Figure 3.3.7 Floor heating function Communication Object
No. | Object function | Name | Type | Flags | DPT |
161 | External temperature sensor, In | Page x-Floor heating | 2bytes | C,W,T,U | 9.001 temperature(℃) |
This object is visible when the temperature reference is set to an external sensor. It is used to receive temperature measurement values sent from a temperature sensor on the bus. -Range: -50 ... 99.8°C | |||||
162 | Power on/off, In/Out | Page x-Floor heating | 1bit | C,W,T,U | 1.001 switch |
This object is used to send switch control telegrams for underfloor heating and receive control status feedback. -Telegram values 1: Underfloor heating control interface on, interface operable. 0: Underfloor heating control interface off, interface not operable.
| |||||
163 | Heating on/off, In/Out | Page x-Floor heating | 1bit | C,W,T,U | 1.001 switch |
163 | Heating control value, Out | Page x-Floor heating | 1byte | C,W,T,U | 5.001 percentage (0..100%) |
This object is used to send control values for floor heating, controlling the opening and closing of the underfloor heating valve. - Telegram values Heating on/off - 2-point control: On/off Heating PWM - use PI control: On/off Heating continuous control - use PI control: 0 ... 100% | |||||
164 | Setpoint , In/Out | Page x-Floor heating | 2bytes | C,W,T,U | 9.001 temperature(℃) |
This object is used to send temperature setting values to the bus and to receive feedback of the temperature setting values. - Range: 5 ... 40°C. | |||||
165 | En./Dis. Timer, In | Page x-Floor heating | 1bit | C,W | 1.003 enable |
This object is used to enable or disable the timer function of the floor heating system. The specific values are defined by parameters. | |||||
166 | Scene, In | Page x-Floor heating | 1byte | C,W | 18.001 scene control |
This object is used to control the scenes of the floor heating system. Parameter settings range from 1 to 64, correlating to actual telegram values from 0 to 63. | |||||
Table 3.3.7 Floor heating functional Communication Object Table