5.3 Parameter Setting Interface "Function"

Prev Next

5.3.1 "Function x"

Figure 5.3.1 "Function x" Interface

  • Function x(x=1..32)

Sets the device type. The default value is Disable.

Options:

  • Disable                          

  • HVAC                        

  • Air conditioner

  • Floor heating

  • Ventilation system

The following sections describe the parameter settings for each function.

5.3.2 "Function x--HVAC"

The parameter setting interface "Function x – HVAC" is shown in Figure 5.3.2.

This section mainly configures fan control parameters and basic HVAC control settings.

Figure 5.3.2 "Function x--HVAC" Interface

  • Description

Sets the device name. Maximum input: 31 characters. Maximum practical display: 10 Chinese characters.

  • Temperature reference from

Sets the source of temperature reference for HVAC.

Options:

  • Internal sensor: When selected, the temperature is determined by the built-in sensor settings in the “General sensor” interface.

  • External sensor

  • Internal sensor combine with External sensor

The following parameters are visible when an external temperature sensor is available in the options:

- Time period for request external sensor [0..255]min

Sets the interval for sending read requests to the external sensor.

Options: 0.. . 255

- Read external sensor after restart

Sets whether to read external sensor data after reset.

Options:

  • No: After bus power-on reset or programming, no immediate read request is sent. The request is sent after the cycle time expires.

  • Yes: A read request is sent to the external sensor immediately after bus power-on reset or programming.

The following parameters are visible when HVAC temperature acquisition uses a combination of internal and external sensors:

- Combination ratio

Sets the proportion of internal and external sensors for temperature measurement.

Options:

  • 10% Internal to 90% External

  • 20% Internal to 80% External

…

  • 80% Internal to 20% External

  • 90% Internal to 10% External

Example: if selecting "40% Internal to 60% External", then control temperature = (Internal × 40%) + (External × 60%). The device's HVAC function will perform temperature control and display based on the calculated temperature.

When two sensors are combined fordetection, if one sensor malfunctions, the temperature value detected by the other sensor is used.

  • Control value after temp.error[0..100%](If 2-point control, set value '0'=0, set value '>0'=1)

Sets the control value when a temperature error occurs.

Options: 0.. 100

In 2-point control mode:

  • Value = 0 → Control output = 0

  • Value > 0 → Control output = 1

  • Power on/off status after download

Sets the switch status of the HVAC interface after the application download.

Options:

  • Off

  • On

  • Power on/off status after bus recovery

Defines the HVAC interface status after bus power is restored.

Options:

  • On: The device powers on at startup. The interface is operable, and the HVAC performs internal computations based on the control mode to determine the current control state.

  • Off: The device remains off at power-up. The interface is not operable, and no computation or control is performed.

  • As before voltage failure: The device restores its state from before the power failure. If it was on, the HVAC performs internal computations based on the control mode to determine the current control state.

  • Control type of fan speed

Sets the data type for fan speed control.

Options:

  • Disable: Fan speed control is disabled.

  • 1bit: The object type for wind speed control is 1bit.

  • 1byte: The object type for fan speed control is 1byte. When selected, the HVAC_Fan parameter configuration sub-interface becomes visible. Go to HVAC_Fan_1byte to view detailed parameter settings.

  • Fan speed auto

Visible when previous parameter is 1bit or 1byte. Enables automatic fan speed operation.

Options:

  • Disable

  • Enable: When enabled, the fan speed includes automatic control.

  • HVAC control mode

Sets HVAC output control mode.

Options:

  • Heating: Heating only

  • Cooling: Cooling only

  • Heating and Cooling: Supports both.

When Heating and Cooling is selected, the following parameters are visible:

- Heating/Cooling status after restart

Sets HVAC output mode after device startup.

Options:

  • Heating

  • Cooling

  • As before reset: After bus power-on, restores pre-power-loss mode. After re-download, mode may be uncertain and requires manual selection.

- HVAC control system

Sets HVAC control system type.

Options:

  • 2 pipes system: A single valve controls both heating and cooling via one supply/return line.

  • 4 pipes system: Two valves control separate hot and chilled water lines for heating and cooling respectively.

  • HVAC operation mode

Sets whether to enable the HVAC operation mode.

Options:

  • Disable: Only temperature baseline is supported.

  • Enable: Mode switching supported.

When the HVAC operation mode is disabled, the following parameter is visible.

- Basic setpoint temperature [℃]

Sets the baseline setpoint temperature.

Options:

  • 10

  • 10.5

...

  • 35

When HVAC operation mode is enabled, the following four parameters become visible.

- Operating mode switchover

Sets object type for room operation mode switching.

Options:

  • 4x1bit: When 1bit is selected, four 1bit objects are visible:

  • HVAC Output--Comfort mode

  • HVAC Output--Economy mode

  • HVAC Output--standby mode

  • HVAC Output--Frost/Heat protection mode

Activating a mode triggers the corresponding object to send a telegram “1”; otherwise, it transmits “0”.

  • 1byte: When 1byte is selected, the object "HVAC Output -- HVAC mode" becomes visible, and the transmitted message value is:

  • "1" : Comfort Mode.

