Fig.5.3 "Output setting" Interface
Device type
Displays the device type according to the actual product application: 4-Fold
A corresponding wiring preview diagram of the product is shown below the parameter.
Dimming channels
Sets the dimming channels. For the dimmer with multiple channels, individual or parallel channels can be configure. Parallel channels can expand the load capacity.
Options:
Individual
Parallel (A+B) and Parallel (C+D)
Parallel (A+B) and Individual (C, D)
Individual (A, B) and Parallel (C+D)
Parallel (A+B+C) and Individual (D)
Individual (A) and Parallel (B+C+D)
Parallel (A+B+C+D)
Channel A/B/C/D/A+B/...
For the dimmer with multiple channels, these parameters are visible depends on the previous parameter. Set whether to enable dimming channel, and corresponding window is visible when enabled.
Configuration of individual channel is as same as the parallel channel, the following is an example of Channel A.
5.3.1 Parameter Setting Interface “Channel”

Fig.5.3.1(1) "Channel" Interface

Fig.5.3.1(2) "Channel" Interface
Description (max 30char.)
Sets the name description of the channel.
Load type
Sets the load type of the channel.
Options:
Resistive&Capacitive load (trailing edge)
Inductive load (leading edge)
LED (trailing edge)
LED (leading edge)
Dimming curve
Sets dimming cure of the channel. A corresponding curve is shown below the parameter.
Options:
Logarithmic function |
| Cubic function |
|
Root function |
| Exponential function |
|
Linear function |
| User defined | |
Quadratic function |
|
TIP:
When User defined is selected, users can customize the dimming curve. For details, see Section 5.3.2.
General dimming time (from min. to max.)
This parameter is for setting the time for the whole dimming process, which refers to the time from minimum to maximum value. Suppose the time is set as 6s, the min. Value is 0% and the max. is 100%, if the brightness is only dimmed from 0% to 50%, then the dimming time only takes 3s.
Options: 2...255 s
If the channel function has not specified a dimming time, use the time set by this parameter, functions such as switch on/off lamps, forced, safety, staircase lighting, threshold, etc.
Minimum brightness value
Maximum brightness value
These parameters are for setting minimum and maximum brightness values individually, to limit the output range of dimming brightness, which is allow the lamps work in a better brightness range depending on the environment or lamps compatibility.
This range is not allowed to be exceeded in any status of lamps on, including threshold, forced, safety functions, etc. Output as min. value when the brightness is lower than the min., and output as max. value when it is higher than the max.
Options of the min. value:
1...49 %;
Options of the max. value:
50...100 %
Switching on value
This parameter is for setting the brightness when the lamp is switched on.
Options:
Preset brightness value
Last brightness value: When the device is powered on for the first time or restarted after downloading, the default value for ”Switch ON” is 50%, meaning the brightness value is 50%.
The following parameter is visible when previous parameter is selected "Preset brightness value".
Preset brightness value
Set the preset brightness value.
Options: 1...100 %
Dimming mode selection for switching on
This parameter is for setting the dimming mode when the lamp is switched on.
Options:
Jumping: Switch on immediately and directly to the target brightness.
Dimming: Switch on with dimming to the target brightness and use the General dimming time.
Dimming mode selection for switching off
This parameter is for setting the dimming mode when the lamp is switched off.
Options:
Jumping: Switch off immediately.
Dimming: Switch off with dimming and use the General dimming time.
Dimming time for relative dimming
This parameter is for setting the time for the whole relative dimming process.
Options: 2...255 s
Dimming time for absolute dimming
This parameter is for setting the time for the whole absolute dimming process. Options: 2...255 s
Allow switch off via relative dimming
This parameter is for setting whether allow to switch lamp off via relative dimming. When disabled, it can only be adjusted downward to the minimum brightness value; while enabled, switch the lamp off directly when the brightness is dimming to less than the minimum brightness value.
Absolute dimming value lower than the minimum value
This parameter is for setting the behaviour when absolute dimming value lower than the minimum value, it only affects the object "Absolute dimming".
