3.4 Communication objects of “Time function”

Prev Next

Figure 3.4 Time function Communication Object

No.

Object function

Name

Type

Flags

DPT

481

On/Off

Time function x

1bit

C,T

1.001 switch

483

1byte unsigned value

Time function x

1byte

C,T

5.010 counter pulses(0..255)

485

Scene control

Time function x

1byte

C,T

17.001 scene number

487

2byte unsigned value

Time function x

2byte

C,T

7.001 pulses

This object is used to send preset telegram values for time function to the bus. The timing interval, preset value, and object type are set by parameters. Once the set time is reached, the preset telegram value will be sent to the bus. A total of 16 timers can be configured (x = 16).

484

Disable/En

Time function x

1bit

C,W

1.003 enable

This object is used to disable/enable the time function x.

The specific values for disabling/enabling are defined by parameters. When disabled, timed function x will not be activated.

513

Dis./En. Monday Time

Time function

1bit

C,W

1.003 enable

514

Dis./En. Tuesday Time

Time function

1bit

C,W

1.003 enable

515

Dis./En. Wednesday Time

Time function

1bit

C,W

1.003 enable

516

Dis./En. Thursday Time

Time function

1bit

C,W

1.003 enable

517

Dis./En. Friday Time

Time function

1bit

C,W

1.003 enable

518

Dis./En. Saturday Time

Time function

1bit

C,W

1.003 enable

519

Dis./En. Sunday Time

Time function

1bit

C,W

1.003 enable

This object is used to enable or disable a weekly timer via the bus, allowing activation or deactivation of a timer for a specific day of the week.

Table 3.4 Time function Communication Object Table