  • "2": Standby mode

  • "3" : Energy-saving mode.

  • "4" : Frost/Heat Protection mode

- Operating mode status

Sets object type for room operation mode feedback.

Options:

  • 4x1bit: The device switches among different modes based on the ON or OFF telegrams received by the following four 1-bit objects:

  • HVAC Input-- Comfort mode

  • HVAC Input-- Economy mode

  • HVAC Input-- Frost/Heat protection mode

  • HVAC Input-- Standby mode

If the first three are all "0", Standby mode is activated.

  • 1byte: Mode changes based on received values:

  • 1: Comfort mode

  • 2: Standby mode

  • 3: Economy mode

  • 4: Frost/Heat protection mode

- Controller status after restart

Sets controlled room mode after device startup.

Options:

  • Standby mode

  • Comfort mode

  • Economy mode

  • Frost/heat protection mode

- Extended comfort mode [0..255, 0=inactive] min

Sets the delay time for automatically switching from Comfort to Economy mode.

Options: 0 ~ 255

  • Value = 0: No automatic switch

  • Value = 1-255: Delay in minutes before switching

NOTE:

This setting only applies to transitions Economy mode and Comfort mode.

  • Scene function

Enables scene function.

Options:

  • Disable: Scene function disabled.

  • Enable: Scene function enabled; Scene subpage visible; configure actions for triggered scenes.

  • Min./Max. set temperature [5..40]℃

Limits adjustable temperature range. The minimum value must be greater than the max one; otherwise, default used. Out-of-range values output as limit.

  • Timer function

Enables timer function.

Options:

  • Disable

  • Enable: Timer function visible for scheduled tasks.

  • Error code enable/disable

Enables error code function.

Options:

  • Disable

  • Enable: Generates three group objects: "Failure status", "Error code", Error text" for displaying error codes of different types.

5.3.2.1 "HVAC Fan"

This interface is visible when the “Control type of fan speed” parameter is set to"1byte", as shown in Figure 5.3.2.1.

Figure 5.3.2.1 "HVAC Fan_1byte" Interface

  • Object datatype of 1byte fan speed

Sets the data type of 1byte fan speed.

Options:

  • Percentage (DPT 5.001)

  • Fan stage (DPT 5.100)

Output value for Fan speed

  • Output value for Fan speed off/low/medium/high

These parameters define the output values for switching to Off, Low, Medium, and High fan speeds.

Available value ranges depend on the data type set above: 0...255 or 0...100.

Status feedback for Fan speed

  • Status value for Fan speed off/low/medium/high

Defines the status feedback values for each fan speed level. The device updates the displayed fan speed based on the received feedback.

Options: 0...255 or 0...100, depending on the object type.

  • Fan speed auto

Enables automatic fan speed control. When enabled, the corresponding object will be displayed.

5.3.2.2 “Temp. Setpoint”

Figure 5.3.2.2(1) "Temp. setpoint_Relative" Interface

Figure 5.3.2.2(2) "Temp. setpoint_Absolute" Interface

The interface is visible when the HVAC operation mode is enabled, displayed based on the control mode.

  • Setpoint method for operating mode

Sets the actual adjusting method for panel temperature setpoints.

Options:

  • Relative: The setpoints for Economy and Standby modes are calculated based on a defined base temperature.

  • Absolute: Each mode has an independent setpoint temperature.

The following parameters are visible when the temperature setpoint adjusting method is set to “Relative”.

  • Basic setpoint temperature [℃]

Sets the base temperature used to derive the Comfort mode setpoint.

Options:

  • 10

  • 10.5

...

  • 35

This value can be modified via the “Setpoint adjustment” object. Changes are saved even after a bus power-down.

  • Reduced heating in standby mode [0..10]℃

  • Increased cooling in standby mode [0..10]℃

Sets the temperature setpoint for Standby mode.

Options: 0 ~ 10 [℃]

  • Heating: Setpoint = Base value - this offset

  • Cooling: Setpoint = Base value + this offset

  • Reduced heating during economy mode [0..10]℃

  • Increased cooling during economy mode [0..10]℃

Sets the temperature setpoint for Economy mode.

Options: 0 ~10 [℃]

  • Heating: Setpoint = Base value - this offset

  • Cooling: Setpoint = Base value + this offset

  • Actual Temp. threshold in frost protection[5..10]℃ ” (for heating)

Set the temperature setpoint for Frost protection mode in heating.

Options: 5 ~ 10 [℃]

In Frost protection mode, when the room temperature drops below this value, a control telegram is sent to trigger heating and prevent freezing.

  • Actual Temp. threshold in heat protection[30..40]℃ ” (for cooling)

Sets the temperature threshold for activating overheat protection in cooling.

Options: 30 ~ 40 [℃]

In overheat protection mode, when the room temperature exceeds this value, a control telegram is sent to activate cooling and prevent overheating.

The following parameters are visible when the temperature setpoint adjusting method is set to “Absolute”.