Options:
0%=0%, otherwise=Minimum brightness value: Output as min. value when the value is lower than the min., but the value is 0% is to switch the lamp off.
To be the minimum brightness value: Output as min. value when the value is lower than the min., even if the value is 0%.
To be 0%: Switch the lamp off directly when the value is lower than the min
Additional startup characteristic when the lamp is off
This parameter is for setting whether the lamp needs the startup characteristic additionally when the lamp is off. Some lamps require a higher voltage to start up when switched off.
The following four parameters are visible when the previous parameter is enabled.
Startup brightness value
This parameter is for setting the brightness value of lamp startup.
Options: 5..90 %
NOTE:
The brightness must not exceed the max. and min. value, otherwise it cannot be set in the ETS.
Behavior for dimming up
This parameter is for setting the behavior for dimming up when the lamp is off.
Options:
Ignore the telegram: Feed back an off telegram immediately to synchronize the status with the control device.
Like normal: Dim up and output normally.
Dim up based on the startup brightness: Use the startup brightness as a based point, and dimming up from this brightness.
Behavior when the switch or dimming value is lower than startup value
This parameter is for setting the behavior when the target brightness is lower than startup value, and the lamp is off.
Options:
Ignore the telegram: Feed back a off telegram immediately to synchronize the status with the control device.
Like normal: Dim and output normally.
Jump to startup brightness: Jump to the startup brightness immediately and feed back the new brightness to the bus.
Jump to startup then delay to target: Jump to startup brightness firstly then dimming to the target brightness after the delay has elapsed
NOTE:
If the target brightness is higher than startup value, dimming from the startup value to the target brightness directly, it is only applied to receive the telegrams of objects "Switching" and "Absolute dimming".
Delay time after reach startup
This parameter is visible when previous parameter is selected "Jump to startup then delay to target". Set the delay time for dimming to target brightness after reaching the startup value.
Options:
50ms
80ms
100ms
...
2s
4s
5s
Reset Behavior
Behavior after download
This parameter is for setting the behaviour of channel after download.
Options:
Switching off
Preset brightness value: Dim to a setting brightness, defined by next parameter.
Brightness before bus failure: Recover to the brightness value stored when the bus failure.
The following parameter is visible when "Preset brightness value" is selected.
Preset brightness value
Sets the preset brightness value.
Options: 1...100 %
Behavior after bus failure
This parameter is for setting the behaviour of channel after bus failure.
Options:
Switching off
Preset brightness value: Dim to a setting brightness, defined by next parameter.
No reaction
Preset brightness value
This parameter is visible when "Preset brightness value" is selected. Set the preset brightness value.
Options: 1...100 %
Behavior after bus recovery
This parameter is for setting the behaviour of channel after bus recovery.
Options:
Switching off
Preset brightness value: Dim to a setting brightness, defined by next parameter.
Brightness before bus failure: Recover to the brightness value stored when the bus failure.
The following parameter is visible when "Preset brightness value" is selected.
Preset brightness value
Sets the preset brightness value.
Options: 1...100 %
Short-circuit detect for operating supply or device reset if output is off
This parameter is for setting whether detect short-circuit for operating supply or device reset if output is off.
When disabled, a short-circuit may be detected only when turn on the lamp until exceed the threshold of short-circuit detection.
When enabled, every time a operating supply or device voltage recovery, it needs to detect a short-circuit firstly if initially the lamp is off or the brightness is lower than the threshold of short-circuit detection, but it is not required to detect if the brightness is higher than the threshold of short-circuit detection. Download database and restart, if the detection has been normal before the download, there is no need to repeat the detection, otherwise it is still necessary to perform a detection.

