--- title: "2.7.2 Gate forwarding" slug: "gate-forwarding" updated: 2026-08-24T06:10:19Z published: 2026-08-24T06:10:19Z canonical: "knowledge.akuvox.com/gate-forwarding" stale: true --- > ## Documentation Index > Fetch the complete documentation index at: https://knowledge.akuvox.com/llms.txt > Use this file to discover all available pages before exploring further. # 2.7.2 Gate forwarding ![](https://cdn.document360.io/f09a6106-e976-455e-b2d0-3d88b5385960/Images/Documentation/image-79SHTKBP.png) Figure 2.7.3 “Logic function - Gate forwarding” Interface - **Object type of Input/Output** Set the data type of the input/output. Options: - 1bit - 4bit - 1byte - **Scene NO. of Gate after startup [1.. 64, 0=inactive]** Specify the initial scene forwarded by the logic gate after device startup, which must be configured in the parameters. Options: 1.. 64, 0 = inactive. > [!NOTE] > **NOTE:** > > It's recommended to select the gate scene before operation; otherwise, the initial scene will be activated by default. - **z->Gate trigger scene NO.[1.. 64, 0=inactive] (z:1~8)** Specify the scene number for logic gate forwarding. Each logic can have up to 8 trigger scene settings configured. Options: 1.. 64, 0 = inactive. - **Input A/B/C/D send on** Set the output of input x (x=A/B/C/D) after gate forwarding. Depending on the option selected, one input can be forwarded to one or more outputs. The input value remains consistent with the the output value. Options: - Output A - Output B ... - Output B, C, D