  • Setpoint Temp. in comfort mode [5..40]℃

  • Setpoint Temp. in standby mode [5..40]℃

  • Setpoint Temp. in economy mode [5..40]℃

  • Setpoint Temp. in frost protection mode [5..40]℃(for heating)

  • Setpoint Temp. in heat protection mode [5..40]℃ (for cooling)

These parameters allow you to directly set the temperature for each mode.

Options: 5 ~ 40 ℃.

5.3.2.3 "Heat&Cool control"

"Switching on/off(use 2-point control)" parameter settings

"Switching PWM(use PI control)" parameter settings

"Continuous control(use PI control)" parameter settings

Figure 5.3.2.3 "Heat&Cool control" Interfaces

  • Type of Heat/Cool control

Defines the type of object used to switch between heating and cooling modes.

Options:

  • Switching on/off (use 2-point control)  

  • Switching PWM (use PI control)  

  • Continuous control (use PI control)

  • Invert control value

Determine the control value sent to the control object is normal or inverted, ensuring compatibility with different valve types.

Options:

  • No

  • Yes: After the control value is inverted, it is sent to the bus via the object.

The following two parameters apply to two-point control:

  • Lower Hysteresis [0..200]*0.1℃

  • Upper Hysteresis [0..200]*0.1℃

Set temperature hysteresis for HVAC heating or cooling.

Options: 0 ~ 200

  • In the heating process

  • Heating stops when the actual temperature (T) > the setpoint temperature + the upper hysteresis value.

  • Heating starts when the actual temperature (T) < the setpoint temperature - the lower hysteresis value.

Example:

With a lower hysteresis of 1°C and an upper hysteresis of 2°C, and a setpoint temperature of 22°C:

  • Heating stops if T > 24°C.

  • Heating starts if T < 21°C.

  • Heating maintains its current state if T is between 21°C and 24°C.

  • In the cooling process

  • Cooling stops when the actual temperature (T) < the setpoint temperature - the lower hysteresis value.

  • Cooling starts when the actual temperature (T) > the setpoint temperature + the upper hysteresis value.

Example:

With a lower hysteresis of 1°C and an upper hysteresis of 2°C, and a setpoint temperature of 26°C:

  • Cooling stops if T < 25°C.

  • Cooling starts if T > 28°C.

  • Cooling maintains its current state if T is between 25°C and 28°C.

NOTE:

Two-point control is a simple method requiring both upper and lower hysteresis values to be set. Consider the following impacts when setting hysteresis temperatures:

  1. A smaller hysteresis range results in less temperature variation but increases bus load due to frequent control value transmissions.

  2. Conversely, a wider hysteresis range reduces switching frequency, but may cause uncomfortable temperature fluctuations.

The following two parameters apply to PI control.

  • Heating speed

  • Cooling speed

Sets the response speed of the heating or cooling PI controller. Different response speeds match various environments.

Options:

  • Hot water heating (5K/150min)

  • Underfloor heating (5K/240 min)

  • Electrical heating (4K/100min)

  • Split unit/ Fan coil unit (4K/90min)

  • User defined

Options:

  • Cooling ceiling (5K/240min)

  • Split unit (4K/90min)

  • Fan coil unit(4K/90min)

  • User defined

When the “User defined” is selected in “Heating/Cooling speed”, the following parameters are visible.

  • Proportional range[10..100]*0.1℃ (P value)

  • Reset time[0..255]min(I value)

The following parameters are visible when the control type is set to “Switching PWM (use PI control)”.

  • PWM cycle time [1..255] min

This parameter defines the cycle time for the control object to periodically transmit switching control values. The object sends on/off telegrams depending on the duty cycle of the control value.

For instance, with a set cycle time of 10 minutes and a control value of 80%, the object will send an "on" telegram for 8 minutes and an "off" telegram for 2 minutes in each cycle. This cycle persists continuously. If the control value is changed, the duty ratio of the object's on/off telegram will adjust accordingly, while the period remains constant at the time set by the parameter.

Options: 1 ~ 255

NOTE:

The PI control values of “Switching PWM (use PI control)” and “Continuous control (use PI control)” are the same. The difference lies in their control object:

The following parameters are visible when the control type is set to “Continuous control (use PI control)”.

  • Send control value on change by [0..100%, 0=inactive]

Specifies the threshold at which a change in the control value prompts its transmission to the bus.

Options: 0 ~ 100. 0=inactive.

  • Cyclically send control value [0..255]min

Set the time period for cyclically sending the control value to the bus.

Options: 0 ~ 255

In the PI control mode, the recommended predefined control parameters for each PI controller in the heating or cooling system are as follows:

1-Heating system

Heating Type

P Value

I Value (Integration time)

Recommended PI Control Type

Recommended PWM Cycle Period

Hot water Heating

5K

150min

Continuous/PWM

15min

Underfloor heating

5K

240min

PWM

15-20min

Electrical heating

4K

100min

PWM

10-15min

Split unit

4K

90min

PWM

10-15min

Fan coil unit

4K

90min

Continuous

/

2-Cooling system

Heating Type

P Value

I Value (Integration time)

Recommended PI Control Type

Recommended PWM Cycle Period

Cooling ceiling

5K

240min

PWM

15-20min

Split unit

4K

90min

PWM

10-15min

Fan coil unit

4K

90min

Continuous

/

3-User defined

When the parameter “Heating/Cooling speed” is set to “User defined”, the values of P (proportionality) and I (integration time) can be set through parameter settings. When adjusting the parameters, refer to the fixed PI value mentioned in the above table. Even slight modifications to these control parameters can result in significantly different control behaviors.