Central Control
Central control is used to control the switching and dimming of all channels, each channel can be configured to support central control or not. When receive the telegram of central control from bus, control the outputs centrally for the supported channels.
NOTE:
Central control function only applies for 2/4-Fold Dimmers, and it is not supported by 1-Fold Dimmer.
Switching
This parameter is for setting whether control switch centrally.
Relative dimming
This parameter is for setting whether control relative dimming centrally.
Absolute dimming
This parameter is for setting whether control absolute dimming centrally.
Status Feedback
Switching/ Brightness value/ Short-circuit/ Over-voltage/ Over-temperature/ Operating voltage failure
These parameters are for setting the way to feed back the status of switch, brightness and abnormal status. The abnormal status including short-circuit, over-voltage, over-temperature, operating voltage failure.
Options:
Respond after read only
Respond after change
Handling of abnormal status:
Trigger hardware protection when channel load terminal is short-circuited, and feed back the status to bus. It will disconnect the output when in protection. If it is the first time a short-circuit has been detected since power on, disconnect the output first then wait a 1 minute to output the current control value again; but if there is still a short-circuit, disconnect the output permanently, and cannot be used unless the device is restarted.
Trigger hardware protection when the operated voltage is higher than the rated voltage, and feed back the status to bus. It will disconnect the output when in protection.
When the measured internal temperature exceeds 90℃ for 10s, then will trigger over-temperature protection and send the status to bus. The brightness will down to 20% or to the minimum value under the protection status. After the temperature is reduced to below 70℃, output normally if a new control telegram is received.
Operation voltage is failure when no valid over-zero signal is detected, and feed back the status to bus. When in voltage failure, it can not feed back control status and no drive signal if receive the control telegram, need to power supply normally and has actual output value can feed back the current status of the lamp.
Extension Function
Scene function
Sets whether the scene function interface is visible after this parameter enabled.
Time function
Sets whether the time function interface is visible after this parameter enabled.
Threshold function
Sets whether the threshold function interface is visible after this parameter enabled.
Forced function
Sets whether the forced function interface is visible after this parameter enabled.
Safety function
Sets whether the safety function interface is visible after this parameter enabled.
Operating hours counter
Sets whether the operating hours counter interface is visible after this parameter enabled.
5.3.2 Parameter Setting Interface “User defined dimming curve”

Fig.5.3.2 “User defined dimming curve" Interface
Number of curve coordinate points
This parameter is for setting the number of curve coordinate points.
Options: 2...16
Coordinate point x (x=1~16)
KNX dimming value
This parameter is for setting KNX dimming value of the curve.
Options: 1..100%
For user defined dimming curve, the first and the last one points are fixed to 1% and 100%.
NOTE:
The previous KNX dimming value must be small than next one, otherwise it can not be set on the ETS:
Output value
This parameter is for setting the output value corresponding to the KNX dimming value.
Options: 1..100%
NOTE:
The previous output value must be small than next one, otherwise it can not be set on the ETS:
Custom curves with different number of coordinate points, as shown as following:
Example 1 (3 coordinate points) | Example 2 (4 coordinate points) | Example 3 (5 coordinate points) | Example 4 (6 coordinate points) |
|
|
|
|
Commissioning Steps of User Defined Dimming Curve:
Step 1: Use the linear function curve at first to determine the adjustable range, then obtain the minimum and maximum adjustable brightness values of the applied lamp with absolute dimming.
Step 2: When testing in step 1, you can experience the brightness changes with relative dimming, then checking the number of curve areas and coordinate points.
Step 3: The minimum brightness value is the point of knx value 1%, the maximum brightness value is the point of knx value 100%.
Step 4: Add the coordinate points of the middle section according to the planning area.
Step 5: Download and commission, according to the experience of dimming process, there may also be slight adjustment of the coordinate points or increase the configuration areas, and even need to adjust the dimming time, until achieve the best results for user satisfaction.
5.3.3 Parameter Setting Interface “Extension function”
Parameter setting interfaces are visible according to the enabling of the extension function parameters.
5.3.3.1 Parameter Setting Interface “Scene function”

Fig.5.3.3.1 “Scene function” Interface
Scene function can work with the control panel or other software to execute the setting scene and output the specified brightness.
Overwrite scene stored values during download
This parameter is for setting whether to override the scene stored values during application download. If select to overwrite, follow the parameter setting, otherwise for the brightness value corresponding to the scene number that has saved the modified value has executed, the last saved value will remain; for the modified brightness has not executed, still use the value set by parameter.
Scene x (x=1~16)
Description
This parameter is for setting the name description of the corresponding scene, up to 30 characters.
Scene NO.
This parameter is for setting the triggered scene number, up to 16 scenes.
Options: 0...64
When scene number is 0, it is invalid, and the brightness and dimming time cannot be set, as shown as following:

