3.3.2 HVAC

Prev Next

Figure 3.3.2 HVAC function Communication Objects

No.

Object function

Name

Type

Flags

DPT

161

External temperature sensor

Page x- HVAC Input

2byte

C,W,T,U

9.001 temperature(℃)

This communication object is used to receive temperature measurement values from temperature sensors on the bus.

- Range:

-50 ~ 99.8°C

162

Setpoint adjustment

Page x- HVAC Input

2byte

C,W

9.001 temperature  (℃)

When the HVAC operation mode is disabled, this object is used to modify the baseline value of the set temperature.

When the HVAC operation mode is enabled and the set temperature is set to be relative adjustment, this object is used to modify the baseline value of the set temperature. Specifically, it adjusts the temperature setting value of the Comfort mode, while the setting temperature of the Standby and the Economy modes change according to the relative change. In Protection mode, only the protection mode temperature is modified.

When the HVAC operation mode is enabled and the set temperature is adjusted absolutely, this object is used to modify the set temperature value of the current operation mode.

163

Switch Heating/Cooling mode

Page x- HVAC Input

1bit

C,W,U

1.100 cooling/heating

This communication object is used to receive status feedback from heaters and coolers on the bus.

The display on the screen will be updated according to the received telegram value.

- Telegram values

1: Heating

0: Cooling

164

HVAC mode

Page x- HVAC Input

1byte

C,W

20.102 HVAC mode

164

Comfort mode

Page x- HVAC Input

1bit

C,W

1.003 enable

165

Standby mode

Page x- HVAC Input

1bit

C,W

1.003 enable

166

Economy mode

Page x- HVAC Input

1bit

C,W

1.003 enable

167

Frost/heat protection mode

Page x- HVAC Input

1bit

C,W

1.003 enable

The operation mode can receive status feedback through either four 1-bit objects (Objects 164, 165, 166, 167) or one 1-byte object (HVAC mode).

  • When using 1bit objects

Object 164: Comfort mode

Object 165: Standby mode

Object 166: Economy mode

Object 167: Frost/heat protection mode

When any of these objects receive a telegram “1”, the corresponding mode will be activated. The mode display status on the screen will also update accordingly.

  • When using 1byte object

Input values and their corresponding operation modes are as follows:

0: Reserved

1: Comfort mode

2: Standby mode

3: Economy mode

4: Frost/heat protection mode

5-255: Reserved, not used

168

Fan speed

Page x- HVAC Input

1byte

C,W ,U

5.001 percentage(0..100%)

168

Fan speed low

Page x- HVAC Input

1bit

C,W ,U

1.001 switch

169

Fan speed medium

Page x- HVAC Input

1bit

C,W ,U

1.001 switch

170

Fan speed high

Page x- HVAC Input

1bit

C,W ,U

1.001 switch

171

Fan speed off

Page x- HVAC Input

1bit

C,W ,U

1.001 switch

The fan speed can receive status feedback through either four 1-bit objects (Objects 168, 169, 170, 171) or one 1-byte object (Fan speed).

  • When using 1bit objects

Object 168: Low fan speed

Object 169: Medium fan speed

Object 170: High fan speed

Object 171: Fan speed off

When any of these objects receive a telegram “1”, the corresponding fan speed will be activated. The fan speed display status on the screen will also update accordingly. When the fan speed is off, the telegram value for all fan speeds must be 0.

  • When using 1byte object

Fan speed status values are defined by parameters. When the object receives the specified value, the fan speed display status on the screen will update to the corresponding fan speed.

172

Fan Automatic operation

Page x- HVAC Input

1bit

C,W,U

1.003 enable

This object is used to receive status feedback from auto control of fan speed.

- Telegram values

1: Auto mode

0: Exit auto mode

173

Instantaneous setpoint

Page x- HVAC output

2bytes

C,R,T

9.001 temperature(℃)

This object is used to send the set temperature value of the current operating mode to the bus.

174

Heating/Cooling mode

Page x- HVAC output

1bit

C,R,T

1.100 cooling/heating

This object is used to send telegrams of switching between heating and cooling functions to the bus.

- Telegram values

1: Heating

0: Cooling

175

HVAC mode

Comfort mode

Page x- HVAC output

1byte

1bit

C,R,T

C,T

20.102 DPT_HVAC Mode

1.003enable

176

Standby mode

Page x- HVAC output

1bit

C,T

1.003enable

177

Economy mode

Page x- HVAC output

1bit

C,T

1.003enable

178

Frost/Heat protection mode

Page x- HVAC output

1bit

C,T

1.003enable

These communication objects are used to send telegrams of the operation mode to the bus.

  • When the object type is 1byte

0: Reserved

1: Comfort mode

2: Standby mode

3: Economy mode

4: Frost/heat protection mode

5~255: Reserved, not used

  • When the object type is 1bit

Upon switching to the specific mode, the mode will send a telegram "1" to the bus.

179

Heating /cooling control value

Page x- HVAC output

1byte

1bit

C,T

5.001 percentage(0..100%)

1.001 switch

179

Heating control value

Page x- HVAC output

1byte

1bit

C,T

5.001 percentage(0..100%)

1.001 switch

180

Cooling control value

Page x- HVAC output

1byte

1bit

C,T

5.001 percentage(0..100%)

1.001 switch

This object sends control values of heating or cooling functions to regulate the HVAC valve, thereby adjusting the indoor temperature.

- Telegram values

Switch on/off use - 2-point control: On/off

Switch PWM - use PI control: On/off

Continuous control - use PI control: 0 ... 100%

181

Fan speed

Fan speed low

Page x- HVAC output

1byte

1bit

C,T

5.001 percentage(0..100%)

1.001 switch

182

Fan speed medium

Page x- HVAC output

1bit

C,T

1.001 switch

183

Fan speed high

Page x- HVAC output

1bit

C,T

1.001 switch

184

Fan speed off

Page x- HVAC output

1bit

C,T

1.001 switch

These communication objects are used to send control telegrams for fan speed to the bus.

  • When using 1bit objects

Object 181: Low fan speed

Object 182: Medium fan speed

Object 183: High fan speed

Object 184: Fan speed off

Activating the corresponding fan speed on the screen triggers the respective object to send a telegram “1” to the bus, except for the fan speed off telegram, which is “0”.

  • When using 1byte objects

The telegram value of each fan speed level is defined by parameters.

Activating the corresponding fan speed on the screen triggers the Object 181 to send the specific fan speed value to the bus.

185

Fan Automatic operation

Page x- HVAC output

1bit

C,T

1.003 enable

This communication object is used to send auto control telegrams for fan speed to the bus.

- Telegram values

1: Auto mode

0: Exit auto mode

186

HVAC on/off

Page x- HVAC output

1bit

C,W,T,U

1.001 switch

This object is used to control the HVAC (Heating, Ventilation, and Air Conditioning) function of the device.

When turning off the HVAC, corresponding controls are deactivated.

187

Base setpoint temperature

Page x- HVAC output

2bytes

C,R,T

9.001 temperature(℃)

This object is visible when the HVAC operation mode is enabled and the temperature adjustment mode is set to relative adjustment. It is used to send the baseline set temperature value to the bus.

Table 3.3.2 HVAC function Communication Object Table