--- title: "4. Project Design and Application" slug: "pda" updated: 2026-08-24T07:57:51Z published: 2026-08-24T07:57:51Z canonical: "knowledge.akuvox.com/pda" stale: true --- > ## Documentation Index > Fetch the complete documentation index at: https://knowledge.akuvox.com/llms.txt > Use this file to discover all available pages before exploring further. # 4. Project Design and Application ## 4.1 Diagram ![](https://cdn.document360.io/f09a6106-e976-455e-b2d0-3d88b5385960/Images/Documentation/image-YUWD2F1Y.png) ## 4.2 Function Overview ### 4.2.1 Control of a Single DALI Device In the Double-channel DALI gateway application, each DALI device for each output channel can be individually switching, dimming, brightness value, colour temperature, colour control via a communication object. Status feedback for switching, dimming, brightness, colour temperature, and colour control can also be requested. Examples of control and status objects for a device “y” on output channel “X” include: - Output X ECG y — Switch (switch control for device y) - Output X ECG y — Relative Dimming (relative dimming control for device y) - Output X ECG y — Brightness value (brightness value control for device y) - Output X ECG y — Relative (percentage) colour temperature (Relative (percentage) colour temperature e control for devicey) - Output X ECG y — Absolute colour temperature (Absolute colour temperature control for device y) - Output X ECG y — RGB colour /HSV Hue(H)/HSV Saturation(S) value (RGB colour /HSV Hue(H)/HSV Saturation(S) control for device y) - Output X ECG y —RGBW colour/White colour value (RGBW colour/White colour control for device y) - Output X ECG y —colour XY/colour X/colour Y value (colour XY/colour X/colour Y control for device y) - Output X ECG y — Relative HSV Hue(H)/HSV Saturation(S) value (Relative HSV Hue(H)/HSV Saturation(S) control for device y) - Output X ECG y — Switch Status (request or respond to the switch status of device y) - Output X ECG y — Brightness Status (request or respond to the brightness status of device y) - Output X ECG y — Relative (percentage) colour temperature status (request or respond to the Relative (percentage) colour temperature status y) - Output X ECG y — Absolute colour temperature status (request or respond to the Absolute colour temperature status of device y) - Output X ECG y — RGB colour /HSV Hue(H)/HSV Saturation(S) value status (request or respond to the RGB colour /HSV Hue(H)/HSV Saturation(S) value status of device y) - Output X ECG y — RGBW colour/White colour value status (request or respond to the RGBW colour/White colour value status of device y) - Output X ECG y — colour XY/colour X/colour Y value status (request or respond to the colour XY/colour X/colour Y value status of device y) - Output X ECG y — Relative HSV Hue(H)/HSV Saturation(S) value status (request or respond to the Relative HSV Hue(H)/HSV Saturation(S) value status of device y) In addition, for these three device types, the entire output channel can be controlled for panic and test functions via communication objects: - Output X — Panic mode (activate panic mode for all connected devices on output X) It can also be configured as emergency lighting powered by a central battery, with the object used to activate the test mode for all emergency lights on the channel. - Output X — Test mode (activate test mode for all connected devices on output X) (X=output channel A, B; y=DALI device 1-64) > [!NOTE] > **NOTE:** > > Panic mode and test mode are only supported with database versions 2.0 or higher and DCA versions 2.0.0.1 or higher. ### ### 4.2.2 Self-Contained Battery light In the application of the DALI gateway, each DALI device on each output channel can support the DT1 Self-Contained Battery light (with an independent internal battery, non-switchable). This device type does not have control or status communication objects for switching, brightness, colour temperature, or colour. It can only execute and record mandatory tests through the following communication objects: - Output X ECG y — Converter, test start (activate converter's duration test and function test for device y) - Output X ECG y — Converter, test result (request or respond to the converter’s test result of device y) - Output X ECG y — Converter, status (request or respond to the converter’s status of device y) - Output X ECG y — Converter battery, status (request or respond to the converter’s battery status of device y) In the event of a power supply failure, the self-contained battery light automatically switches to emergency mode, using its internal battery for power. However, during commissioning or