NO. | Symptom | Possible Cause | Solution | Remark |
1 | Flickering or jitter at low brightness | Lamp driver unstable at low voltage | Increase the minimum brightness to avoid unstable range | |
Use a custom dimming curve; set 1% output to the lowest stable brightness | ||||
2 | No noticeable change at high brightness | LED reaches maximum luminous output | Reduce maximum brightness to avoid ineffective control | |
Use a custom curve; set 100% output to the LED’s maximum brightness control value | ||||
3 | Flicker or unstable output on startup | Driver requires higher startup voltage | Enable “Startup feature” and configure parameters to skip unstable range | |
4 | Minimum control value to turn on is higher than expected | Driver needs extra startup voltage to ignite | Enable “Startup feature” and adjust parameters for smoother dimming | |
5 | Flicker during dimming | Lamp may not support dimming | Verify lamp’s dimming specifications | Consider replacing lamp or driver if unresolved |
Lamp-driver mismatch | Verify compatibility | |||
Load type or curve mismatch | Adjust ETS parameters and verify | |||
Dimming speed too fast | Increase dimming time or adjust curve | |||
Flicker in mid-range only | Fine-tune custom curve slope | |||
Flicker at high brightness | Reduce maximum brightness | |||
Low-quality driver or unstable voltage | Add a parallel incandescent lamp or dummy load for testing | |||
6 | Dimming range does not cover 0–100% | Limited driver voltage or lamp performance | Use custom curve; set 1% to minimum visible brightness, 100% to max brightness | |
7 | Lamp too bright at low levels | Inappropriate dimming curve | Use curves with slower growth (quadratic, cubic, logarithmic) or custom curve | |
Minimum brightness too high | Lower the minimum brightness value | |||
8 | Lamp fails to switch on/off | Power interruption | Check and reconnect | Enable monitoring of abnormal status telegrams; diagnose based on alarm type |
Load overload triggering thermal protection | Reduce the load power | |||
Short circuit at output | Reconnect the wiring and test that there are no problems before power up again | |||
Excessive inrush current from driver | Reduce load | |||
Switch to trailing-edge (RC) dimming | ||||
Replace with higher-quality lamps or drivers | ||||
Temporary KNX bus power loss | Diagnose bus; ensure stable connection | |||
9 | LED can not turn off | Driver incompatible with dimmer | Add parallel incandescent lamp or dummy load to test | Replace lamp or driver if unresolved |
Add a relay in series to physically disconnect driver during off | ||||
Replace with high-quality dimmable lamps or drivers |