled and the set temperature is adjusted absolutely, this object is used to modify the set temperature value of the current operation mode. | ||||||
170 | Input-Switch Heating Cooling mode | Function x HVAC | 1bit | C, W, U | 1.100 cooling/heating | |
This communication object is used to receive status feedback from heaters and coolers on the bus. The display on the screen will be updated according to the received telegram value. - Telegram values 1: Heating 0: Cooling | ||||||
171 | Input mode | Function x HVAC | 1 byte | C,W | 20.102 HVAC mode | |
172 | Input-Comfort mode | Function x HVAC | 1bit | C, W | 1.003 enable | |
173 | Input-Standby mode | Function x HVAC | 1bit | C,W | 1.003 enable | |
174 | Input-Economy mode | Function x HVAC | 1bit | C, W | 1.003 enable | |
175 | Input-Frost/heat protection mode | Function x HVAC | 1-bit | C,W | 1.003 enable | |
The operation mode can receive status feedback through either four 1-bit objects (Objects 172, 173, 174, 175) or one 1-byte object (HVAC mode).
Object 172: Comfort mode Object 173: Standby mode Object 174: Economy mode Object 175: Frost/heat protection mode When any of these objects receive a telegram “1”, the corresponding mode will be activated. The mode display status on the screen will also update accordingly.
Input values and their corresponding operation modes are as follows: 0: Reserved 1: Comfort mode 2: Standby mode 3: Economy mode 4: Frost/heat protection mode 5-255: Reserved, not used | ||||||
176 | Input-Fan speed | Function x HVAC | 1 byte | C, W, U | 5.001% (0..100%) | |
203 | Input-Fan speed | Function x HVAC | 1 byte | C, W, U | 5.100 fan stage(0..255) | |
177 | Input-Fan speed low | Function x HVAC | 1-bit | C, W, U | 1.001 switch | |
178 | Input-Fan speed medium | Function x HVAC | 1bit | C, W, U | 1.001 switch | |
179 | Input-Fan speed high | Function x HVAC | 1-bit | C, W, U | 1.001 switch | |
180 | Input-Fan speed off | Function x HVAC | 1bit | C, W, U | 1.001 switch | |
The fan speed can receive status feedback through either four 1-bit objects (Objects 177, 178, 179, 180) or one 1-byte object (Fan speed).
Object 177: Low fan speed Object 178: Medium fan speed Object 179: High fan speed Object 180: Fan speed off When any of these objects receive a telegram “1”, the corresponding fan speed will be activated. The fan speed display status on the screen will also update accordingly. When the fan speed is off, the telegram value for all fan speeds must be 0.
Fan speed status values are defined by parameters. When the object receives the specified value, the fan speed display status on the screen will update to the corresponding fan speed. | ||||||
181 | Input-Fan Automatic operation | Function x HVAC | 1bit | C, W, U | 1.003 enable | |
This object is used to receive status feedback from auto control of fan speed. - Telegram values 1: Auto mode 0: Exit auto mode | ||||||
182 | Output-Instantaneous setpoint | Function x HVAC | 2 bytes | C, R, T | 9.001 temperature(℃) | |
This object is used to send the set temperature value of the current operating mode to the bus. | ||||||
183 | Output-Heating/Cooling mode | Function x HVAC | 1bit | C, R, T | 1.100 cooling/heating | |
This object is used to send telegrams of switching between heating and cooling functions to the bus. - Telegram values 1: Heating 0: Cooling | ||||||
184 | Output-HVAC mode | Function x HVAC | 1byte | C,R, T | 20.102 DPT_HVAC Mode | |
185 | Output-Comfort mode | Function x HVAC | 1bit | C,T | 1.003enable | |
186 | Output-Standby mode | Function x HVAC | 1bit | C,T | 1.003enable | |
187 | Output-Economy mode | Function x HVAC | 1bit | C,T | 1.003enable | |
188 | Output-Frost/Heat protection mode | Function x HVAC | 1bit | C,T | 1.003enable | |
These communication objects are used to send telegrams of the operation mode to the bus.
