3.3.7 Floor heating

Prev Next

Figure 3.3.7 Floor heating function Communication Object

No.

Object function

Name

Type

Flags

DPT

161

External temperature sensor, In

Page x-Floor heating

2bytes

C,W,T,U

9.001 temperature(℃)

This object is visible when the temperature reference is set to an external sensor.

It is used to receive temperature measurement values sent from a temperature sensor on the bus.

-Range: -50 ... 99.8°C

162

Power on/off, In/Out

Page x-Floor heating

1bit

C,W,T,U

1.001 switch

This object is used to send switch control telegrams for underfloor heating and receive control status feedback.

-Telegram values

1: Underfloor heating control interface on, interface operable.

0: Underfloor heating control interface off, interface not operable.

NOTE:

In the off state, all interface icons except for the timer and switch icons are non-operational.

163

Heating on/off, In/Out

Page x-Floor heating

1bit

C,W,T,U

1.001 switch

163

Heating control value, Out

Page x-Floor heating

1byte

C,W,T,U

5.001 percentage (0..100%)

This object is used to send control values for floor heating, controlling the opening and closing of the underfloor heating valve.

- Telegram values

Heating on/off - 2-point control: On/off

Heating PWM - use PI control: On/off

Heating continuous control - use PI control: 0 ... 100%

164

Setpoint , In/Out

Page x-Floor heating

2bytes

C,W,T,U

9.001 temperature(℃)

This object is used to send temperature setting values to the bus and to receive feedback of the temperature setting values.

- Range: 5 ... 40°C.

165

En./Dis. Timer, In

Page x-Floor heating

1bit

C,W

1.003 enable

This object is used to enable or disable the timer function of the floor heating system. The specific values are defined by parameters.

166

Scene, In

Page x-Floor heating

1byte

C,W

18.001 scene control

This object is used to control the scenes of the floor heating system.

Parameter settings range from 1 to 64, correlating to actual telegram values from 0 to 63.

Table 3.3.7 Floor heating functional Communication Object Table