Power Supply | Bus voltage | 21-30V DC,via the KNX bus |
Bus current | <7.5mA/24V, <6.5mA/30V | |
Bus consumption | <195mW | |
Output | Dimming channel | 4 (separate phase connection) |
Max. load | 300W per channel (incandescent/ Halogen/ LED, trailing edge) | |
Rated voltage | 110~230 V AC (50/60HZ) | |
Standby loss | Approx. 0.7W | |
Load loss | ≤2W per channel | |
Connection | KNX | Bus connection terminals, 0.8 mm Ø |
Outputs | Screw terminals | |
Wire Range | 0.2—6.0mm2 | |
Environment | Storage | –25 °C ~ + 55 °C |
Working Temperature | –5 °C ~ + 45 °C | |
Working Humidity | 0~93%RH (non-condensing) | |
Installation | 35mm DIN rail | |
2.1 Supported Loads
2.1.1 Maximum Load Capacity per Channel
Load Type | Max. Load capacity (110V) | Max. Load capacity (230V) | ||
Leading Edge | Trailing Edge | Leading Edge | Trailing Edge | |
Incandescent Lamp | 10~150W | 10~150W | 10~300W | 10~300W |
High-Voltage Halogen Lamp | 10~150W | 10~150W | 10~300W | 10~300W |
Low-Voltage Halogen Lamp with Electronic Transformer | 10~150W | 10~150W | 10~300W | 10~300W |
High-Voltage LED | 2~30W | 2~150W | 2~60W | 2~300W |
Low-Voltage LED with Electronic Transformer | 2~40W | 2~150W | 2~80W | 2~300W |
Low-Voltage LED with Constant Current Driver (Down light, Spotlight) | 2~40W | 2~150W | 2~80W | 2~300W |
Low-Voltage LED with Constant Voltage Driver | 2~40W | 2~150W | 2~80W | 2~300W |
Resistive Load |
| |||
Capacitive Load |
| |||
Inductive Load |
| |||
| ||||
2.1.2 Parallel Output Load Capacity
The 4-gang dimmer supports independent or parallel outputs. Parallel output increases load capacity.
Load Type | Max. Load Capacity (110V) | |||||
Parallel with 2 Channels | Parallel with 3 Channels | Parallel with 4 Channels | ||||
Leading Edge | Trailing Edge | Leading Edge | Trailing Edge | Leading Edge | Trailing Edge | |
Incandescent Lamp | 300W | 300W | 400W | 400W | 500W | 500W |
High-Voltage Halogen Lamp | 300W | 300W | 400W | 400W | 500W | 500W |
Low-Voltage Halogen Lamp with Electronic Transformer | 300W | 300W | 400W | 400W | 500W | 500W |
High-Voltage LED | - | 300W | - | 400W | - | 500W |
Low-Voltage LED with Electronic Transformer | - | 300W | - | 400W | - | 500W |
Low-Voltage LED with Constant Current Driver (Down light Spotlight) | - | 300W | - | 400W | - | 500W |
Low-Voltage LED with Constant Voltage Driver | - | 300W | - | 400W | - | 500W |
Load Type | Max. Load Capacity (230V) | |||||
Parallel with 2 Channels | Parallel with 3 Channels | Parallel with 4 Channels | ||||
Leading Edge | Trailing Edge | Leading Edge | Trailing Edge | Leading Edge | Trailing Edge | |
Incandescent Lamp | 500W | 500W | 750W | 750W | 1000W | 1000W |
High-Voltage Halogen Lamp | 500W | 500W | 750W | 750W | 1000W | 1000W |
Low-Voltage Halogen Lamp with Electronic Transformer | 500W | 500W | 750W | 750W | 1000W | 100W |
High-Voltage LED | - | 500W | - | 750W | - | 1000W |
Low-Voltage LED with Electronic Transformer | - | 500W | - | 750W | - | 1000W |
Low-Voltage LED with Constant Current Driver (Down light,Spotlight) | - | 500W | - | 750W | - | 1000W |
Low-Voltage LED with Constant Voltage Driver | - | 500W | - | 750W | - | 1000W |
NOTE:
For the same output channel, capacitive and inductive loads must not be connected together. Mixing capacitive + resistive or inductive + resistive loads is allowed, but power derating must be considered. It is strongly recommended to connect the same load type to each output channel.
The maximum load capacity mainly depends on the lamp’s inrush current and power loss. In leading-edge mode, these loads—especially LED lamps—can generate high inrush currents and excessive heat. Therefore, the use of leading-edge mode for LED lamps should be minimized. Always test in advance to ensure the connected load does not trigger overload or overtemperature protection.
2.2 Operation Modes
The dimming system supports leading-edge and trailing-edge dimming.
Leading-edge dimming
This mode uses leading-edge cut-off and trailing-edge conduction. The input voltage is chopped from the zero-crossing point, and voltage is applied only after the dimmer turns on. It is suitable for inductive loads.

Trailing-edge dimming
This mode uses leading-edge conduction and trailing-edge cut-off. The dimmer turns on at the zero-crossing point, so the voltage is very low at turn-on, avoiding inrush current to the load. There is no minimum load requirement, enabling better performance with single lamps or very small loads. This mode helps extend lamp life and reduces interference to the power grid. It is suitable for resistive and capacitive loads.