installation, it may be necessary to cut off the power to prevent continuous emergency operation and battery discharge. To prevent the light from switching to emergency mode, the inhibit mode for all self-contained battery lights on the output channel can be activated via: - Output X — Converter inhibit mode (activate inhibit mode for all connected devices on output X) (X=output channel A, B; y=DALI device 1..64) > [!NOTE] > **NOTE:** > > Self-contained battery lights are supported only on database versions 2.0 or higher and DCA version 2.0.0.1 or above. ### ### 4.2.3 Group Control The Double-channel DALI gateway supports up to 16 groups per output channel. Multiple DALI devices on each channel can be controlled together for switching, dimming, brightness, colour temperature, and colour via communication objects. To use group control: 1. Activate the group function in the ETS parameter configuration and configure the relevant parameters. 2. Use the DCA tool to assign DALI devices to groups. A single ECG can belong to multiple groups simultaneously. The following communication objects are available for group control: - Output X Group y — Switch (switch control for device y) - Output X Group y — Relative Dimming (relative dimming of all devices in group y) - Output X Group y — Brightness value (brightness value control for device y) - Output X Group y—Absolute colour temperature (Absolute colour temperature control for device y) - Output X Group y— Relative (percentage) colour temperature (Relative (percentage) colour temperature control for device y) - Output X ECG y — RGB colour /HSV Hue(H)/HSV Saturation(S) value (RGB colour /HSV Hue(H)/HSV Saturation(S) control for device y) - Output X ECG y —RGBW colour/White colour value (RGBW colour/White colour control for device y) - Output X ECG y —colour XY/colour X/colour Y value (colour XY/colour X/colour Y control for device y) - Output X ECG y — Relative HSV Hue(H)/HSV Saturation(S) value (Relative HSV Hue(H)/HSV Saturation(S) control for device y) - Output X Group y — Switch Status (request or respond to the switch status of the y group device) - Output X Group y — Brightness Status (request or respond to the brightness status of the y group device) - Output X Group y—Absolute colour temperature (request or respond to the Absolute colour temperature of the y group device) - Output X Group y — Relative (percentage) colour temperature status (request or respond to the Relative (percentage) colour temperature status of the y group device) - Output X ECG y — RGB colour /HSV Hue(H)/HSV Saturation(S) value status (request or respond to the RGB colour /HSV Hue(H)/HSV Saturation(S) value status of device y) - Output X ECG y —RGBW colour/White colour value status (request or respond to the RGBW colour/White colour value status of device y) - Output X ECG y —colour XY/colour X/colour Y value status (request or respond to the colour XY/colour X/colour Y value status of device y) - Output X ECG y — Relative HSV Hue(H)/HSV Saturation(S) value status (request or respond to the Relative HSV Hue(H)/HSV Saturation(S) value status of device y ) (X=output channel A, B; y=group 1..16) > [!NOTE] > **NOTE:** > > Groups are configured via the DCA tool. To ensure proper operation of ECGs in a group, the ECGs must also be activated via ETS; otherwise, group control for these ECGs will not work. ### ### 4.2.4 Scene Control The scene control of the double-channel DALI gateway is divided into DALI scene, group scene, and global scene. DALI scenes allow recalling the internal scene settings of DALI drivers via DALI scene objects. Group scenes control the target state of device groups when a KNX scene control is received. Global scenes enable control of custom ECGs or groups using KNX scene numbers. - **DALI scenes:** Each output channel has an independent DALI scene control object. By setting the object value, the gateway can directly recall up to 16 standard scenes stored in the corresponding DALI system. This function requires using the DCA tool to enable the standard DALI scenes for each driver and configure the corresponding states (including brightness, colour temperature, and colour) when executing the scenes. When a KNX device sends a DALI scene number to the gateway, all ECGs assigned to that scene will execute the operation and adjust the lights to their preset states. - **Group scenes:** Each group supports up to 16 group scene controls. Brightness, colour temperature, and colour values for each group scene can be configured in ETS. When a KNX device sends a scene number to recall a group scene, the gateway sends the corresponding group control command