Figure 3.3.2 HVAC function Communication Objects
No. | Object function | Name | Type | Flags | DPT | |||
161 | External temperature sensor | Page x- HVAC Input | 2byte | C,W,T,U | 9.001 temperature(℃) | |||
This communication object is used to receive temperature measurement values from temperature sensors on the bus. - Range: -50 ~ 99.8°C | ||||||||
162 | Setpoint adjustment | Page x- HVAC Input | 2byte | C,W | 9.001 temperature (℃) | |||
When the HVAC operation mode is disabled, this object is used to modify the baseline value of the set temperature. When the HVAC operation mode is enabled and the set temperature is set to be relative adjustment, this object is used to modify the baseline value of the set temperature. Specifically, it adjusts the temperature setting value of the Comfort mode, while the setting temperature of the Standby and the Economy modes change according to the relative change. In Protection mode, only the protection mode temperature is modified. When the HVAC operation mode is enabled and the set temperature is adjusted absolutely, this object is used to modify the set temperature value of the current operation mode. | ||||||||
163 | Switch Heating/Cooling mode | Page x- HVAC Input | 1bit | C,W,U | 1.100 cooling/heating | |||
This communication object is used to receive status feedback from heaters and coolers on the bus. The display on the screen will be updated according to the received telegram value. - Telegram values 1: Heating 0: Cooling | ||||||||
164 | HVAC mode | Page x- HVAC Input | 1byte | C,W | 20.102 HVAC mode | |||
164 | Comfort mode | Page x- HVAC Input | 1bit | C,W | 1.003 enable | |||
165 | Standby mode | Page x- HVAC Input | 1bit | C,W | 1.003 enable | |||
166 | Economy mode | Page x- HVAC Input | 1bit | C,W | 1.003 enable | |||
167 | Frost/heat protection mode | Page x- HVAC Input | 1bit | C,W | 1.003 enable | |||
The operation mode can receive status feedback through either four 1-bit objects (Objects 164, 165, 166, 167) or one 1-byte object (HVAC mode).
Object 164: Comfort mode Object 165: Standby mode Object 166: Economy mode Object 167: Frost/heat protection mode When any of these objects receive a telegram “1”, the corresponding mode will be activated. The mode display status on the screen will also update accordingly.
Input values and their corresponding operation modes are as follows: 0: Reserved 1: Comfort mode 2: Standby mode 3: Economy mode 4: Frost/heat protection mode 5-255: Reserved, not used | ||||||||
168 | Fan speed | Page x- HVAC Input | 1byte | C,W ,U | 5.001 percentage(0..100%) | |||
168 | Fan speed low | Page x- HVAC Input | 1bit | C,W ,U | 1.001 switch | |||
169 | Fan speed medium | Page x- HVAC Input | 1bit | C,W ,U | 1.001 switch | |||
170 | Fan speed high | Page x- HVAC Input | 1bit | C,W ,U | 1.001 switch | |||
171 | Fan speed off | Page x- HVAC Input | 1bit | C,W ,U | 1.001 switch | |||
The fan speed can receive status feedback through either four 1-bit objects (Objects 168, 169, 170, 171) or one 1-byte object (Fan speed).
Object 168: Low fan speed Object 169: Medium fan speed Object 170: High fan speed Object 171: Fan speed off When any of these objects receive a telegram “1”, the corresponding fan speed will be activated. The fan speed display status on the screen will also update accordingly. When the fan speed is off, the telegram value for all fan speeds must be 0.
Fan speed status values are defined by parameters. When the object receives the specified value, the fan speed display status on the screen will update to the corresponding fan speed. | ||||||||
172 | Fan Automatic operation | Page x- HVAC Input | 1bit | C,W,U | 1.003 enable | |||
This object is used to receive status feedback from auto control of fan speed. - Telegram values 1: Auto mode 0: Exit auto mode | ||||||||
173 | Instantaneous setpoint | Page x- HVAC output | 2bytes | C,R,T | 9.001 temperature(℃) | |||
This object is used to send the set temperature value of the current operating mode to the bus. | ||||||||
174 | Heating/Cooling mode | Page x- HVAC output | 1bit | C,R,T | 1.100 cooling/heating | |||
This object is used to send telegrams of switching between heating and cooling functions to the bus. - Telegram values 1: Heating 0: Cooling | ||||||||
175 | HVAC mode Comfort mode | Page x- HVAC output | 1byte 1bit | C,R,T C,T | 20.102 DPT_HVAC Mode 1.003enable | |||
176 | Standby mode | Page x- HVAC output | 1bit | C,T | 1.003enable | |||
177 | Economy mode | Page x- HVAC output | 1bit | C,T | 1.003enable | |||
178 | Frost/Heat protection mode | Page x- HVAC output | 1bit | C,T | 1.003enable | |||
These communication objects are used to send telegrams of the operation mode to the bus.
0: Reserved 1: Comfort mode 2: Standby mode 3: Economy mode 4: Frost/heat protection mode 5~255: Reserved, not used
Upon switching to the specific mode, the mode will send a telegram "1" to the bus. | ||||||||
179 | Heating /cooling control value | Page x- HVAC output | 1byte 1bit | C,T | 5.001 percentage(0..100%) 1.001 switch | |||
179 | Heating control value | Page x- HVAC output | 1byte 1bit | C,T | 5.001 percentage(0..100%) 1.001 switch | |||
180 | Cooling control value | Page x- HVAC output | 1byte 1bit | C,T | 5.001 percentage(0..100%) 1.001 switch | |||
This object sends control values of heating or cooling functions to regulate the HVAC valve, thereby adjusting the indoor temperature. - Telegram values Switch on/off use - 2-point control: On/off Switch PWM - use PI control: On/off Continuous control - use PI control: 0 ... 100% | ||||||||
181 | Fan speed Fan speed low | Page x- HVAC output | 1byte 1bit | C,T | 5.001 percentage(0..100%) 1.001 switch | |||
182 | Fan speed medium | Page x- HVAC output | 1bit | C,T | 1.001 switch | |||
183 | Fan speed high | Page x- HVAC output | 1bit | C,T | 1.001 switch | |||
184 | Fan speed off | Page x- HVAC output | 1bit | C,T | 1.001 switch | |||
These communication objects are used to send control telegrams for fan speed to the bus.
Object 181: Low fan speed Object 182: Medium fan speed Object 183: High fan speed Object 184: Fan speed off Activating the corresponding fan speed on the screen triggers the respective object to send a telegram “1” to the bus, except for the fan speed off telegram, which is “0”.
The telegram value of each fan speed level is defined by parameters. Activating the corresponding fan speed on the screen triggers the Object 181 to send the specific fan speed value to the bus. | ||||||||
185 | Fan Automatic operation | Page x- HVAC output | 1bit | C,T | 1.003 enable | |||
This communication object is used to send auto control telegrams for fan speed to the bus. - Telegram values 1: Auto mode 0: Exit auto mode | ||||||||
186 | HVAC on/off | Page x- HVAC output | 1bit | C,W,T,U | 1.001 switch | |||
This object is used to control the HVAC (Heating, Ventilation, and Air Conditioning) function of the device. When turning off the HVAC, corresponding controls are deactivated. | ||||||||
187 | Base setpoint temperature | Page x- HVAC output | 2bytes | C,R,T | 9.001 temperature(℃) | |||
This object is visible when the HVAC operation mode is enabled and the temperature adjustment mode is set to relative adjustment. It is used to send the baseline set temperature value to the bus. | ||||||||
Table 3.3.2 HVAC function Communication Object Table