5.2 Parameter Setting Interface "General Setting"

Prev Next

5.2.1 "General setting"

Figure 5.2.1 "General setting" Interface

  • Device name

Sets the name of the K32 panel. This name is currently not displayed and is reserved for Phase II.

  • Interface Language

Sets the display language. Options: English, Persian, German, Arabic, Spanish, French, Hebrew, Italian, Dutch, Polish, Portuguese, Turkish, Russian, Ukrainian, Simplified Chinese, Traditional Chinese, Japanese, Korean, Other.

If the required language is not listed, select Other and enter the language in the Language Name field.

NOTE:

In Phase I, only English and Simplified Chinese are supported.

  • Language name

When Interface Language is set to Other, enter a language supported by HyPanel in this field. The HyPanel will apply the selected language accordingly.

If the entered language is not supported by the K32 panel, the display will remain in the language used before downloading the application.

NOTE:

In Phase I, only English and Simplified Chinese are supported.

  • Send cycle of"In operation" telegram [1…240s, 0 =inactive]

Sets the interval for cyclic transmission of the “In operation” telegram to indicate normal operation.

Options: 0...240s, 0=No telegram is sent.

To reduce bus load, select the longest interval that meets project requirements.

  • Date and Time can be changed via bus

Determines whether the date and time of the K32 panel can be modified via the bus.

Options:

  • No: Modification not allowed.

  • Yes: The objects “Date” and “Time” become visible. Configure the corresponding group objects as required.

  • Display T&H resource

Selects the temperature and humidity source displayed on the panel.

Options:

  • Internal Sensor: : Uses the built-in temperature and humidity sensor.

  • External Sensor: Uses an external temperature and humidity sensor.

NOTE:

Not supported in Phase I. Reserved for Phase II.

  • Temperature display units

Sets the temperature display unit.

Options:

  • Celsius(℃)

  • Fahrenheit(℉)

  • Screen brightness resource

Selects the light sensor source used for brightness control.

Options:

  • Internal Sensor: Uses the built-in light sensor.

  • External Sensor: Uses an external light sensor.

  • Sent brightness value to bus

Displayed when Screen brightness resource is set to Internal Sensor.

Determines whether the brightness value is sent to the bus.

Options:

  • No: Not sent.

  • Yes: The object “Screen backlight brightness” becomes visible. When brightness changes, the value is sent to the bus.

  • Automatic Brightness Control

Enables or disables automatic brightness adjustment.

Options:

  • No: Disabled.

  • Yes: The screen brightness adjusts automatically based on ambient light.

  • Screen Saver Times

Sets the time before the screen enters screen saver mode.

Options: 15s, 30s, 1min, 5mins, 10mins, 30mins, 1hr.

  • Floor

Specifies the floor where the K32 panel is located when added to the home center.

Not supported in Phase I. Reserved for Phase II.

  • Room

Specifies the room where the K32 panel is located when added to the home center.

Not supported in Phase I. Reserved for Phase II.

5.2.2 "Proximity setting"

The “Proximity setting” parameter interface is shown in Figure 5.2.2.

This section configures the proximity function, including the sensor source, detection distance, telegrams sent when a person approaches or leaves the detection area, and the delay time for telegram transmission.

Detection by the built-in sensor corresponds to “approaching”, while no detection corresponds to “leaving”.

Figure 5.2.2 "Proximity setting" Interface

  • Proximity

Enables/disables the proximity function.

Options:

  • Disable: The proximity function is disabled. The parameter “Proximity sensor source” is not displayed.

  • Enable: The proximity function is enabled. The K32 thermostat wakes up automatically based on the selected sensor source.

  • Proximity sensor resource

Displayed when Proximity is set to Enable.

Selects the source of the proximity sensor.

Options:

  • Internal Sensor: Uses the built-in proximity sensor. The parameters “Proximity sensor distance” and “Object type of output value” are displayed.

  • External Sensor: Uses an external proximity sensor. These additional parameters are not displayed.

  • Proximity sensor distance

Displayed when Proximity sensor source is set to Internal Sensor.

Sets the detection range of the built-in sensor.

Options:

  • Short distance: The screen wakes up when a person is detected within 30 cm.

  • Long distance: The screen wakes up when a person is detected within 60 cm.

  • Object type of output value

Displayed when Proximity sensor source is set to Internal Sensor.

Defines the data type of the telegram sent to the bus when the proximity status changes (approaching or leaving).

Options:

  • 1bit[On/Off]

  • 1byte[scene control]

  • 1 byte [0..255]

  • 1byte[0..100%]

  • Reaction for approaching/leaving

Determines whether a telegram is sent when a person approaches or leaves the detection area.

Options:

  • No action

  • Send a value: When this option is selected, the following setting parameters become visible:

  • Output value[On/Off]

  • Output scene NO.[1..64]

  • Output value[0..255]

  • Output value[0..100%]

These parameters define the telegram value sent to the bus. The available value range depends on the selected data type.

  • Delay time for sending[0..255]

Sets the delay time before sending the telegram.

Optional: 0.. . 255

NOTE:

If a “leaving” event occurs during the delay time of an “approaching” telegram, the approaching telegram is suppressed. A telegram is only sent when the proximity status changes.

5.2.3 "Internal temperature setting"

The “Internal temperature setting” interface is shown in Figure 5.2.3.

This section configures the parameters of the built-in temperature sensor.

Figure 5.2.3 "Internal temperature setting" Interface

  • Filter type

Defines the averaging level of the measurement filter before the temperature value is sent to the bus.

Options:

  • Low: Average of 4 measurements is sent to the bus.

  • Average: Average of 16 measurements is sent to the bus

  • High: Average of 64 measurements is sent to the bus.

  • Temperature offset

Sets the temperature correction value of the built-in sensor.

The offset adjusts the measured temperature to better match the actual ambient temperature. The offset affects only the telegram value sent to the bus and does not affect the panel display.

Options: -5℃~5℃

  • Minimum change of value to send[K] (0 means no value sent on change)

Defines the minimum temperature change required to trigger transmission of a new temperature value.

Options: 0...5 (0: No telegram is sent when the temperature changes.)

  • Cyclic sending interval

Sets the time interval for periodically sending temperature measurement values to the bus.

Options: 0...120 min

TIP:

The cyclic timer runs independently. It starts after programming or reset and is not affected by value-change transmission.