Figure 3.3.3-1 Air conditioner setting 1byte Communication Object

Figure 3.3.3-2 Air conditioner setting 1bit Communication Object
No. | Object function | Name | Type | Flags | DPT | ||||||
161 | External temperature sensor, In | Page x-AC | 2bytes | C,W,T,U | 9.001 temperature(℃) | ||||||
This communication object is used to receive temperature measurement values from the indoor temperature sensor on the bus and display the indoor temperature on the screen. | |||||||||||
162 | Power on/off,Out | Page x-AC | 1bit | C,T | 1.001 switch | ||||||
Power on/off: Send air conditioner power switch telegrams. | |||||||||||
163 | Status of Power,In | Page x-AC | 1bit | C,W,T,U | 1.001 switch | ||||||
This object is visible in Gateway mode and is used to receive feedback of power switch status. | |||||||||||
164 | Control mode,Out | Page x-AC | 1byte | C,T | 20.105 HAVC control mode | ||||||
164 | Heat mode,In/Out | Page x-AC | 1bit | C,W,T,U | 1.003 enable | ||||||
This object is visible in Gateway mode when the mode type is 1byte. It is used to send control telegrams for various modes.
This object is visible in Gateway mode when the mode type is 1bit. It is used to send control telegrams for the heating mode and receive status feedback. | |||||||||||
165 | Status of control mode,In | Page x-AC | 1byte | C,W,T,U | 20.105 HAVC control mode | ||||||
165 | Cool mode,In/Out | Page x-AC | 1bit | C,W,T,U | 1.003 enable | ||||||
This object is visible in Gateway mode when the mode type is 1byte. It is used to receive feedback telegrams for various modes.
This object is visible in Gateway mode when the mode type is 1 bit. It is used to send control telegrams for the cooling mode and receive status feedback. | |||||||||||
166 | Dry mode,In/Out | Page x-AC | 1bit | C,W,T,U | 1.003 enable | ||||||
This communication object is visible in air conditioner gateway mode when the mode type is 1bit. It is used to send control telegrams for the dry mode of the air conditioner and can also receive status feedback. | |||||||||||
167 | Fan mode,In/Out | Page x-AC | 1bit | C,W,T,U | 1.003 enable | ||||||
This object is visible in Gateway mode when the fan speed type is 1bit. It is used to send control telegrams for the fan mode and receive status feedback. | |||||||||||
168 | Auto mode,In/Out | Page x-AC | 1bit | C,W,T,U | 1.003 enable | ||||||
This object is visible in Gateway mode when the fan speed type is 1bit. It is used to send control telegrams for the auto mode and receive status feedback. | |||||||||||
169 | Fan speed,Out | Page x-AC | 1byte | C,T | 5.001 percentage(0..100%) | ||||||
169 | Fan speed low,In/Out | Page x-AC | 1bit | C,W,T,U | 1.001 switch | ||||||
This object is visible in Gateway mode when the fan speed type is 1byte. It is used to send control telegrams for various fan speeds.
This object is visible in Gateway mode when the fan speed type is 1bit. It is used to send control telegrams for low fan speed and receive status feedback. | |||||||||||
170 | Status of Fan speed,In | Page x-AC | 1byte | C,W,T,U | 5.001 percentage(0..100%) | ||||||
170 | Fan speed medium | Page x-AC | 1bit | C,W,T,U | 1.001 switch | ||||||
This communication object is visible in air conditioner gateway mode when the fan speed type is 1byte. It is used to receive status feedback telegrams for various fan speeds.
This communication object is visible in air conditioner gateway mode when the fan speed type is 1 bit. It is used to send control telegrams for Fan speed medium and can also receive status feedback. | |||||||||||
171 | Fan speed high | Page x-AC | 1bit | C,W,T,U | 1.001 switch | ||||||
This object is visible in Gateway mode when the fan speed type is 1bit. It is used to send control telegrams for high fan speed and receive status feedback. | |||||||||||
172 | Fan speed Auto,In/Out | Page x-AC | 1bit | C,W,T,U | 1.001 switch | ||||||
This object is visible in Gateway mode when the fan speed type is 1bit. It is used to send control telegrams for auto fan speed and receive status feedback. | |||||||||||
173 | Wind direction fixed/swing,In/Out | Page x-AC | 1bit | C,W,T,U | 1.017 trigger | ||||||
This object is visible in Gateway mode when the wind direction adjustment is enabled. It is used to send control telegrams for adjusting the wind direction. - Telegram values 1: Swing wind direction 0: Fixed wind direction | |||||||||||
174 | Wind direction position,Out | Page x-AC | 1byte | C,T | 5.010 counter pulses(0..255) | ||||||
This object is visible in Gateway mode when the wind direction adjustment is enabled. It is used to send control telegrams for setting the fixed wind direction position from 1 to 5. | |||||||||||
175 | Status of Wind direction position,In | Page x-AC | 1byte | C,W,T,U | 5.010 counter pulses(0..255) | ||||||
This object is visible in Gateway mode when the wind direction adjustment is enabled. It is used to receive status feedback telegrams of the fixed wind direction positions ranging from 1 to 5. | |||||||||||
176 | Temperature setpoint, In/Out | Page x-AC | 1byte 2byte | C,W,T,U | 5.010 counter pulses(0..255) 9.001 temperature(℃) | ||||||
This object is visible in Gateway mode and is used to send and receive the set temperature.
| |||||||||||
Table 3.3.3 Air conditioner Communication Object Table