to the DALI bus, adjusting all devices in that group to the configured state. - **Global scenes:** Global scenes are configured via the DCA tool. Users can select individual ECGs or groups as execution targets and assign a target state for each. When the gateway receives a KNX scene control telegram on the bus, it recalls the configured execution operation for all targets in the scene. ### ### 4.2.5 Broadcast Control In broadcast mode, all DALI devices on a channel can be controlled simultaneously for switching, dimming, brightness, colour temperature, and colour. Due to variations in device response, brightness changes may not be perfectly synchronized—some devices may reach the target brightness before others. If the database is not configured, pressing the Test A/B button on the gateway will also switch all DALI devices on the corresponding channel. ### ### 4.2.6 Operation Mode The following operation modes are applicable to DT6-LED dimming control devices, DT8-colour control devices, and DT7-relays modules. > [!NOTE] > **NOTE:** > > Panic mode and test mode are only supported with database versions 2.0 or higher and DCA versions 2.0.0.1 or higher. - **Normal mode:** Each DALI device and group can be switched, dimmed, adjusted for brightness, colour temperature, and colour, with feedback on switching and brightness status. - **Permanent mode:** Devices or groups output a fixed brightness value. After a gateway reset or reprogramming, the preset brightness is applied automatically. > [!NOTE] > **NOTE:** > > If a device fails (e.g., the ECG is unpowered) and cannot output the preset brightness value, the brightness will be automatically corrected within 60 seconds. The ECG’s colour and colour temperature control functions remain available. - **Staircase mode:** The brightness values of the DALI device sand the DALI groups can can be adjusted via switching, relative dimming, or brightness value objects. Lights turn off automatically after a delay or via object control. If turned on again during the delay, the timer resets. - **Normal/Night mode:** Night mode behaves like Staircase or Permanent mode but must be activated via a night mode object. If the night mode is not activated, the DALI devices or the DALI groups operate in Normal mode. In night mode, devices or group lights either turn off automatically after a delay or maintain a fixed brightness. - **Panic mode**: The panic mode can be activated centrally via a channel object. All ECGs with panic mode enabled will switch to the setting brightness upon receiving commands. In this mode, they can no longer be controlled individually, and both group assignments and scenes are disabled. Exiting panic mode restores previous brightness and on/off settings, and individual/group control resumes. - **Test mode (controlled by central battery):** Through function definition, the DALI gateway supports the configuration of emergency lights controlled by a central battery. Any ECGs (except for self-contained battery lights) can be configured as an emergency light, even if the ECG has been assigned to a group. Test mode can be activated centrally via a channel object. All ECGs with test mode enabled will switch to the preset brightness and run a test for a defined duration. In this mode, they can no longer be controlled individually, and both group assignments and scenes are disabled. After completion, devices return to previous brightness or the setting on/off state and can be individually controlled again or reassigned to groups. > [!NOTE] > **NOTE:** > > 1. Mode priority(from highest to lowest): **Test mode (controlled by central battery) > Panic mode > Burn-in function > Permanent mode > Broadcast control (button switch) > Disable function > Normal, Night, Staircase mode.** > > - During Test mode or Burn-in, commands from lower modes (Broadcast, Permanent, Normal, Night, Staircase) are ignored. Disable function commands are recorded and take effect after the higher mode ends. > - Higher modes override lower ones and restore to the previous state when exited. > - Telegrams from lower modes are ignored during Disable mode. > - Test mode interrupts the Burn-in function. After the exiting Test mode, the Burn-in function needs to be restarted via the object. > - If Test mode is activated before Permanent mode, exiting Test mode restores Permanent mode. > > 1. When a DALI device is assigned to group control, independent control is not recommended to avoid conflicts between single-device and group control modes. > 2. The operation mode of an individual ECG has a lower priority than that of the group it belongs to. If the ECG is assigned to