0: Reserved 1: Comfort mode 2: Standby mode 3: Economy mode 4: Frost/heat protection mode 5~255: Reserved, not used
Upon switching to the specific mode, the mode will send a telegram "1" to the bus. | ||||||
201 | Output-Heating/cooling control value | Function x HVAC | 1bit | C,T | 1.001 switch | |
202 | Output-Heating/Cooling Control Value | Function x HVAC | 1 byte | C,T | 5.001% (0..100%) | |
197 | Output-Heating control value | Function x HVAC | 1-bit | C,T | 1.001 switch | |
198 | Output-Heating control value | Function x HVAC | 1 byte | C,T | 5.001% (0..100%) | |
199 | Output-Cooling control value | Function x HVAC | 1-bit | C,T | 1.001 switch | |
200 | Output-Cooling control value | Function x HVAC | 1 byte | C,T | 5.001% (0..100%) | |
This object sends control values of heating or cooling functions to regulate the HVAC valve, thereby adjusting the indoor temperature. - Telegram values Switch on/off use - 2-point control: On/off Switch PWM - use PI control: On/off Continuous control - use PI control: 0 ... 100% | ||||||
189 | Output-Fan speed | Function x HVAC | 1 byte | C, W, U | 5.001 percentage(0..100%) | |
204 | Output-Fan speed | Function x HVAC | 1 byte | C, W, U | 5.100 fan stage(0..255) | |
190 | Output-Fan speed low | Function x HVAC | 1bit | C, W, U | 1.001 switch | |
196 | Output-Fan speed medium | Function x HVAC | 1bit | C, W, U | 1.001 switch | |
192 | Output-Fan speed high | Function x HVAC | 1bit | C, W, U | 1.001 switch | |
193 | Output-Fan speed off | Function x HVAC | 1bit | C, W, U | 1.001 switch | |
These communication objects are used to send control telegrams for fan speed to the bus.
Object 190: Low fan speed Object 196: Medium fan speed Object 192: High fan speed Object 193: Fan speed off Activating the corresponding fan speed on the screen triggers the respective object to send a telegram “1” to the bus, except for the fan speed off telegram, which is “0”.
The telegram value of each fan speed level is defined by parameters. Activating the corresponding fan speed on the screen triggers the Object 189 or 204 to send the specific fan speed value to the bus. | ||||||
194 | Output-Fan Automatic operation | Function x HVAC | 1bit | C,T | 1.003 enable | |
This communication object is used to send auto control telegrams for fan speed to the bus. - Telegram values 1: Auto mode 0: Exit auto mode | ||||||
191 | Input-on/off | Function x HVAC | 1bit | C, W, T, U | 1.001 switch | |
195 | Output-on/off | Function x HVAC | 1bit | C, W, T, U | 1.001 switch | |
This object is used to control the HVAC (Heating, Ventilation, and Air Conditioning) function of the device. When turning off the HVAC, corresponding controls are deactivated. | ||||||
206 | Scene,in | Function x HVAC | 1byte | C, W | 18.001 scene control | |
This communication object is visible when the Scene function is enabled. It is used to recall scenes via the bus. | ||||||
205 | Error code | Function x HVAC | 2 bytes | C, W | 8.001 pulses difference | |
207 | Error text | Function x HVAC | 14 bytes | C, W | 16.001 character string (ISO 8859-1) | |
208 | Failure status | Function x HVAC | 1bit | C, W | 1.005 alarm | |
When the Error code function is enabled, the three communication objects become visible. They are used to display error codes of different data types. | ||||||
Table 6.2.1 "HVAC" Function Communication Objects Table
6.2.2 "Air conditioner"



Figure 6.2.2 "Air conditioner" Communication Objects
No. | Object Function | Name | Type | Flag | DPT | ||||
168 | External temperature sensor, In | Function x AC | 2 bytes | C, W, T, U | 9.001 temperature(℃) | ||||
This communication object is used to receive temperature measurement values from the indoor temperature sensor on the bus and display the indoor temperature on the screen. | |||||||||
169 | Power on/off,Out | Function x AC | 1 bit | C,T | 1.001 switch | ||||
Power on/off: Send air conditioner power switch telegrams. | |||||||||
170 | Status of Power,In | Function x AC | 1 bit | C, W, T, U | 1.001 switch | ||||
This object is visible in Gateway mode and is used to receive feedback of power switch status. | |||||||||
171 | Control mode,Out | Function x AC | 1 byte | C,T | 20.105 HAVC control mode | ||||
In Gateway mode, it is used to send control telegrams for various modes. | |||||||||
172 | Status of control mode, In: | Function x AC | 1 byte | C, W, T, U | 20.105 HAVC control mode | ||||
This object is visible in Gateway mode when the mode type is 1byte. It is used to receive feedback telegrams for various modes. | |||||||||
173 | Fan speed,Out | Function x AC | 1 byte | C,T | 5.001 percentage(0..100%) | ||||
175 | Fan Speed Status, | Function x AC | 1 byte | C, W, T, U | 5.001% (0..100%) | ||||
174 | Fan speed,Out | Function x AC | 1 byte | C,T | 5.100 fan stage(0..255) | ||||
176 | Status of Fan speed,In | Function x AC | 1 byte | C, W, T, U | 5.100 fan stage(0..255) | ||||
This communication object is available in Air Conditioner Gateway mode. The displayed data type depends on the selected configuration. It is used to send control telegrams for different fan speed levels.
