Figure 3.3.6 Air Quality display function Communication Object
No. | Object function | Name | Type | Flags | DPT | |||||
161 | AQI,In | Page x-Air Quality | 2bytes | C,W,T,U | 7.001 pulses | |||||
This object is used to receive inputs of AQI value and update the display with the value obtained from the bus. - Range: 0 ... 500 | ||||||||||
162 | PM2.5,In | Page x-Air Quality | 2bytes | C,W,T,U | 9.030 concentration(ug/m3) 7.001 pulses | |||||
This object is used to receive inputs of PM2.5 value and update the display with the value obtained from the bus. The unit is micrograms per cubic meter (ug/m3). The data type of the object is determined by the parameter settings. - Range: 0 ... 999 | ||||||||||
163 | PM10,In | Page x-Air Quality | 2bytes | C,W,T,U | 9.030 concentration(ug/m3) 7.001 pulses | |||||
This object is used to receive inputs of PM10 value and update the display with the value obtained from the bus. The unit is ug/m3. The data type of the object is determined by the parameter settings. - Range: 0 ... 999 | ||||||||||
164 | Temperature,In | Page x-Air Quality | 2bytes | C,W,T,U | 9.001 temperature(℃) | |||||
This object receives temperature measurement values from the temperature sensor on the bus. - Range: -40~40℃ | ||||||||||
165 | Humidity,In | Page x-Air Quality | 2bytes | C,W,T,U | 9.007 humidity(%) | |||||
This object is used to receive humidity measurement values from the humidity sensor on the bus. - Range: 0 ... 100%. | ||||||||||
166 | VOC,In | Page x-Air Quality | 2bytes | C,W,T,U | 9.008 parts/million(ppm) 7.001 pulses 9.030 concentration(ug/m3) | |||||
This communication object is used to receive VOC values sent from the VOC sensor on the bus. The unit is ug/m3. The data type of the object is determined by parameters. - Range: 0 ... 9.99 When the object data type is set to 7.001 pulses, it is scaled down by a factor of 1000 based on the data point type 7.001 pulses. For example, if the received value is 5000 (μg/m³), it would be displayed as 5.00 mg/m³. | ||||||||||
167 | CO2,In | Page x-Air Quality | 2bytes | C,W,T,U | 9.008 parts/million(ppm) | |||||
This object is used to receive CO2 (Carbon Dioxide) values sent from the CO2 sensor on the bus. The unit is ppm. - Range: 0 ... 4000 | ||||||||||
168 | Brightness,In | Page x-Air Quality | 2bytes | C,W,T,U | 7.013 brightness(lux) 9.004 lux(Lux) | |||||
This object receives input brightness values from the bus and updates the display accordingly. The unit is lux. The data type of the object is determined by parameters. - Range: 0 ... 5000 | ||||||||||
169 | Windspeed | Page x-Air Quality | 2bytes | C,W,T,U | 9.005 speed(m/s) | |||||
This object receive the input of wind speed values from the bus and updates the display accordingly. The unit is m/s. - Range: 0 ... 50 | ||||||||||
Table 3.3.6 Air Quality display function Communication Object Table