Moreover, it's crucial to set the integration time appropriately. A large integration time value will lead to slow adjustments and subtle oscillations. Conversely, a small integration time value can cause rapid adjustments but may result in oscillations. A value of 0 for the integral time indicates that the integral term is not used.

Settings and effects of User-defined parameters:

Parameter setting

Effect

K: the proportion range is too small

Rapid adjustment; overshoot will occur

K: the proportion range is too large

Slow adjustment, without overshoot

TN: the integration time is too short

Rapid adjustment; oscillation will occur

TN: the integration time is too long

Slow adjustment, with subtle oscillation

5.3.2.4 "Scene"

Figure 5.3.2.4 "Scene" Interface

When the Scene function is enabled, this interface is visible and allows to configure 5 scenes with the following parameters:

  • X->Assign scene NO.[0..64,0=inactive]

Sets the associated scene. When triggered, the configured operation is executed.  

Options: 0~64 (0 = Not linked to a scene.)

The following parameters are visible when Assign scene NO. is set to non-zero.

- Power on/off status

Sets the HVAC power status when the associated scene is triggered.

Options:

  • Unchange

  • Off

  • On

- Operation mode

Sets the HVAC operation mode when the associated scene is triggered.

Options:

  • Unchange            

  • Comfort mode        

  • Standby mode        

  • Economy mode        

  • Frost/heat protection  

5.3.3 "Function x--Air conditioner"

Parameter setting Interface “Function x-- Air conditioner”, as shown in Figure 5.3.3, configures basic control parameters for air conditioners. It applies to two types of air conditioning controls: IR split units and gateway Integrate.

Figure 5.3.3 "Function x-- Air conditioner General Parameters" Interface

  • Description

Sets the device name. A maximum of 31 characters can be entered, while the display supports up to 10 Chinese characters.

  • Temperature display from

Sets the source of ambient temperature displayed on the AC interface.

Options:

  • Internal sensor

  • External sensor

NOTE:

The AC temperature settings are similar to those for HVAC, except they do not support combined sensors. See Section 5.3.2 for more details.

  • Time period for request external sensor [0..255]min

Sets the time period for the device to send read requests to the external temperature sensor.

Options: 0 ... 255

  • Read external sensor after restart

Specifies whether the device reads external sensor data after a reset.

Options:

  • No: The read command waits until the next scheduled polling cycle.

  • Yes: A read command is sent immediately after restart or programming.

  • Control type

Sets the air conditioning control method.

Currently available: VRV/VRF Gateway.

  • Object datatype of setpoint

Specifies the data type used for temperature setpoints.

Options:

  • Value in ℃ (DPT_5.010)      

  • Float value in ℃ (DPT_9.001)

  • Min./Max. set temperature [16..32]℃

Specify the range of temperature setpoints. The minimum value must be set lower than the maximum value. If the set temperature exceeds the defined limits, it will be automatically adjusted to fit within the specified range.

NOTE:

If the minimum temperature exceeds the maximum, the range is set to 16~32℃ by default.  

Options:

  • 16℃

  • 17℃

  • ...

  • 32℃

For the setpoint temperature, the minimum value must always be lower than the maximum value. If not met, the parameter cannot be set in ETS.

  • Scene function

Enables or disables the scene function.

Options:

  • Disable

  • Enable: A subpage becomes available to configure triggered actions.

  • Vanes swing

Enables or disables the swing function. When enabled, the following parameters and objects will be visible.

- Object value for vanes swing

Sets the object value for the vanes swing object. The read-only value is Stop=0 / Swing=1.

- Vanes position

Sets to enable vanes position control. When enabled, the corresponding parameters and objects will be displayed.

  • Timer function

Enables/disables the timer function.

Options:

  • Disable.

  • Enable: Timer function enabled. The Timer feature becomes available on the K32 panel, allowing scheduled tasks to be configured.

  • Error code enable/disable

Enables or disables the error code function.

Options:

  • Disable

  • Enable: Generates three communication objects: Failure Status, Error Code, and Error Text.

5.3.3.1 "AC Mode"

Figure 5.3.3.1 "AC Mode General Parameters" Interface

  • Auto/Heating/Cooling/Fan/Dehumidification mode

When these parameters are enabled, the following parameters will be visible.

- Output value for Auto/Heating/Cooling/Fan/Dehumidification

Defines the value sent to switch to each mode.

Options: 0 ~ 255

- Status value for Auto/Heating/Cooling/Fan/Dehumidification

Set status feedback values for each mode. The device updates the mode icon status based on the received feedback value.

