Figure 3.3.9 Energy metering display function Communication Object
No. | Object function | Name | Type | Flags | DPT | |||
161 | Current in mA(DPT 7.012) | Page x-Energy Meter y | 2bytes | C,W,T,U | 7.012 current (mA) | |||
This object is used to receive the current value from the bus and update it on the display. - Display range: 0 ~ 65535 mA, with a resolution of 1 mA. | ||||||||
162 | Current in mA(DPT 9.021) | Page x-Energy Meter y | 2bytes | C,W,T,U | 9.021 current (mA) | |||
This object is used to receive the current value from the bus and update it on the display. - Display range: -670760 ~ 670760 mA, with a resolution of 0.01 mA. | ||||||||
163 | Current in A(DPT 14.019) | Page x-Energy Meter y | 4bytes | C,W,T,U | 14.019 electric current (A) | |||
This object is used to receive the current value from the bus and update it on the display. - Display range: -99999999.9 ~ 99999999.9A , with a resolution of 0. 1A | ||||||||
164 | Voltage in mV(DPT 9.020) | Page x-Energy Meter y | 2bytes | C,W,T,U | 9.020 voltage (mV) | |||
This object is used to receive the voltage value from the bus and update it on the display. - Display range: -670760 ~ 670760mV, with a resolution of 0.01mV. | ||||||||
193 | Voltage in V(DPT 14.027) | Page x-Energy Meter y | 4bytes | C,W,T,U | 14.027 electric potential (V) | |||
This object is used to receive the voltage value from the bus and update it on the display. - Display range: -99999999.9 ~ 99999999.9V, with a resolution of 0. 1V. | ||||||||
194 | Power in W(DPT 14.056) | Page x-Energy Meter y | 4bytes | C,W,T,U | 14.056 power (W) | |||
This object is used to receive the power value from the bus and update it on the display. - Display range: -99999999.9 ~ 99999999.9W, with a resolution of 0. 1W. | ||||||||
195 | Power in kW(DPT 9.024) | Page x-Energy Meter y | 2bytes | C,W,T,U | 9.024 power (kW) | |||
This object is used to receive the power value from the bus and update it on the display. - Display range: -670760 ~ 670760kW, with a resolution of 0.01kW. | ||||||||
196 | Active energy in Wh(DPT 13.010) | Page x-Energy Meter y | 4bytes | C,W,T,U | 13.010 active energy (Wh) | |||
This object is used to receive the energy value from the bus and update it on the display. - Display range: -2147483648 ~ 2147483647Wh, with a resolution of 1Wh. | ||||||||
225 | Active energy in kWh(DPT 13.013) | Page x-Energy Meter y | 4bytes | C,W,T,U | 13.013 active energy (kWh) | |||
This object is used to receive the energy value from the bus and update it on the display. - Display range: -2147483648 ~ 2147483647kWh, with a resolution of 1kWh. | ||||||||
Table 3.3.9 Energy metering display function Communication Object Table