When scene numbers are greater than 0, if there are same scene numbers, display following error message:

Brightness
This parameter is for setting the brightness of the corresponding scene.
Options: 0...100 %
Dimming
This parameter is for setting the dimming time of the corresponding scene.
Options: 2...255 s
5.3.3.2 Parameter Setting Interface “Time function”

Delay switch

Flash switch

Staircase lighting
Fig.5.3.3.2 "Time function" Interface
Different configurations of time function can be used for different application.
Time function
This parameter is for setting the time function, its brightness is depending on the value of switch on/off.
Options:
Delay switch: Delay a period time to switch on/off, dimming mode is Jumping.
Flashing switch: Flash to switch on/off, dimming mode is Jumping.
Staircase lighting: Dimming mode is Jumping, use the General dimming time.
NOTE:
Time function will be interrupted directly after entering safety or forced operation.
The following parameters are visible when "Delay switch" is selected.
Delay for switch on
Delay for switch off
Configure the delayed switch function for dimming output (delay on/off). The switch operation received from the bus is executed only after the delay. If the same telegram is received during the delay, the timer restarts.
Options: 00:00:00 ...23h:59min:59s
The following parameters are visible when “Flashing switch" is selected.
Parameter “On time for flashing"
Parameter “Off time for flashing"
Set the duration time of flashing for switch on/off.
Options: 00:00:05s ...23h:59min:59s
Number of flashing cycles [0..10000,0=no limit]
Sets the number of flashing cycles, a cycle includes an on and an off. 0 means the cycles is no limited.
Options: 0...10000
Status after flashing
Sets the status after flashing.
Options:
Switching off
Switching on
Unchange
NOTE:
When “Switching on” or “Switching off” is selected, the output may perform an additional action for up to half a cycle.
Control mode of flashing
Sets the control mode of flashing.
Options:
Start with"1", Stop with "0": It will start flashing with value "1" and stop flashing with "0", action to the end status when stopped, which is defined via previous parameter.
Start with"0", Stop with "1": It will start flashing with value "0" and stop flashing with "1", action to the end status when stopped, which is defined via previous parameter.
Start with"0/1", can not be stopped: It will start flashing with value "0" or "1", and can not stop until the number of the flashing cycles is exhausted, or stop via the interruption from other operation.
The following parameters are visible when "Staircase lighting" is selected.
Duration time
Sets the duration time of staircase lighting switch on, and switch off automatically after the time has elapsed.
Options: 00:00:05s ...23h:59min:59s
Time extension
Sets whether to retrigger or extend the duration time when receive an on telegram during the time.
Options:
Not retriggerable: Ignore the telegram, switch off automatically after the time has elapsed.
Retriggerable: Retrigger the duration time when receive an on telegram during the time.
Extend duration time: Extends the remaining duration. When a new “staircase light ON” telegram is received, the remaining countdown is added to the configured duration. For example: if the duration is set to 60 s and 40 s remain, receiving a new ON telegram will extend the remaining time to 40 s + 60 s = 100 s. The staircase light will turn off automatically after 100 s. If multiple ON telegrams are received consecutively, the duration will continue to accumulate until it reaches the configured maximum limit.
Control mode of staircase lighting
Sets the control mode of staircase lighting.
Options:
Start with"1", Stop with "0": It will switch on the staircase light with the value "1" and stop the timing with "0", keep the current lamps status until it is changed by other operations.
Start with"1", no reaction with "0": It will switch on the staircase lights with the value "1" and no reaction with "0".
Start with"0/1", can not be stopped: it will switch on the staircase lights with the value "1" or "0", and can not stop until the duration time is exhausted, or stop via the interruption from other operation.
Start with"1", Off with "0": It will switch on the staircase lights with the value "1" and switch off with "0".
Prewarning before staircase time end
Sets whether to prewarn before staircase light time end, and sets the prewarning mode. User can be noticed before the staircase light time is about to finish.
Options:
No: No prewarn, and switch off automatically after the time has elapsed.
No, but dim-down the dimming value after end: No prewarn, but dim down the brightness after the time has elapsed.
Via object: Prewarn via the object.
Via flashing switching on-off: Prewarn via a short flashing, 1s to switch on and 1s to switch off, dimming mode is Jumping.
Via flashing switching on-off and object: prewarn, refer to the explanation of the previous options.
Dim-down the dimming value: Prewarn via dimming down the brightness.
Dim-down the dimming value and via object: Dim-down the dimming value and via object: prewarn, refer to the explanation of the previous options.
The following parameter is visible when the selection does not contains "No...".
√ Warning time
Sets the time of prewarning.
Options: 00:00:05s...00h:59min:59s
NOTE:
The warning time must be less than the duration time, or it cannot set on the ETS.
NOTE:
The warning time is contained in the startup time of staircase lighting. If switch off before the warning time, there is no prewarning.
The following parameter is visible when the selection contains “Dim-down the dimming value....".
√ Value of dimming down
Sets the brightness value of dimming down at the end of the staircase lighting.
Options: 1...100 %
Duration time can be changed via bus
Sets whether the duration time can be changed via bus. Store the modified value when bus failure, recovery to the value set by parameter after download.