This communication object is available in Air Conditioner Gateway mode. The displayed data type depends on the selected configuration. It is used to receive status feedback telegrams for different fan speed levels. | |||||||||
177 | Vanes swing (1-swing,0-stop) | Function x AC | 1 bit | C, W, T, U | 1.010 start/stop | ||||
Visible when the swing function is enabled. This communication object is used to send telegrams controlling the vanes swing (oscillation) to the bus. | |||||||||
178 | Vanes swing (1-swing, 0-stop), status | Function x AC | 1 bit | C, W, T, U | 1.010 start/stop | ||||
Visible when the swing function is enabled. This communication object is used to receive the swing status of the vanes from the bus. - Telegram values: 1: Swinging 0: Fixed | |||||||||
179 | Vanes position 1..5 | Function x AC | 1 byte | C, W, T, U | 5.010 counter pulses(0..255) | ||||
Visible when the vanes position function is enabled. This communication object is used to send control telegrams for vanes fixed positions 1 to 5 to the bus. | |||||||||
180 | Vanes position 1..5, status | Function x AC | 1 byte | C, W, T, U | 5.010 counter pulses (0..255) | ||||
Visible when the vanes position function is enabled. This communication object is used to receive status feedback for vanes fixed positions 1 to 5 from the bus. | |||||||||
181 | Current setpoint adjustment | Function x AC | 1 byte 2 byte | C,T | 5.010 counter pulses(0..255) 9.001 temperature(℃) | ||||
This communication object is used to adjust the setpoint temperature value and send telegram values to the bus.
| |||||||||
182 | Current setpoint adjustment,in | Function x AC | 1 byte 2 byte | C, W, T, U | 5.010 counter pulses(0..255) 9.001 temperature(℃) | ||||
This communication object is used to receive the current setpoint temperature value from the bus and display it on the panel.
| |||||||||
206 | Scene,in | Function x HVAC | 1 byte | C, W | 18.001 scene control | ||||
Visible when the scene function is enabled. This communication object is used to call a scene via the bus. | |||||||||
183 | Error code | Function x HVAC | 2 bytes | C, W | 8.001 pulses difference | ||||
207 | Error text | Function x HVAC | 14 bytes | C, W | 16.001 character string (ISO 8859-1) | ||||
208 | Failure status | Function x HVAC | 1 bit | C, W | 1.005 alarm | ||||
When the error code function is enabled, three communication objects will become visible. These are used to display error codes of different data types. | |||||||||
Table 6.2.2 "Air conditioner" Communication Object Table
6.2.3 "Floor heating"


Figure 6.2.3 "Floor heating" Function Communication Objects
No. | Object Function | Name | Type | Flag | DPT |
168 | Floor heating-External temperature sensor, In | Function x FloorHeating | 2 bytes | C, W, T, U | 9.001 temperature(℃) |
This object is visible when the temperature reference is set to an external sensor. It is used to receive temperature measurement values sent from a temperature sensor on the bus. -Range: -50 ... 99.8°C | |||||
169 | Floor heating-Power on/off, In/Out | Function x FloorHeating | 1 bit | C, W, T, U | 1.001 switch |
This object is used to send switch control telegrams for underfloor heating and receive control status feedback. -Telegram values 1: Underfloor heating control interface on, interface operable. 0: Underfloor heating control interface off, interface not operable.
