Fig.6.1 “General" Communication Object
NO. | Object Function | Name | Data Type | Flag | DPT |
1 | In operation | General | 1bit | C,R,T | 1.001 switch |
The communication object is used to periodically send a telegram "1" to the bus to indicate that the device is working properly. | |||||
2 | Central: Switching | General | 1bit | C,W | 1.001 switch |
The communication object is used to receive a command of switching on/off lamps for central control, it only applies to the channel that the central control is enabled. | |||||
3 | Central: Relative dimming | General | 4bit | C,W | 3.007 dimming |
The communication object is used to receive a command of relative dimming for central control, to dim up or dim down. It only applies to the channel that the central control is enabled. | |||||
4 | Central: Absolute dimming | General | 1byte | C,W | 5.001 percentage |
The communication object is used to receive a command of absolute dimming for central control, it only applies to the channel that the central control is enabled. | |||||
5 | Central: Safety | General | 1bit | C,W | 1.005 alarm |
The communication object is used to receive the 1bit telegram that is sent from other device (such as sensor, controller, etc.), the cancel telegram value is decided by the parameter. If no corresponding telegram is received within the monitoring time, it is assumed that other devices are failure, and the channel with a safety function activates the safety operation. With a monitoring time of 0, it is also possible to activate and exit the safety operation by receiving the corresponding value with this object. In the case that the safety operation is not active, the cancel telegram is meaningless and it will be ignored. | |||||
Table 6.1 "General" Communication Object Table