6.1 Communication objects of “General Setting”

Prev Next

Figure 6.1 General Setting Communication Object

No.

Object Function

Communication Object Name

Data Type

Flags

DPT

76

Date

General

3bytes

C,W,TU

11.001 date

This communication object is used to modify the device’s date via the bus.

77

Time

General

3bytes

C,W,T,U

10.001 time of day

This communication object is used to modify the device’s time via the bus.

73

In Operation

General

bit

C,T

10.001 time of day

This communication object is used to periodically send the value “1” to the bus to indicate that the device is operating normally.

78

Temperature

Internal sensor

2bytes

C,W,T,U

9.001 temperature (℃)

This communication object is visible when the “Display D&H resource parameter” is set to “Internal sensor”, and is used to send the temperature from the internal sensor to the bus.

74

Proximity,1 bit value

Proximity,scene NO.

Proximity,1 byte value

Internal sensor

1bit

1byte

C,T

1.001 switch

17.001 scene number

5.010 counter pulses(0..255)

5.001 percentage(0..100%)

This communication object is visible when the “Proximity sensor resource” is set to “Internal sensor”.

When a person is detected approaching or leaving the sensing area, the object sends telegrams to the bus accordingly. The value range is determined by the selected data type.

74

Proximity

External sensor

1bit

C,W,T,U

1.001 switch

This communication object is visible when the “Proximity sensor resource” is set to “External sensor”, and is used to transmit the trigger status of the human presence detector on the bus to the K32 panel.

Table 6.1 General Setting Communication Object