| |||||
170 | Floor heating- Heating on/off, In/Out | Function x FloorHeating | 1 bit | C, W, T, U | 1.001 switch |
171 | Floor heating-Heating control value, Out | Function x FloorHeating | 1 byte | C, W, T, U | 5.001% (0..100%) |
This object is used to send control values for floor heating, controlling the opening and closing of the underfloor heating valve. - Telegram values Heating on/off - 2-point control: On/off Heating PWM - use PI control: On/off Heating continuous control - use PI control: 0 ... 100% | |||||
172 | Floor heating-Setpoint,In/Out | Function x Floor heating | 2 bytes | C, W, T, U | 9.001 temperature(℃) |
This object is used to send temperature setting values to the bus and to receive feedback of the temperature setting values. - Range: 5 ... 40°C | |||||
174 | Floor heating-Scene,in | Function x Floor heating | 1 byte | C, W | 18.001 scene control |
Visible when scene function enabled, and used for bus sending scene. | |||||
175 | Error code | Function x Floor heating | 2 bytes | C, W | 8.001 pulses difference |
207 | Error text | Function x Floor heating | 14 bytes | C, W | 16.001 character string (ISO 8859-1) |
208 | Failure status | Function x Floor heating | 1 bit | C, W | 1.005 alarm |
When the error code function is enabled, these three communication objects become visible and are used to display error codes for different data types. | |||||
Table 6.2.3 "Floor heating" Function Communication Object Table
6.2.4 "Ventilation System"












Figure 6.2.4 "Ventilation System" Function Communication Objects
NO. | Object Function | Name | Type | Flag | DPT | |||||||
168 | Ventilation-Power on/off,In/Out | Function x Ventilation | 1bit | C, W, T, U | 1.001 switch | |||||||
This object is used to send power on/off telegrams for ventilation control and receive control status feedback. - Telegram values 1: Ventilation control interface on, interface operable 0: Ventilation control interface off, interface not operable | ||||||||||||
169 | Ventilation-En./Dis. Heat Recovery,In | Function x Ventilation | 1bit | C,W | 1.003 enable | |||||||
This object is used to disable/enable the heat recovery function of the ventilation system. The specific values are defined by parameters. When disabled, the heat exchange is turned off and cannot be controlled. | ||||||||||||
170 | Ventilation-Heat Recovery, In/Out | Function x Ventilation | 1bit | C, W, T, U | 1.001 sw | |||||||
This object is used to send control commands to turn on/off the heat recovery, and it can also receive status feedback values. -Telegram values 1: On 0: Off | ||||||||||||
171 | Ventilation-Filter time reset, In | Function x Ventilation | 1bit | C, W | 1.015 reset | |||||||
This object is used to reset the filter time. After resetting, the duration of filter usage restarts counting. - Telegram values 1: Reset | ||||||||||||
172 | Ventilation-Filter time counter, In/Out | Function x Ventilation | 2byte | C, W, T, U | 7.001 plus | |||||||
This object is used to count the filter usage time in hours. Changes in the count value are transmitted to the bus, and this time can also be adjusted via the bus. | ||||||||||||
173 | Ventilation-Filter alarm, Out | Function x Ventilation | 1bit | C,T | 1.005 alarm | |||||||
When the filter usage time exceeds the set value, this object triggers an alarm to remind the user to replace the filter. - Telegram values 1: Alarm | ||||||||||||
174 | Fan speed, Out | Function x Ventilation | 1 byte | C,T | 5.010% (0..100%) | |||||||
175 | Fan speed, Out | Function x Ventilation | 1 byte | C,T | 5.100 fan stage (0..255) | |||||||
When the wind speed type is set to "1 byte," this object becomes visible. It sends control telegrams for the wind speed to the bus. The specific telegram values for each wind speed level are defined by parameters. | ||||||||||||
176 | Status of Fan speed, In | Function x Ventilation | 1 byte | C, W, T, U | 5.010 percentage(0..100%) | |||||||
177 | Fan SpeedStatus,In | Function x Ventilation | 1 byte | C, W, T, U | 5.100 fan stage (0..255) | |||||||
When the wind speed type is “1byte”, this object is visible. It receives feedback of the wind speed. The specific telegram values for each wind speed level are defined by parameters. | ||||||||||||
178 | Ventilation-Fan Speed No.1 1Bit, In/Out | Function x Ventilation | 1bit | C, W, T, U | 1.001 switch | |||||||
179 | Ventilation-Fan Speed No.2 1Bit, In/Out | Function x Ventilation | 1bit | C, W, T, U | 1.001 switch | |||||||