Options: 0 ~ 255

5.3.3.2 "AC Fan"

Figure 5.3.3.2 "AC Fan General Parameters" Interface

  • Object datatype of 1byte fan speed

Sets the data type of 1byte fan speed.

Options:

  • Percentage (DPT 5.001)

  • Fan stage (DPT 5.100)

Output value for Fan speed

  • Output value for Fan speed auto/low/medium/high

Defines the output values to switch to each fan speed level, supporting four fan speeds: Auto, Low, Medium, and High.

Depending on the object type of the previous parameter, the options are: 0..255/0..100.

Status feedback for Fan speed

  • Status value for Fan speed auto/low/medium/high

Set the status feedback values for each fan speed. The device will update the displayed fan speed based on the feedback values.

Options: 0..255/0..100.

5.3.3.3 "Scene"

Figure 5.3.3.3 "Scene General Parameters" Interface

When the Scene function is enabled, this interface is visible and allows to configure 5 scenes with the following parameters:

  • X->Assign scene NO.[0..64,0=inactive]

Sets the associated scene. When triggered, the configured operation is executed.  

Options: 0~64 (0 : Not linked to a scene.)

The following parameters are visible, when Assign scene NO. is set to non-zero.

- Power on/off status

Sets the AC power status when the associated scene is triggered.

Options:

  • Unchange

  • Off

  • On

- Set Temperature[16..32]

Sets the AC preset temperature when the associated scene is triggered.

Options:

  • Unchange            

  • 16℃

  • 17℃

  • ...

  • 32℃

- Set mode

Sets the AC operation mode when the associated scene is triggered.

Options:

  • Unchange            

  • Auto mode            

  • Heating mode          

  • Cooling mode          

  • Fan mode            

  • Dehumidification mode  

- Set Fan

Sets the AC fan speed when the associated scene is triggered.

Options:

  • Unchange            

  • Auto

  • Low

  • Medium

  • High

5.3.3.4 "Vanes position"

Figure 5.3.3.4 "Vanes position General Parameters" Interface

When vanes position function is enabled, this interface is visible, offering five selectable vanes positions.

Output value for Vanes position

The following parameters configure the output values sent by the objects “Vanes position 1..5, status” when switching to each vanes position.

  • “Command value for position 1/2/3/4/5”

Defines the control values corresponding to the five vanes positions.

Options: 0~255

Status feedback for Vanes position

The following parameters configure the status feedback values for each vanes position.

  • “Status value for position 1/2/3/4/5”

Sets the status feedback values for each vanes position. The device updates the vanes position icon status based on the received feedback value.

Options: 0~255

5.3.4 "Function x--Floor heating"

The parameter setting interface "Function x--Floor heating", as shown in Figure 5.3.4, configures the floor heating actuator control settings.

Figure 5.3.4 "Function x--Floor heating" Interface

  • Description

Sets the device name, which can display up to 31 English characters or 10 Chinese characters.

  • Temperature reference from

Sets the source of temperature reference for the floor heating function.

Options:

  • Internal sensor

  • External sensor

  • Internal and External sensor combination

NOTE:

Temperature settings of floor heating are similar to that of HVAC function. For more details, please refer to Section 5.3.2.

  • Power on/off status after download

Defines the power on/off status of the floor heating interface after downloading application.

Options:

  • Off

  • On

  • Power on/off status after voltage recovery

Sets the power status of the floor heating interface after bus voltage recovery.

Options:

  • On: The device powers on in an active state. The interface is operable, and the system determines whether to heat based on the control method.

  • Off: The device powers on in an inactive state. Only the timer and power icons are operable; all other icons on the interface are disabled.

  • As before voltage failure: The device restores its previous power state before the outage. If it was on, the system performs internal calculations based on the control method to determine heating output.

  • Default set temperature[32..64]*0.5℃

Sets the initial temperature when floor heating is activated.

Options: 32.. 64

  • Min./Max. set temperature[16..32]℃

Specifies the range of set temperature. The minimum value must be set lower than the maximum value. If the set temperature exceeds the defined limits, it will be automatically adjusted to fit within the specified range.

Options: 16.. 32

  • Temperature control method

Sets the temperature control method. Different control types are for controlling different temperature controllers.

Options:

  • Heating on/off (use 2-point control)

  • Heating PWM (use PI control) PWM

  • Heating continuous control (use PI control)

When the parameter “Temperature control method” is set to “Heating on/off (use 2-point control)”, the following parameters are visible:

In two-point control, heating is turned off when the temperature exceeds one certain set temperature; It is on when it falls below another set temperature.

- Object value of Heating on/off

Defines the trigger values for heating on/off.

Options:

  • Heat on=1, Heat off=0

  • Heat on=0, Heat off=1

- Lower Hysteresis [0.. 200]*0.1℃

- Upper Hysteresis [0.. 200]*0.1℃

Sets the lower/upper hysteresis values for the set temperature of floor heating.

Options: 0..200

NOTE:

  • Heating stops when the actual temperature (T) > the setpoint temperature + the upper hysteresis value.

  • Heating starts when the actual temperature (T) < the setpoint temperature - the lower hysteresis value.