5.3.3.3 Parameter Setting Interface “Threshold function”

Fig.5.3.3.3 "Threshold function" Interface
Switch on/off or dimming the brightness according to telegram from the bus and threshold set on the ETS.
NOTE:
The brightness of threshold function is depending on the value of switch on/off.
Threshold value datatype
This parameter is for setting the threshold value datatype.
Options:
1byte unsigned value (DPT5.010)
1byte percentage (DPT5.001)
Temperature (DPT9.001)
Illuminance (DPT9.004)
Threshold value 1
Threshold value 2
These two parameters are for setting the threshold value 1 and 2. Options are display according to the threshold value datatype.
When “1byte unsigned value” is selected:
options: 0...255
When “1byte percentage” is selected:
options: 0...100 %
When “Temperature” is selected:
options: -20...95 °C
When “Illuminance” is selected:
options: 0...65535 lux
NOTE:
The threshold 1 must be less than threshold 2, or they cannot be set on the ETS, as shown as following:
Threshold value can be changed via bus
This parameter is for setting whether the threshold 1 and 2 can be changed via bus.
Store the modified value when bus failure, recovery to the value set by parameter after download.
Threshold behavior
This parameter is for setting whether the threshold 1 and 2 with hysteresis.
Options:
Without hysteresis
With hysteresis
The hysteresis can avoid the unnecessary behaviour caused by the input value if the value is between two threshold values.
Output type
This parameter is for setting the output type after threshold comparison.
Options:
Switching
Brightness value
If input value<=threshold value 1
Sets the output value when input value is less than or equal to the threshold 1. Following parameter and its options are displayed according to the output type.
The following parameter is visible when "Switching" is selected.
Output is
Options:
Switching off
Switching on
Unchange
The following parameter is visible when "Brightness value" is selected.
Dimming value is
Options: 0...100 %
If threshold value 1<input value<threshold value 2
Sets the output value when input value is between the threshold 1 and 2. Output parameter and its options are displayed according to the output type, as above explanation.
NOTE:
When with hysteresis, the output is only Unchange.
If input value>=threshold value 2
Sets the output value when input value is greater than the threshold 2. Output parameter and its options are displayed according to the output type, as above explanation.
5.3.3.4 Parameter Setting Interface “Forced function”