180 | Ventilation-Fan Speed No.3 1Bit, In/Out | Function x Ventilation | 1bit | C, W, T, U | 1.001 switch | |||||||
When the wind speed type is 1”bit”, these three communication objects are visible. The wind speed is controlled by three objects simultaneously, with each wind speed level corresponding to specific telegram values defined by parameters. They can receive feedback, with feedback values needing to correspond to the parameter-defined values to update the display on the screen. | ||||||||||||
181 | Ventilation-Automatic function, In/Out | Function x Ventilation | 1bit | C, W, T, U | 1.003 enable | |||||||
This object is used to enable the automatic operation function. By default, automatic operation is disabled after power recovery or programming. It can be disabled by turning off the device, manually adjusting the fan speed, or activating a scene. Specific values for enabling or disabling automatic operation are defined by parameters. | ||||||||||||
183 182 | CO2, In | Function x Ventilation | 2byte | C, W, T, U | 9.008 parts/million(ppm) 7.001 pulse | |||||||
This object is used to receive the input of CO2 values from the bus and update the display accordingly. The unit is ppm. - Range: 0 ... 4000 If the automatic operation control value is set to CO2, the ventilation system in automatic mode adjusts fan speed based on CO2 concentration. The object's data type is determined by parameters. | ||||||||||||
185 184 | PM2.5, In | Function x Ventilation | 2byte | C, W, T, U | 9.030 concentration(ug/m3) 7.001 pulses | |||||||
This object is used to receive the input of PM2.5 values from the bus, updating the display accordingly. The unit is ug/m3. - Range: 0 ... 999 If the control value for automatic operation is set to PM2.5, the ventilation system in automatic mode adjusts fan speed based on PM2.5 concentration. The object's data type is determined by parameters. | ||||||||||||
183 182 | PM10, In | Function x Ventilation | 2byte | C, W, T, U | 9.030 concentration(ug/m3) 7.001 pulses | |||||||
This object is used to receive the input of PM10 values from the bus, updating the display accordingly. The unit is ug/m3. - Range: 0 ... 999 If the control value for automatic operation is set to PM2.5, the ventilation system in automatic mode adjusts fan speed based on PM2.5 concentration. The object's data type is determined by parameters. | ||||||||||||
182 | AQI, In | Function x Ventilation | 2byte | C, W, T, U | 7.001 pulses | |||||||
This object is used to receive the input of AQI values from the bus, updating the display accordingly. The unit is ug/m3. - Range: 0 ... 999 If the control value for automatic operation is set to AQI, the ventilation system in automatic mode adjusts fan speed based on AQI concentration. The object's data type is determined by parameters. | ||||||||||||
183 182 | VOC, In | Function x Ventilation | 2byte | C, W, T, U | 9.008 parts per million (ppm) 7.001 pulses | |||||||
This object is used to receive the input of VOC values from the bus, updating the display accordingly. The unit is ppm. - Range: 0 ... 4000 If the control value for automatic operation is set to VOC, the ventilation system in automatic mode adjusts fan speed based on VOC concentration. The object's data type is determined by parameters. | ||||||||||||
182 | Others, In | Function x Ventilation | 2byte | C, W, T, U | 7.001 pulses | |||||||
This object is used to receive the input of Other sensor from the bus, updating the display accordingly. - Range: 0 ...65535 If the control value for automatic operation is set to Other, the ventilation system in automatic mode adjusts fan speed based on Other concentration. The object's data type is determined by parameters. | ||||||||||||
186 | Scene,in | Function x Ventilation | 1byte | C,W | 18.001 scene control | |||||||
Visible when scene function enabled, and used for bus sending scene. | ||||||||||||
187 | Error code | Function x Ventilation | 2 bytes | C, W | 8.001 pulses difference | |||||||
207 | Error text | Function x Ventilation | 14 bytes | C,W | 16.001 character string (ISO 8859-1) | |||||||
208 | Failure status | Function x Ventilation | 1bit | C,W | 1.005 alarm | |||||||
When the error code function is enabled, three communication objects will become visible. These are used to display error codes of different data types. | ||||||||||||
Table 6.2.4 "Ventilation System" Function Communication Objects Table