3.3.6 Air Quality display

Prev Next

Figure 3.3.6 Air Quality display function Communication Object

No.

Object function

Name

Type

Flags

DPT

161

AQI,In

Page x-Air Quality

2bytes

C,W,T,U

7.001 pulses

This object is used to receive inputs of AQI value and update the display with the value obtained from the bus.

- Range: 0 ... 500

162

PM2.5,In

Page x-Air Quality

2bytes

C,W,T,U

9.030 concentration(ug/m3)

7.001 pulses

This object is used to receive inputs of PM2.5 value and update the display with the value obtained from the bus. The unit is micrograms per cubic meter (ug/m3). The data type of the object is determined by the parameter settings.

- Range: 0 ... 999

163

PM10,In

Page x-Air Quality

2bytes

C,W,T,U

9.030 concentration(ug/m3)

7.001 pulses

This object is used to receive inputs of PM10 value and update the display with the value obtained from the bus. The unit is ug/m3. The data type of the object is determined by the parameter settings.

- Range: 0 ... 999

164

Temperature,In

Page x-Air Quality

2bytes

C,W,T,U

9.001 temperature(℃)

This object receives temperature measurement values from the temperature sensor on the bus.

- Range: -40~40℃

165

Humidity,In

Page x-Air Quality

2bytes

C,W,T,U

9.007 humidity(%)

This object is used to receive humidity measurement values from the humidity sensor on the bus.

- Range: 0 ... 100%.

166

VOC,In

Page x-Air Quality

2bytes

C,W,T,U

9.008 parts/million(ppm)

7.001 pulses

9.030 concentration(ug/m3)

This communication object is used to receive VOC values sent from the VOC sensor on the bus. The unit is ug/m3. The data type of the object is determined by parameters.

- Range: 0 ... 9.99

When the object data type is set to 7.001 pulses, it is scaled down by a factor of 1000 based on the data point type 7.001 pulses. For example, if the received value is 5000 (μg/m³), it would be displayed as 5.00 mg/m³.

167

CO2,In

Page x-Air Quality

2bytes

C,W,T,U

9.008 parts/million(ppm)

This object is used to receive CO2 (Carbon Dioxide) values sent from the CO2 sensor on the bus. The unit is ppm.

- Range: 0 ... 4000

168

Brightness,In

Page x-Air Quality

2bytes

C,W,T,U

7.013 brightness(lux)

9.004 lux(Lux)

This object receives input brightness values from the bus and updates the display accordingly. The unit is lux. The data type of the object is determined by parameters.

- Range: 0 ... 5000

169

Windspeed

Page x-Air Quality

2bytes

C,W,T,U

9.005 speed(m/s)

This object receive the input of wind speed values from the bus and updates the display accordingly. The unit is m/s.

- Range: 0 ... 50

Table 3.3.6 Air Quality display function Communication Object Table