Example:

With a lower hysteresis of 1°C and an upper hysteresis of 2°C, and a setpoint temperature of 16°C:

  • Heating stops if T > 18°C.

  • Heating starts if T < 15°C.

  • Heating maintains its current state if T is between 15°C and 18°C.

When the parameter “Temperature control method” is set to “Heating PWM (use PI control)” or “Heating continuous control(use PI control)”, the following parameters are visible.

In the PWM switch control, floor heating cyclically switches the valve based on the control value.

In the Continuous control, floor heating regulates the opening and closing of the valve based on the control value.

- Invert control value

Sets whether the control value is sent normally or inverted before being sent to the bus to accommodate the valve type.

Options:

  • No

  • Yes

The control value is inverted before being sent to the bus.

- PWM cycle time [1.. 255] min

This parameter is exclusively accessible when the "Temperature Control Method" is configured as "Heating PWM (use PI control)". It defines the cycle time for the control object to periodically transmit switching control values. The object sends on/off telegrams depending on the duty cycle of the control value.

For instance, with a set cycle time of 10 minutes and a control value of 80%, the object will send an "on" telegram for 8 minutes and an "off" telegram for 2 minutes in each cycle. This cycle persists continuously. If the control value is changed, the duty ratio of the object's on/off telegram will adjust accordingly, while the cycle time remains constant.

Options: 1.. 255

- Heating speed

Specifies the response speed of the heating PI controller. Different response speeds are applicable for different environments.

Options:

  • Hot water heating (5K/150min)

  • Underfloor heating (5K/240 min)

  • Electrical heating (4K/100min)

  • User defined: Once selected, the following two parameters are visible.

- Proportional range[10.. 100]*0.1℃ (P value)

- Reset time[0.. 255]min (I value)

They set the control values of PI controller. For more details about 2-point and PI control methods, please refer to Section 5.3.3.

  • Cyclically send control value [0..255]min

Defines the interval for cyclically sending control values to the bus.

Options: 0.. 255

  • Scene function

Enables or disables the scene functions of the floor heating.

Options:

  • Disable

  • Enable: The Scene function subpage is visible to configure the triggered actions.

  • Timer function

Enables/disables the timer function.

Options:

  • Disable

  • Enable: Timer function enabled. The Timer feature becomes available on the K32 panel, allowing scheduled tasks to be configured.

  • Error code enable/dis

Enables or disables the error code function.

Options:

  • Disable

  • Enable: Three group objects “Failure status”, “Error code” and “Error text” will be generated for displaying different data types of error codes.

  • x->Assign scene NO. [1..64,0=inactive], x=1~5

Sets the scene number.

Options: 0.. 64,0=inactive

  • Power on/off status

Sets the power on/off status of scene x for the floor heating interface.

Options:

  • Off

  • On

5.3.4.1 "Scene"

Figure 5.3.4.1 "Scene" Interface

This page is visible when the Scene function is enabled. Up to 5 scenes can be configured. The parameters are described below:

  • X->Assign scene NO.[0..64,0=inactive]

Specifies the scene number associated with this function. When the assigned scene is triggered, the configured actions will be executed.

Options: 0~64 (0 = no scene is associated)

The following parameters are visible, when Assign scene NO. is set to non-zero.

- Power on/off status

Defines the power status of Floor Heating when the associated scene is triggered.

Options:

  • Unchange  

  • Off        

  • On        

- Set temperature[16..32]

Sets the preset temperature of Floor Heating when the associated scene is triggered.

Options:

  • Unchange            

  • 32*0.5℃

  • 33*0.5℃

  • ...

  • 64*0.5℃

5.3.5 "Function x-- Ventilation System"

The parameter setting interface “Function x - Ventilation System”, as shown in Figure 5.3.5, sets the parameters for the ventilation system controlling.

Figure 5.3.5 "Functionx-- Ventilation System" Interface

  • Description

Sets the device name. Up to 31 characters can be entered, while the display supports a maximum of 10 Chinese characters.

  • Power on/off status after download

Sets the power on/off status of the ventilation interface after the application is downloaded.

Options:

  • Off

  • On

  • Power on/off status after voltage recovery

Sets the power on/off status of the ventilation interface after the power is restored.

Options:

  • On: When power is restored, the device will be in the On state, and the interface will be operational.

  • Off: When power is restored, the device will be in the Off state. Other icons in the interface are not operational except for filter reset and on/off icons.

  • As before voltage failure: Upon power restoration, the device returns to its status prior to power off.

  • Default fan speed after power on

Sets the initial fan speed when the ventilation is turned on.

Options:

  • Off

  • Low

  • Medium

  • High

  • Heat Recovery function

Enables or disables the heat recovery function.

Options:

  • Disable

  • Disable=0/Enable=1

  • Disable=1/Enable=0

TIP:

If the last two options are selected, the heat recovery function defaults to enable upon system power-on. If not enabled, the heat recovery function is uncontrollable.

  • Filter timer counter

Defines whether enable the filter timer function.

When enabled, the following parameter is visible.

- Evaluation time[100..10000]h

Sets the service life of the filter.