a group, it An ECG’s mode follows its group’s mode. If in multiple groups, the group with the smallest number takes precedence. ### ### 4.2.7 Operation Hour Calculation The gateway records each light’s operating time (in hours) whenever brightness exceeds 0%. The recorded time can be reset via the corresponding object. It’s recommended to set a maximum lifetime for each ECG based on light specifications and enable the alarm object to prompt maintenance when nearing end of life. To evaluate light lifespan, lights often undergo a burn-in test during initial use. During this phase, lights run continuously at 100% brightness and cannot be dimmed or switched off. The gateway supports a burn-in function for each ECG and group, which can be activated via an object. While burn-in is active, individual control of the ECG or group is disabled. If the gateway loses power during burn-in, the process does not resume automatically after power recovery and must be restarted via the object. When burn-in ends normally (time completed or stopped via object), the device returns to its previous on/off or brightness state according to parameter settings and can be controlled individually again. ### ### 4.2.8 ECG or Light Failure Identification A key advantage of DALI technology is its ability to identify individual light or ECG failures. The gateway supports this feature and provides multiple diagnostic options. The gateway periodically scans all connected ECGs to detect ECG and light failures. The scan interval is configurable. For example, with the default 1 s interval and 64 connected ECGs, a full scan cycle takes about 64 s (1 s per ECG and fault type). Therefore, failure detection may take up to about one minute. Each channel performs its scan independently without interference and can be executed simultaneously. Detected fault information can be sent to the KNX bus via the ECG fault object (2 byte, 1 byte, or 1 bit). In addition, failure status for all ECGs can be viewed in the DCA tool, or queried individually for each ECG and light via object 7. > [!NOTE] > **NOTE:** > > Converter failure identification is supported in database versions 2.0 or later and DCA versions 2.0.0.1 or later. ### ### 4.2.9 Device Failure Count and Failure Rate Analysis Across the DALI bus, device failures are categorized as ECG failures and light failures. The gateway allows users to set alarm thresholds for each failure type and obtain the failure count or rate via communication objects, as well as the total failure count and rate for the entire DALI segment. Additionally, the DCA tool provides detailed viewing of failure counts and rates for each type, along with overall statistics for all ECGs and lights. > [!NOTE] > **NOTE:** > > Converter failure count and rate analysis are supported in database versions 2.0 or later and DCA versions 2.0.0.1 or later. ### ### 4.2.10 Colour Temperature Adjustment Colour temperature determines the perceived colour of light, measured in Kelvin (K). Group control supports colour temperature adjustment. Typical Kelvin values for reference: - 1500 K - Candlelight - 2700 K - Incandescent light (60W) - 2800 K - Halogen light - 4000 K - Fluorescent light (natural white) The table below lists common colour temperatures along with their corresponding lighting ambiance and typical application scenarios. | **Colour Temperature** | **Colour** | **Atmosphere** | **Scene** | | --- | --- | --- | --- | | 2700 K | Warm white | Comfortable, warm | Living room, bedroom | | 3000 K | Bright and warm white | Warm, slightly brighter | Living space, restaurant | | 3500 K | Natural white | Neutral, friendly | Corridor, office, showroom | | 4000 K | Natural white | Bright | Bathroom, kitchen, basement, garage | | ≥5300 K | Daylight white | Similar to daylight, high blue ratio | Industrial area, classroom | > [!NOTE] > **NOTE:** > > When selecting DALI lights that support colour temperature or colour adjustment, pay attention to the light type - DT6 or DT8 - as their control methods differ. DT6 occupies two DALI addresses, while DT8 uses only one. Using two DALI addresses per light reduces the total number of lights that can be controlled on the DALI bus by half. ### ### 4.2.11 RGB(W) Adjustment A colour can be created by mixing different single colours (RGB or RGBW), based on the mixing ratio of the individual channels (e.g., 50% red, 0% green, 60% blue). The resulting colour is not fully precise and depends largely on the physical properties of the LEDs (wavelength, intensity). Still, indicating the percentage of each primary colour provides a useful relative description. DT8 ballasts can set colours via