6.2 "Output setting" Communication Object

Prev Next

Fig.6.2 "Output setting" Communication Object

NO.

Object Function

Name

Data Type

Flag

DPT

78

Switching

Channel A-{{...}}

1bit

C,W

1.001 switch

The communication object is used to receive a command of switching on/off lamps. Telegrams:

  • 1——Switch on

  • 0——Switch off

The name in parentheses changes with the parameter "Description (max 30char.)". If description is empty, display "Channel A - ..." by default. The same below.

79

Relative dimming

Channel A-{{...}}

4bit

C,W

3.007 dimming

The communication object is used to receive a command of relative dimming, to dim up or dim down.

Dimming down when telegram is 1~7, and the larger this range the adjust step is smaller. That is, the maximum step of dimming down when is 1, and the minimum step of dimming down when is 7, stop dimming when is 0;

Dimming up when telegram is 9~15, and the larger this range the adjust step is smaller. That is, the maximum step of dimming up when is 9, and the minimum step of dimming up when is 15, stop dimming when is 8.

80

Absolute dimming

Channel A-{{...}}

1byte

C,W

5.001 percentage

The communication object is used to receive a command of absolute dimming.

Telegrams:

  • 0...100%

81

Switching, status

Channel A-{{...}}

1bit

C,R,T

1.001 switch

The communication object is used to report the status of the current switch to the bus. Send "1" to the bus when the value of the brightness is larger than 0, send "0" to the bus with value of "0". Send the status when voltage recovery.

82

Brightness value, status

Channel A-{{...}}

1byte

C,R,T

5.001 percentage

The communication object is used to report the status of the current brightness value to the bus. Send the status at power-up when voltage recovery.

83

Short-circuit, status

Channel A-{{...}}

1bit

C,R,T

1.005 alarm

The communication object is used to report the status of short circuit to the bus. Send the status at power-up when voltage recovery.

Telegrams:

  • 1——Short circuit

  • 0——Normal

84

Over-voltage, status

Channel A-{{...}}

1bit

C,R,T

1.005 alarm

The communication object is used to report the status of over-voltage to the bus. Send the status when voltage recovery.

Telegrams:

  • 1——Over voltage

  • 0——Normal

85

Over-temperature, status

Channel A-{{...}}

1bit

C,R,T

1.005 alarm

The communication object is used to report the status of over-temperature to the bus. Send the status when voltage recovery.

Telegrams:

  • 1——Over temperature

  • 0——Normal

87

Operation voltage failure

Channel A-{{...}}

1bit

C,R,T

1.005 alarm

The communication object is used to report the status of operation voltage failure to the bus. Operation voltage is failure when no valid over-zero signal is detected. Send the status when voltage recovery.

Telegrams:

  • 1——Operation voltage failure

  • 0——Normal

88

Scene

Channel A-{{...}}

1byte

C,W

18.001 scene control

The communication object is used to receive a 8 bit command to recall or storage scene. Detailed 8bit the meaning of the directive.

Set up a 8bit Orders for the (Binary code): FXNNNNNN

                           F: '0' recall scene; '1' for storage scene;

                           X : 0 ;

                           NNNNNN: Scene number( 0... 63).

As follows:

Object message value

Description

0

1

2

…

63

Recall scene 1

Recall scene 2

Recall scene 3

...

Recall scene 64

128

129

130

…

191

Store scene 1

Store scene 2

Store scene 3

...

Store scene 64

Parameter setting Options are 1~64, actually communication object "Scene" corresponds to the telegram received is 0~63. Such as parameter settings is the scene 1, communication object "Scene" sends the scene for 0.

89

Delay switch

Channel A-{{...}}

1bit

C,W

1.001 switch

The communication object is visible when "Delay Switch" is selected for time function, used to turn on the function of delay switch.

89

Flashing switch

Channel A-{{...}}

1bit

C,W

1.010 start/stop

The communication object is visible when "Flashing Switch" is selected for time function, used to turn on the function of flashing switch.

89

Staircase lighting

Channel A-{{...}}

1bit

C,W

1.010 start/stop

The communication object is visible when "Staircase lighting" is selected for time function, used to turn on the function of staircase lighting.

90

Duration of staircase lighting (5..65535s)

Channel A-{{...}}

2byte

C,W,R

7.005time(s)

The communication object is visible when "Staircase lighting" is selected for time function and duration time can be changed via bus. Used to modify the time, and save it after voltage failure. If the duration has not been modified, the value read from the object is the setting value of ETS parameter.

91

Staircase lighting Prewarning

Channel A-{{...}}

1bit

C,R,T

1.005 alarm

The communication object is visible when "Staircase lighting" is selected for time function and prewarn via bus. Used to send the telegram of prewarning before staircase lighting end.

Telegram:

  • 1——Warning

  • 0——End of warning

92

Threshold  input

Channel A-{{...}}

1byte

2byte

C,W

5.010 counter pulses(0..255)

5.001 percentage

9.001 temperature

9.004 brightness (lux)

The communication object is receive the input value of threshold function. Telegram value is determined by the datatype, and the datatype is determined by the parameter setting.

93

Threshold value 1

Channel A-{{...}}

1byte

2byte

C,W,R

5.010 counter pulses(0..255)

5.001 percentage

9.001 temperature

9.004 brightness (lux)

94

Threshold value 2

Channel A-{{...}}

1byte

2byte

C,W,R

5.010 counter pulses(0..255)

5.001 percentage

9.001 temperature

9.004 brightness (lux)

These two communication objects are visible when the threshold value 1/2 can be changed via bus. Used to modify the values, and save them after voltage failure. If the thresholds have not been modified, the value read from the object is the setting value of ETS parameter.

NOTE:

threshold value 1 must be less than threshold value 2, or ignore the telegram.

95

Forced operation

Channel A-{{...}}

1bit

2bit

C,W

1.003 enable

2.001 DPT_Switch control

The communication object is used to trigger a forced operation. Save the trigger status when voltage failure, and keep the status at voltage recovery.

When 1bit, activate the forced operation when receive telegram 1, at this time, ignore all the other actions; End the forced operation when receive telegram 0, and the behaviour in forced operation is defined by parameter.

When 2bit, force to switch off when receive telegram 3; force to switch on when receive telegram 2; End the forced operation when receive telegram 1 or 0.

The end telegram is invalid when the forced operation is not active, and ignore it directly.

103

Operating hours counter

Channel A-{{...}}

2byte

4byte

C,R,W,T

7.007 time (h)

13.100 time lag (s)

The communication object is used to send the accumulated operating time that the lamp has been switched on to the bus, begin to count when brightness is greater than “0”, and the accumulated time can also be modified via the bus, and send it after the device is restarted.

104

Reset operating hours counter

Channel A-{{...}}

1bit

C,W

1.015 reset

The communication object is used to reset the accumulated operating time to 0. Telegrams:

  • 1——Reset

  • 0——NA

105

Exceedance of operating hours

Channel A-{{...}}

1bit

C,R,T

1.005 alarm

The communication object is used to send the status to the bus when the accumulated operating time exceeds the threshold, remind user the exceedance. Send the status when voltage recovery.

Telegrams:

  • 1——Exceed

  • 0——Normal

Table 6.2 "Output setting" Communication Object Table