Options: 100..10000

When the filter usage time exceeds the set value, a filter cleaning alert will be sent to the bus.

The usage time can be reset via the “Filter Timer Reset” object.

The usage duration is tracked via the “Filter Timer Counter” object, measured in hours. When the value changes, it is sent to the bus. The counter value can also be modified via the bus.

  • Auto. operation function

Defines whether enable the automatic fan speed operation interface.

When enabled, the fan speed is automatically adjusted based on air quality values such as PM2.5 or CO2, with sensor data retrieved from the bus.

A telegram value of 1 activates automatic fan speed control, while 0 deactivates it.

  • Scene function

Enables or disables the scene function.

Options:

  • Disable

  • Enable: The Scene function subpage becomes visible, where operations executed by triggering linked scenes can be configured.

  • Timer function

Enables the timing function.

Options:

  • Disable

  • Enable: The timer function is enabled. The Timer feature becomes available on the K32 panel, allowing scheduled tasks to be configured.

  • Error code enable/dis

Enables or disables the error code function.

Options:

  • Disable

  • Enable: Three group objects “Failure status”, “Error code” and “Error text” will be generated for displaying different data types of error codes.

5.3.5.1 "Fan"

Figure 5.3.5.1 "Fan General Parameters" Interface

  • Data type of fan speed

Sets the data type of the fan speed.

Options:

  • 1bit

  • 1byte

The following parameters are visible when the “Data type of fan speed” is “1bit”.

- Object value for Fan speed off/low/medium/high

Defines the values sent to switch to each fan speed, simultaneously transmitted by three 1-bit objects.

Options:

  • No.1=0, No.2=0, No.3=0

  • No.1=1, No.2=0, No.3=0

  • No.1=0, No.2=1, No.3=0

  • No.1=1, No.2=1, No.3=0

  • No.1=0, No.2=0, No.3=1

  • No.1=1, No.2=0, No.3=1

  • No.1=0, No.2=1, No.3=1

  • No.1=1, No.2=1, No.3=1

The following parameters are visible when the “Data type of fan speed” is “1byte”.

- Object datatype of 1byte fan speed

Defines the object datatype of 1byte fan speed

Options:

  • Percentage (DPT 5.001)

  • Fan stage (DPT 5.100)

Output value for Fan speed

- Output value for Fan speed off/low/medium/high

Defines the values sent to switch to each fan speed, supporting four types: off, low, medium, high.

Options: 0..255/0..100

Status feedback for Fan speed

- Status value for Fan speed off/low/medium/high

Sets the status feedback values for each fan speed. The device updates the fan speed status based on the received feedback values.

Options: 0..255/0..100

  • Delay between fan speed switch [0..100]*50ms

Sets a delay in changing fan speeds, considering the technical specifications of the fan.

Options: 0..100

When switching fan speeds, the fan speed should first be turned off. Then, after a delay, the fan speed can be turned on before the telegram is sent to the bus. If the delay time is set to 0, the fan will switch directly to the next speed without turning off first.

5.3.5.2 “Auto. Control”

When the auto operation is activated, the ventilation system will automatically adjust the fan speed based on the control values. The parameters visible are available when the ventilation system's automatic operation is enabled. The parameter setting interface is displayed as below.

Figure 5.3.5.2-1 "Auto. Control_PM 2.5” Interface

Figure 5.3.5.2-2 "Auto. "Control_CO2" Interface

Figure 5.3.5.2-3 "Auto. "Control_PM10" Interface

Figure 5.3.5.2-4 "Auto. Control_AQI” Interface

Figure 5.3.5.2-5 "Auto. "Control_VOC" Interface

Figure 5.3.5.2-6 "Auto. "Control_Others" Interface

  • Auto operation function on object value

Sets the telegram value for activating automatic operation.

Options:

  • 0=Auto/1=Cancel: Activates automatic operation when the object “Automatic function, In/Out” receives a telegram value of 0 and cancels automatic operation when it receives 1.

  • 1=Auto/0=Cancel: Activates automatic operation when the object “Automatic function, In/Out” receives a telegram value of 1 and cancels automatic operation when it receives 0.

NOTE:

After power-on, automatic operation is not activated by default.

  • Control value reference from

Sets the source of the control value.

Options:

  • PM2.5

  • CO2

  • PM10

  • AQI

  • VOC

  • Others

  • Period for request control value [0..255] Min

Sets the time period for the device to send control value read requests to external sensors.

Options: 0.. 255

  • The speed status when the control value error

Sets the default fan speed when a control value error occurs.

Options:

  • Off

  • Low

  • Medium

  • High

NOTE:

If attempts to read control values from external sensors yield no response, it will be considered a sensor malfunction and a control value error.

  • Object datatype of PM2.5

Selects the type for PM2.5, which determines the object type and should be chosen according to the type of PM2.5 sensor in use.

Options:

  • Value in ug/m3(DPT_7.001)

  • Float value in ug/m3(DPT_9.030)

  • DPT_7.001: Applicable for integer values

  • DPT_9.030: Applicable for floating-point values

  • Object datatype of CO2

Sets the data type for CO2, which determines the object type and should be chosen according to the type of CO2 sensor in use.