a 3-byte object (RGB) or 6-byte object (RGBW). According to DALI standard EN 62386-209, up to six colours (RGBWAF) can be set. However, the DALI-2 gateway currently supports up to four colours, which aligns with the commonly used ECG types on the market. ### ### 4.2.12 XY Adjustment This method defines colours using two coordinates (x-y) in the colour space. Any point within this space represents a selectable colour. ![](https://cdn.document360.io/f09a6106-e976-455e-b2d0-3d88b5385960/Images/Documentation/pda-image-wafxpzl0.png) For devices supporting the x-y method, colour is set using two values between 0 and 1.0. Due to the physical characteristics of LEDs, not all colours are achievable; the closest available value is usually used. > [!NOTE] > **NOTE:** > > x and y values should follow the manufacturer’s instructions for ECGs and lights. Values outside the specified range may produce incorrect or unachievable colours. ### ### 4.2.13 Motion and Brightness Sensor The DALI gateway supports up to 8 motion and brightness sensors per output channel. DALI motion sensors can control devices on the KNX bus by sending telegrams for switches, scenes, brightness values, etc., to KNX actuators, or can work together with brightness sensors for combined control. > [!NOTE] > **NOTE:** > > Only DALI motion and brightness sensors compliant with IEC 62386 Part 303/304 are supported. ## ## 4.3 Operation Steps This section outlines the required commissioning flow for newly installed or updated DALI projects using the DCA tool: 1. Ensure ETS is licensed an running with a valid dongle, and install the DCA .etsapp file into the ETS. 2. Short-press the gateway’s Test/Set button to broadcast switch all devices and identify any unconnected DALI devices. 3. Configure device parameters via ETS and download them to the gateway. > [!NOTE] > **NOTE:** > > ECG devices in ETS are initially matched to DALI driver addresses; this can be adjusted via DCA. 1. Enter the DCA editing interface, select the commission channel, and read the device status. 2. Initialization: Click “[All] init DALI device” or “[No Addr] init DALI device” to assign unique addresses to all drivers on the DALI bus. 3. Sync the DALI bus and obtain the DALI device list: Use the DCA tool to read the driver status. 4. Obtain ECG list: Click “Synchronize ETS data” to obtain the list of ECGs configured in the ETS. > [!NOTE] > **NOTE:** > > If no database file is available, click “Sync. Gateway” to use cached gateway data. 1. Modify the correlation between ECG and DALI driver and download it to the gateway. Methods: - Drag the ECG grid to the target driver address. - Right-click a device grid and select “Modify Address”. > [!NOTE] > **NOTE:** > > Ensure ECG type matches the driver type; otherwise, DCA will report an error. 1. Configure DALI driver parameters: Double-click the device grid to enter the driver configuration page and modify device and scene settings. > [!NOTE] > **NOTE:** > > Driver configuration changes take effect only after being applied and sent from the configuration page; otherwise, they will not be valid. 1. Click “Sync. Gateway” to read the data in the gateway and check whether the sent data is correct. > [!NOTE] > **NOTE:** > > - If the above steps are not followed, DALI devices may not operate according to the preset values. > - In the address allocation phase, if there is an incomplete allocation address, start the initialization without address allocation operation (by DCA tool). If address allocation still fail more than twice, then you need to start the DALI bus initialization operation (by DCA tool or long press the Test/set button on the KNX-DALI-2 Gateway for more than 5 seconds), this operation may cause the DALI device addressed to occur change, you need to check the correspondence between the ECG and the driver address after configuration to ensure that the device type set by the ECG needs to be the same as the type of the actual driver, otherwise some of the functions will not be controlled. > - During address allocation, if any address assignment is incomplete, perform Initialize DALI devices(no address) via the DCA tool. If the allocation still fails after two attempts, initialize the DALI bus (using the DCA tool or by pressing and holding the Test/Set button on the DALI Gateway for over 5 seconds). This operation may change the assigned DALI device addresses. Afterward, verify that each ECG matches the correct driver address and that the configured ECG type is consistent with the actual driver type, otherwise certain functions may not work properly. 1. Export configuration, and save the gateway configuration.