1bit

2bit
Fig.5.3.3.4 "Forced function" Interface
The lamp can be forcibly fixed at a brightness in some special situations. Forced function has the highest priority. Ignore the normal control telegram received from bus when during in forced or safety operation.
Forced operation datatype
This parameter is for setting the datatype of forced operation.
Options:
1bit
2bit
The following parameters are visible when “Forced operation datatype” is set to “1bit”.
Forced operation at object value
Sets the object value for activating or canceling the forced.
Options:
0=Forced/1=Cancel
1=Forced/0=Cancel
Behavior at forced operation
Sets the behavior for forced operation.
Options:
Switching off
Preset brightness value
Unchange
The following parameter is visible when "Preset brightness value" is selected.
√ Preset brightness value
Sets the preset brightness value.
Options: 1...100 %
The following parameters are visible when “Forced operation datatype” is set to “2bit”.
Behavior at forced operation "switch on"
Sets the behavior at forced operation “switch on" when receive telegram value 3 from 2bit.
Options:
Preset brightness value
Unchange
√ Preset brightness value
This parameter is visible when "Preset brightness value" is selected. Set the preset brightness value.
Options: 1...100 %
Behavior at forced operation "switch off"
Sets the behavior at forced operation "switch off" when receive telegram value 2 from 2bit.
Option is:
only Switching off
Behavior at end of forced operation
Defines the output behavior when the forced operation is canceled.
Options:
Switching off
Preset brightness value
Unchange
NOTE:
For 2-bit objects, receiving telegram 0 or 1 cancels the forced operation.
When a cancel telegram is received, it is considered valid only if the forced operation was previously active; otherwise, the telegram is ignored.
If the cancel telegram is valid and another higher-priority function (e.g. safety operation) is active, the device follows that priority behavior and ignores the forced-operation cancel action. Otherwise, the device executes the output behavior defined by this parameter.
The following parameter is visible when "Preset brightness value" is selected.
Preset brightness value
Sets the preset brightness value.
Options: 1...100 %
NOTE:
When a cancel telegram is received, it is considered valid only if the forced operation was previously active; otherwise, the telegram is ignored.
If the cancel telegram is valid and another higher-priority function (e.g. safety operation) is active, the device follows that priority behavior and ignores the forced-operation cancel action. Otherwise, the device executes the output behavior defined by this parameter.
5.3.3.5 Parameter Setting Interface “Safety function“

Fig.5.3.3.5 "Safety function" Interface
Safety function can work with external sensor and perform dimming behaviour in some emergency situations. Safety function has the second highest priority and only lower than forced function.
Behavior at safety operation
Behavior at end of safety operation
Define the behavior for activating or canceling the safety operation.
Options:
Switching off
Preset brightness value
Unchange
The following parameter is visible when "Preset brightness value" is selected.
Parameter "Preset brightness value"
Defines the preset brightness value.
Options: 1...100 %
5.3.3.6 Parameter Setting Interface “Operating hours counter”

Fig.5.3.3.6 “Operating hours counter” Interface
Operating hours counter
Enables/disables the operating hours counter and defines the counter type. The counter records the ON time of a dimming channel. Counting starts when the brightness value is greater than 0. The counter can operate in seconds or hours.
Options:
Inactive
Value in s (DPT 13.100)
Value in h (DPT 7.007)
The following parameters are visible when “Operating hours counter” is activated.
Send counter value in second [0..65535]
Visible when Value in s (DPT 13.100) is selected. Sets the interval for sending the ON-time counter value to the bus (e.g. 3600 s = send every 3600 s).
Options: 60...65535 s
≡
Send counter value in hours [0..255]
Visible when Value in h (DPT 7.007) is selected. Sets the interval for sending the ON-time counter value to the bus (e.g. 1 h = send every hour).
Options: 1...255
Monitoring operation hours
Enables/disables operating-hours monitoring to supervise the channel ON time. When the operating time approaches the lamp lifetime, a status message is sent to remind lamp replacement.
The following parameters are visible when “Monitoring operation hours” is enabled:
Threshold for operation hours
Sets the operating-time threshold, typically based on lamp lifetime. The range depends on the counter type:
Value in s (DPT 13.100)”: 100...2147483647 s
Value in h (DPT 7.007)”: 1...65535 h
Send status cyclical [0..255,0=inactive]
Sets the interval for cyclically sending the status message; 0 disables cyclic sending. Send-on-change remains enabled.
Options: 0...255 min