Options:

  • Value in ppm(DPT_7.001)

  • Float value in ppm(DPT_9.008)

  • DPT_7.001: Applicable for integer values

  • DPT_9.008: Applicable for floating-point values

  • Object datatype of PM10

Sets the data type for PM10, which determines the object type and should be chosen according to the type of PM10 sensor in use.

Options:

  • Value in ug/m3(DPT_7.001)

  • Float value in ug/m3(DPT_9.030)

  • DPT_7.001: Applicable for integer values

  • DPT_9.030: Applicable for floating-point values

  • Object datatype of VOC

Sets the data type for VOC, which determines the object type and should be chosen according to the type of VOC sensor in use.

Options:

  • Value in ug/m3(DPT_7.001)

  • Float value in ug/m3(DPT_9.030)

  • DPT_7.001: Applicable for integer values

  • DPT_9.030: Applicable for floating-point values

  • Threshold value OFF<-->speed Low[1..999]/[1..4000] /[1..65535]

Defines the threshold value for turning off the fan and running at low speed.

Options: 1…/1...4000/1...65535

NOTE:

If the control value is greater than or equal to the threshold value, the fan will run at low speed. If the control value is less than this threshold value, the fan will be turned off.

  • Threshold value speed low<-->medium[1..999]/[1…4000]  /[1..65535]

Defines the threshold value for switching to the medium-level fan speed. If the control value is greater than or equal to the threshold value, the fan will run at medium speed.          

Options: 1…999/1...4000/1...65535

  • Threshold value speed medium<-->high[1..999]/[1…4000] /[1..65535]

Define the threshold value for switching to the high-level fan speed.

If the control value is greater than or equal to this threshold value, the fan runs at high speed.

Options: 1…999/1...4000/1...65535

NOTE:

The controller evaluates thresholds in ascending order. The correct execution of the function is guaranteed only under this condition:

  • First check → OFF -> Low fan speed threshold → Low fan speed -> Medium fan speed threshold → Medium fan speed -> High fan speed threshold.

  • Hysteresis value is threshold value in +/- [10..30]/[100..400] /[1..65535]

Specifies the hysteresis value for the threshold, which helps prevent unnecessary fan actions when the control value fluctuates near the threshold.

Options: 10..30/100..400/1...65535

Example:

With a control value of PM2.5, a hysteresis value of 10, and a threshold value of 35, the upper threshold limit would be 45(threshold value+hysteresis value), and the lower threshold limit would be 25(threshold value-hysteresis value).

When the control value falls between 25 and 45, the fan's operation state remains unchanged. Changes occur only when the control value is below 25, or equals 45 or higher. As shown in the following figure:

NOTE:

When hysteresis is enabled and there is overlapping of thresholds, the fan's action is as follows:

  1. Hysteresis determines the control point for fan speed transition.

  2. New fan speed is determined by control value and threshold without considering hysteresis.

For example, with PM2.5:

  • OFF <-> Low fan speed threshold is 20.

  • Low <-> Medium fan speed threshold is 40.

  • Medium <->High fan speed threshold is 70.

  • Hysteresis is set to 10.

  1. When the fan speed increases from OFF

  • The OFF status changes when the control value reaches 30 (≥20+10).

  • If the received control value is 41, the fan speed goes to Medium (41 falls between 40 and 70, and hysteresis is not considered). In this case, the Low speed is bypassed.

  • If the received control value is 39, the fan speed will be Low (39 falls between 20 and 40, and hysteresis is not considered).

  1. When the fan speed decreases from the high-level:

  • The high-speed status changes when the control value is at 60 (<70-10).

  • If the received control value is 39, the fan speed becomes Low (39 falls between 20 and 40, and the hysteresis is not considered at this point). In this case, the Medium speed is bypassed.

  1. When the control value is 0, the fan must be OFF status.

  • Minimum time in fan speed [0…65535]s

Specifies the minimum time interval for the fan to maintain its current speed before speed changes, ensuring a minimum operating time for each fan speed. The fan must wait for this duration before changing its speed. If it runs at the current speed for longer than the set minimum time, it can quickly switch to another speed.

Options: 0..65535 (0: No minimum running time, but the delay in switching fan speed should be considered.)

NOTE:

This minimum time setting only applies to Auto mode.

5.3.5.3 "Scene"

Figure 5.3.5.3 "Scene General Parameters" Interface

When the Scene function is enabled, this interface is visible and allows to configure 5 scenes with the following parameters:

  • X->Assign scene NO.[0..64,0=inactive]

Sets the associated scene. When triggered, the configured operation is executed.  

Options: 0~64 (0 means not linked to a scene.)

The following parameters are visible, when Assign scene NO. is set to “non-zero”.

- Fan level

Sets the fan level of ventilation system when the associated scene is triggered.

Options:

  • Unchange  

  • Off        

  • Low        

  • Medium    

  • High        

- Heat recovery

Sets the heat recovery of ventilation system when the associated scene is triggered.

Options:

  • Unchange            

  • Off                  

  • On