AND/OR/XOR

Prev Next

Figure: Logic - AND/OR/XOR interface

  • Input a/b/c/d/e/f/g//h

Configure whether logic input x is involved in the operation, and it is normal or inverted.

Options:

  • Disconnected: Not involved.

  • Normal: The input directly involved.

  • Inverted: The input is inverted before being involved.

Note

The initial value of the input is not inverted.

  • Default value

Set the initial value of the logic input x.

Options:

  • 0

  • 1

  • Result is inverted

Determine whether the logical operation result is inverted.

Options:

  • No: Output directly

  • Yes: Invert and then output

  • Read input object value after bus voltage recovery

Decide whether a read request is sent to the logic input object following bus power recovery or programming.

Options:

  • No

  • Yes

  • Output send when

Set the conditions for sending the logical operation result to the bus.

Options:

  • Receiving a new telegram: Result sent upon each reception of a new logical input value.

  • Every change of output object: Result sent only when it changes.

Note

When conducting the initial logical operation, the result will be sent even if it remains unchanged.

  • Send delay time

Set the delay time for sending the logical operation result to the bus, calculated as Delay time = Base x Factor. If the “Base” is set to "None", there is no delay.

Base:

  • None

  • 0.1s

  • 1s

  • 2s

  • 5s

  • 10s

  • 25s

Factor: 1 .. 255