Parameter setting interface of “Event group”

Prev Next

Figure 2.6.1 shows the parameter setting interface for the "Event Group function," facilitating the configuration of up to 8 event groups. Each group, as shown in Figure 2.6.2, has 8 outputs.

Figure2.6.1: Event Group function interface

Figure2.6.2: Groupx - Output y function interface

  • Event Group x Function (x:1.. 8)

Enable event group x function.

Options:

  • Disable

  • Enable: When a specific group is enabled, the configuration parameters for its 8 outputs become visible.

All eight groups share the same function, with identical configurations for each group's 8 outputs. Here we use one of the outputs as an example.

  • Object type of Output y (y:1.. 8)

Defines the data type of output y in group x.

Options:

  • 1bit

  • 1byte

  • 2byte

  • z->Trigger scene NO.[1.. 64,0=inactive] (z:1.. 8)

Specify the scene number that triggers output y in group x. Each output can configure up to 8 triggered scenes.

Options: 0 to 64, 0=inactive.

  • Object value of Output y [0 .. 1/0 .. 255/0 .. 65535]

Sets the output value. The value range is determined by the data type of output y:

  • 1bit: 0 .. 1

  • 1byte: 0 .. 255

  • 2byte: 0 .. 65535

  • Delay time for sending [0 ..255]*0.1s

Set a delay before sending the output value to the bus.

Options: 0 .. 255