2. Technical Specifications

Prev Next

Power Supply

Bus voltage

21-30V DC,via the KNX bus

Bus current

<7.5mA/24V, <6.5mA/30V

Bus consumption

<195mW

Output

Dimming channel

4 (separate phase connection)

Max. load

300W per channel (incandescent/ Halogen/ LED, trailing edge)

Rated voltage

110~230 V AC (50/60HZ)

Standby loss

Approx. 0.7W

Load loss

≤2W per channel

Connection

KNX

Bus connection terminals, 0.8 mm Ø

Outputs

Screw terminals

Wire Range

0.2—6.0mm2

Environment

Storage

–25 °C ~ + 55 °C      

Working Temperature

–5 °C ~ + 45 °C

Working Humidity

0~93%RH (non-condensing)

Installation

35mm DIN rail

2.1 Supported Loads

2.1.1 Maximum Load Capacity per Channel

Load Type

Max. Load capacity (110V)

Max. Load capacity (230V)

Leading Edge

Trailing Edge

Leading Edge

Trailing Edge

Incandescent Lamp

10~150W

10~150W

10~300W

10~300W

High-Voltage Halogen Lamp

10~150W

10~150W

10~300W

10~300W

Low-Voltage Halogen Lamp with Electronic Transformer

10~150W

10~150W

10~300W

10~300W

High-Voltage LED

2~30W

2~150W

2~60W

2~300W

Low-Voltage LED with Electronic Transformer

2~40W

2~150W

2~80W

2~300W

Low-Voltage LED with Constant Current Driver (Down light, Spotlight)

2~40W

2~150W

2~80W

2~300W

Low-Voltage LED with Constant Voltage Driver

2~40W

2~150W

2~80W

2~300W

Resistive Load

Capacitive Load

图片2

Inductive Load

LED Load

图片2

2.1.2 Parallel Output Load Capacity

The 4-gang dimmer supports independent or parallel outputs. Parallel output increases load capacity.

Load Type

Max. Load Capacity (110V)

Parallel with 2 Channels

Parallel with 3 Channels

Parallel with 4 Channels

Leading Edge

Trailing Edge

Leading Edge

Trailing Edge

Leading Edge

Trailing Edge

Incandescent Lamp

300W

300W

400W

400W

500W

500W

High-Voltage Halogen Lamp

300W

300W

400W

400W

500W

500W

Low-Voltage Halogen Lamp with Electronic Transformer

300W

300W

400W

400W

500W

500W

High-Voltage LED

-

300W

-

400W

-

500W

Low-Voltage LED with Electronic Transformer

-

300W

-

400W

-

500W

Low-Voltage LED with Constant Current Driver

(Down light Spotlight)

-

300W

-

400W

-

500W

Low-Voltage LED with Constant Voltage Driver

-

300W

-

400W

-

500W

Load Type

Max. Load Capacity (230V)

Parallel with 2 Channels

Parallel with 3 Channels

Parallel with 4 Channels

Leading Edge

Trailing Edge

Leading Edge

Trailing Edge

Leading Edge

Trailing Edge

Incandescent Lamp

500W

500W

750W

750W

1000W

1000W

High-Voltage Halogen Lamp

500W

500W

750W

750W

1000W

1000W

Low-Voltage Halogen Lamp with Electronic Transformer

500W

500W

750W

750W

1000W

100W

High-Voltage LED

-

500W

-

750W

-

1000W

Low-Voltage LED with Electronic Transformer

-

500W

-

750W

-

1000W

Low-Voltage LED with Constant Current Driver

(Down light,Spotlight)

-

500W

-

750W

-

1000W

Low-Voltage LED with Constant Voltage Driver

-

500W

-

750W

-

1000W

NOTE:

For the same output channel, capacitive and inductive loads must not be connected together. Mixing capacitive + resistive or inductive + resistive loads is allowed, but power derating must be considered. It is strongly recommended to connect the same load type to each output channel.

The maximum load capacity mainly depends on the lamp’s inrush current and power loss. In leading-edge mode, these loads—especially LED lamps—can generate high inrush currents and excessive heat. Therefore, the use of leading-edge mode for LED lamps should be minimized. Always test in advance to ensure the connected load does not trigger overload or overtemperature protection.

2.2 Operation Modes

The dimming system supports leading-edge and trailing-edge dimming.

  1. Leading-edge dimming

    This mode uses leading-edge cut-off and trailing-edge conduction. The input voltage is chopped from the zero-crossing point, and voltage is applied only after the dimmer turns on. It is suitable for inductive loads.

图片11

  1. Trailing-edge dimming

    This mode uses leading-edge conduction and trailing-edge cut-off. The dimmer turns on at the zero-crossing point, so the voltage is very low at turn-on, avoiding inrush current to the load. There is no minimum load requirement, enabling better performance with single lamps or very small loads. This mode helps extend lamp life and reduces interference to the power grid. It is suitable for resistive and capacitive loads.